airFMSysConfig OBJECT IDENTIFIER ::= { airFMSystem 4 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airFMSysConfig OBJECT IDENTIFIER ::= { airFMSystem 4 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.4.1 | airFMSysPrimaryControlSensor | 1 | 1 | Selects whether return or remote sensors will control the system. A value of notApplicable indicates that this OID does not apply … |
1.3.6.1.4.1.318.1.1.13.1.4.4.2 | airFMSysRemoteSensorData | 1 | 1 | Selects whether average temperature or max temperature will be used when remote sensors are selected for control of the system. A … |
1.3.6.1.4.1.318.1.1.13.1.4.4.3 | airFMSysFastStartup | 1 | 1 | Minimizes the time for the cooling process to begin after other delay constraints have been met. A value of notApplicable indicat… |
1.3.6.1.4.1.318.1.1.13.1.4.4.4 | airFMSysStartupDelay | 1 | 1 | Set the delay that begins when power is applied and ends when the System starts. This allows you to create a staged restart among… |
1.3.6.1.4.1.318.1.1.13.1.4.4.5 | airFMSysModeDelay | 1 | 1 | Set the delay between starting the blowers and engaging the modes. It allows the sensors to read room conditions accurately and a… |
1.3.6.1.4.1.318.1.1.13.1.4.4.6 | airFMSysCommLossShutdownDelay | 1 | 1 | Set the delay between an Expansion Module losing communication with the Main Module and the Expansion Module shutting down. A val… |
1.3.6.1.4.1.318.1.1.13.1.4.4.7 | airFMSysResetSysFailure | 1 | 1 | Setting this OID to reset(2) will allows the system to return from any failure condition, if the failure(s) have cleared. Getting … |
1.3.6.1.4.1.318.1.1.13.1.4.4.8 | airFMSysResetUserDflts | 1 | 1 | Setting this OID to reset(2) will reset all system parameters that can be edited by the user to their factory default values. Gett… |
1.3.6.1.4.1.318.1.1.13.1.4.4.9 | airFMSysResetFldSrvcDflts | 1 | 1 | Setting this OID to reset(2) will reset all system parameters that can only be edited by the field service engineer to their fact… |
1.3.6.1.4.1.318.1.1.13.1.4.4.10 | airFMSysResetRunHours | 1 | 1 | Setting this OID to reset(2) will reset the system Run Hours. Getting this OID will do nothing and return the noOperation(1) val… |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.1 | airFMSysStatus | 25 | 50 | None |
1.3.6.1.4.1.318.1.1.13.1.4.2 | airFMSysDemands | 14 | 28 | None |
1.3.6.1.4.1.318.1.1.13.1.4.3 | airFMSysSetup | 16 | 32 | None |
1.3.6.1.4.1.318.1.1.13.1.4.5 | airFMSysCooling | 23 | 46 | None |
1.3.6.1.4.1.318.1.1.13.1.4.6 | airFMSysHumidify | 7 | 14 | None |
1.3.6.1.4.1.318.1.1.13.1.4.7 | airFMSysDehumidify | 9 | 18 | None |
1.3.6.1.4.1.318.1.1.13.1.4.8 | airFMSysReheat | 10 | 20 | None |
1.3.6.1.4.1.318.1.1.13.1.4.9 | airFMSysThresholds | 16 | 32 | None |
1.3.6.1.4.1.318.1.1.13.1.4.10 | airFMSysInputs | 2 | 10 | None |
1.3.6.1.4.1.318.1.1.13.1.4.11 | airFMSysOutputs | 2 | 7 | None |
1.3.6.1.4.1.318.1.1.13.1.4.12 | airFMSysAlarmMap | 6 | 126 | None |