The active power consumption of the input feed. A non-
negative value indicates the active power consumption in
Watts. A negative value indicates that the active power
consumption was not available.
Parsed from file Sentry3_SMIv1.mib.txt
Company: None
Module: Sentry3-MIB
The active power consumption of the input feed. A non-
negative value indicates the active power consumption in
Watts. A negative value indicates that the active power
consumption was not available.
Parsed from file Sentry3-MIB.mib
Module: Sentry3-MIB
Vendor: Server Technology, Inc.
Module: Sentry3-MIB (Sentry3_SMIv1.mib)
Type: TABULAR
Access: read-only
Syntax: INTEGER
Automatically extracted from www.mibdepot.com
infeedPower OBJECT-TYPE SYNTAX INTEGER(-1..15000) UNITS "Watts" MAX-ACCESS read-only STATUS current DESCRIPTION "The active power consumption of the input feed. A non- negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available." ::= { infeedEntry 12 }
infeedPower OBJECT-TYPE SYNTAX INTEGER(-1..15000) UNITS "Watts" MAX-ACCESS read-only STATUS current DESCRIPTION "The active power consumption of the input feed. A non- negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available." ::= { infeedEntry 12 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.1718.3.2.2.1.1 | infeedIndex | 0 | 0 | Index for the input feed table. |
1.3.6.1.4.1.1718.3.2.2.1.2 | infeedID | 0 | 0 | The ID of the input feed. |
1.3.6.1.4.1.1718.3.2.2.1.3 | infeedName | 0 | 0 | The name of the input feed. |
1.3.6.1.4.1.1718.3.2.2.1.4 | infeedCapabilities | 0 | 0 | The capabilities of the input feed. |
1.3.6.1.4.1.1718.3.2.2.1.5 | infeedStatus | 0 | 0 | The status of the input feed. If the infeedCapabilities 'onSense' bit is TRUE, then all of the states are supported and indicate… |
1.3.6.1.4.1.1718.3.2.2.1.6 | infeedLoadStatus | 0 | 0 | The status of the load measured on the input feed. If the infeedCapabilities 'loadSense' bit is TRUE, then all of the states are… |
1.3.6.1.4.1.1718.3.2.2.1.7 | infeedLoadValue | 0 | 0 | The load measured on the input feed. A non-negative value indicates the measured load in hundredths of Amps. A negative value i… |
1.3.6.1.4.1.1718.3.2.2.1.8 | infeedLoadHighThresh | 0 | 0 | infeedLoadHighthresh |
1.3.6.1.4.1.1718.3.2.2.1.9 | infeedOutletCount | 0 | 0 | The number of outlets on the input feed. |
1.3.6.1.4.1.1718.3.2.2.1.10 | infeedCapacity | 0 | 0 | The load capacity of the input feed. A non-negative value indicates the maximum load in Amps. A negative value indicates that t… |
1.3.6.1.4.1.1718.3.2.2.1.11 | infeedVoltage | 0 | 0 | The voltage of the input feed. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that t… |
1.3.6.1.4.1.1718.3.2.2.1.13 | infeedApparentPower | 0 | 0 | The apparent power consumption of the input feed. A non- negative value indicates the apparent power consumption in Volt-Amps. … |
1.3.6.1.4.1.1718.3.2.2.1.14 | infeedPowerFactor | 0 | 0 | The power factor of the input feed. A non-negative value indicates the power factor in hundredths. A negative value indicates t… |
1.3.6.1.4.1.1718.3.2.2.1.15 | infeedCrestFactor | 0 | 0 | The crest factor for the load of the input feed. A non- negative value indicates the crest factor in tenths. A negative value i… |
1.3.6.1.4.1.1718.3.2.2.1.16 | infeedEnergy | 0 | 0 | The energy consumption of the input feed. A non-negative value indicates the energy consumption in Watt-Hours. A negative value… |
1.3.6.1.4.1.1718.3.2.2.1.17 | infeedReactance | 0 | 0 | infeedReactance OBJECT-TYPE SYNTAX INTEGER { unknown(0), capacitive(1), inductive(2), resistive(3) } MAX-ACCESS read-only STATU… |
1.3.6.1.4.1.1718.3.2.2.1.18 | infeedPhaseVoltage | 0 | 0 | infeedPhaseVoltage OBJECT-TYPE SYNTAX INTEGER(-1..2640) UNITS "tenth Volts" MAX-ACCESS read-only STATUS current DESCRIPTION "Th… |
1.3.6.1.4.1.1718.3.2.2.1.19 | infeedPhaseCurrent | 0 | 0 | infeedPhaseCurrent OBJECT-TYPE SYNTAX INTEGER(-1..25500) UNITS "hundredth Amps" MAX-ACCESS read-only STATUS current DESCRIPTION… |
1.3.6.1.4.1.1718.3.2.2.1.20 | infeedCapacityUsed | 0 | 0 | infeedCapacityUsed OBJECT-TYPE SYNTAX INTEGER(-1..1500) UNITS "tenth percentage" MAX-ACCESS read-only STATUS current DESCRIPTIO… |
1.3.6.1.4.1.1718.3.2.2.1.21 | infeedLineID | 0 | 0 | infeedLineID OBJECT-TYPE SYNTAX DisplayString(SIZE(0..4)) MAX-ACCESS read-only STATUS current DESCRIPTION "The ID of the input … |
1.3.6.1.4.1.1718.3.2.2.1.22 | infeedLineToLineID | 0 | 0 | infeedLineToLineID OBJECT-TYPE SYNTAX DisplayString(SIZE(0..7)) MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-li… |
1.3.6.1.4.1.1718.3.2.2.1.23 | infeedPhaseID | 0 | 0 | infeedPhaseID OBJECT-TYPE SYNTAX DisplayString(SIZE(0..6)) MAX-ACCESS read-only STATUS current DESCRIPTION "The ID of the input… |
1.3.6.1.4.1.1718.3.2.2.1.24 | infeedVACapacity | 0 | 0 | infeedVACapacity OBJECT-TYPE SYNTAX INTEGER(-1..25000) UNITS "Volt-Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "The a… |
1.3.6.1.4.1.1718.3.2.2.1.25 | infeedVACapacityUsed | 0 | 0 | infeedVACapacityUsed OBJECT-TYPE SYNTAX INTEGER(-1..1500) UNITS "tenth percentage" MAX-ACCESS read-only STATUS current DESCRIPT… |