airFMSysDemands OBJECT IDENTIFIER ::= { airFMSystem 2 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airFMSysDemands OBJECT IDENTIFIER ::= { airFMSystem 2 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.2.1 | airFMSysDXCoolingDmd | 1 | 1 | The direct expansion cooling output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID … |
1.3.6.1.4.1.318.1.1.13.1.4.2.2 | airFMSysDXDehumDmd | 1 | 1 | The direct expansion dehumidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that … |
1.3.6.1.4.1.318.1.1.13.1.4.2.3 | airFMSysDXActualCoolDehum | 1 | 1 | The direct expansion cooling or dehumidification output measured by the System. Measured in percent. A value of -2147483648 indi… |
1.3.6.1.4.1.318.1.1.13.1.4.2.4 | airFMSysCoilFluidCoolDmd | 1 | 1 | The fluid coil cooling output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not… |
1.3.6.1.4.1.318.1.1.13.1.4.2.5 | airFMSysCoilFluidDehumDmd | 1 | 1 | The fluid coil dehumidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that this O… |
1.3.6.1.4.1.318.1.1.13.1.4.2.6 | airFMSysCoilFluidActualCoolDehum | 1 | 1 | The fluid coil cooling or dehumidification output measured by the System. Measured in percent. A value of -2147483648 indicates … |
1.3.6.1.4.1.318.1.1.13.1.4.2.7 | airFMSysElectricReheatDmd | 1 | 1 | The electric reheating output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not… |
1.3.6.1.4.1.318.1.1.13.1.4.2.8 | airFMSysActualElectricReheat | 1 | 1 | The electric reheating output of the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to… |
1.3.6.1.4.1.318.1.1.13.1.4.2.9 | airFMSysSteamHotGasReheatDmd | 1 | 1 | The steam, hot water, or hot gas reheating output demanded by the System. A value of notApplicable indicates that this OID does no… |
1.3.6.1.4.1.318.1.1.13.1.4.2.10 | airFMSysActualSteamHotGasReheat | 1 | 1 | The steam, hot water, or hot gas reheating output of the System. A value of notApplicable indicates that this OID does not apply t… |
1.3.6.1.4.1.318.1.1.13.1.4.2.11 | airFMSysSteamElectrodeHumDmd | 1 | 1 | The steam electrode humidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that thi… |
1.3.6.1.4.1.318.1.1.13.1.4.2.12 | airFMSysActualSteamElectrodeHum | 1 | 1 | The average steam electrode humidification output measured for the Modules in the System. Measured in percent. A value of -214748… |
1.3.6.1.4.1.318.1.1.13.1.4.2.13 | airFMSysSteamHumDmd | 1 | 1 | The steam humidification output demanded by the System. A value of notApplicable indicates that this OID does not apply to this d… |
1.3.6.1.4.1.318.1.1.13.1.4.2.14 | airFMSysActualSteamHum | 1 | 1 | The steam humidification output for the System. A value of notApplicable indicates that this OID does not apply to this device du… |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.1 | airFMSysStatus | 25 | 50 | None |
1.3.6.1.4.1.318.1.1.13.1.4.3 | airFMSysSetup | 16 | 32 | None |
1.3.6.1.4.1.318.1.1.13.1.4.4 | airFMSysConfig | 10 | 20 | None |
1.3.6.1.4.1.318.1.1.13.1.4.5 | airFMSysCooling | 23 | 46 | None |
1.3.6.1.4.1.318.1.1.13.1.4.6 | airFMSysHumidify | 7 | 14 | None |
1.3.6.1.4.1.318.1.1.13.1.4.7 | airFMSysDehumidify | 9 | 18 | None |
1.3.6.1.4.1.318.1.1.13.1.4.8 | airFMSysReheat | 10 | 20 | None |
1.3.6.1.4.1.318.1.1.13.1.4.9 | airFMSysThresholds | 16 | 32 | None |
1.3.6.1.4.1.318.1.1.13.1.4.10 | airFMSysInputs | 2 | 10 | None |
1.3.6.1.4.1.318.1.1.13.1.4.11 | airFMSysOutputs | 2 | 7 | None |
1.3.6.1.4.1.318.1.1.13.1.4.12 | airFMSysAlarmMap | 6 | 126 | None |