This sub-tree is used to register Liebert environmental configuration
object identifiers.
Parsed from file LIEBERT_GP_ENV.MIB.txt
Company: None
Module: LIEBERT-GP-ENVIRONMENTAL-MIB
This sub-tree is used to register Liebert environmental configuration
object identifiers.
Parsed from file LIEBERT-GP-ENVIRONMENTAL-MIB.mib
Module: LIEBERT-GP-ENVIRONMENTAL-MIB
Vendor: Emerson Computer PowerRoger Draper
Module: LIEBERT-GP-ENVIRONMENTAL-MIB
[Automatically extracted from oidview.com]
lgpEnvConfig OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental configuration object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Configuration Group." ::= { lgpEnvironmental 4 }
lgpEnvConfig OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental configuration object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Configuration Group." ::= { lgpEnvironmental 4 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.476.1.42.3.4.4.1 | lgpEnvConfigReheatLockout | 1 | 1 | If locked-out the reheats will not operate even if controller calls for its operation. |
1.3.6.1.4.1.476.1.42.3.4.4.2 | lgpEnvConfigHumLockout | 1 | 1 | If locked-out the humidifier will not operate even if controller calls for its operation. |
1.3.6.1.4.1.476.1.42.3.4.4.4 | lgpEnvConfigRestartDelay | 1 | 1 | When utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is rest… |
1.3.6.1.4.1.476.1.42.3.4.4.7 | lgpEnvConfigRemoteShutdown | 1 | 1 | When in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing. |
1.3.6.1.4.1.476.1.42.3.4.4.8 | lgpEnvConfigCoolingServiceInterval | 1 | 1 | The amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this v… |
1.3.6.1.4.1.476.1.42.3.4.4.9 | lgpEnvConfigHumidifierServiceInterval | 1 | 1 | The amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this va… |
1.3.6.1.4.1.476.1.42.3.4.4.10 | lgpEnvConfigFilterServiceInterval | 1 | 1 | The amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this val… |
1.3.6.1.4.1.476.1.42.3.4.4.11 | lgpEnvConfigSleepModeDeadbandRangeDegC | 1 | 1 | The allowable deviation above and below the temperature set point used to create a no control region, a deadband, where heating… |
1.3.6.1.4.1.476.1.42.3.4.4.12 | lgpEnvConfigSleepModeDeadbandRangeDegF | 1 | 1 | The allowable deviation above and below the temperature set point used to create a no control region, a deadband, where heating… |
1.3.6.1.4.1.476.1.42.3.4.4.13 | lgpEnvConfigSupplyTempLowLimitDegF | 1 | 1 | The minimum allowable supply temperature. |
1.3.6.1.4.1.476.1.42.3.4.4.14 | lgpEnvConfigSupplyTempLowLimitDegC | 1 | 1 | The minimum allowable supply temperature. |
1.3.6.1.4.1.476.1.42.3.4.4.15 | lgpEnvConfigTemperatureIntegTime | 1 | 1 | The value used as the integration factor in the proportional integral derivative (PID) temperature calculation. |
1.3.6.1.4.1.476.1.42.3.4.4.16 | lgpEnvConfigLocalTemperatureUnit | 1 | 1 | The local temperature unit of the system. |
1.3.6.1.4.1.476.1.42.3.4.4.17 | lgpEnvConfigSleepMode | 1 | 1 | The configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepD… |
1.3.6.1.4.1.476.1.42.3.4.4.18 | lgpEnvConfigHumidityIntegTime | 1 | 1 | The value used as the integration factor in the proportional integral derivative (PID) humidity calculation. |
1.3.6.1.4.1.476.1.42.3.4.4.19 | lgpEnvConfigFreecoolingDeltaDegF | 1 | 1 | The minimum temperature differential between the control temperature measurement and the coolant required to utilize Freecooling. |
1.3.6.1.4.1.476.1.42.3.4.4.20 | lgpEnvConfigFreecoolingDeltaDegC | 1 | 1 | The minimum temperature differential between the control temperature measurement and the coolant required to utilize Freecooling. |
1.3.6.1.4.1.476.1.42.3.4.4.21 | lgpEnvConfigSupplyTempLowLimit | 1 | 1 | The system configuration parameter to enable or disable the supply air low temperature limit. |
1.3.6.1.4.1.476.1.42.3.4.4.22 | lgpEnvConfigSensorEventsStandard | 1 | 1 | The system configuration parameter to enable or disable the standard sensor events. |
1.3.6.1.4.1.476.1.42.3.4.4.23 | lgpEnvConfigSensorEvents1 | 1 | 1 | The system configuration parameter to enable or disable sensor 1 events. |
1.3.6.1.4.1.476.1.42.3.4.4.24 | lgpEnvConfigSleepModeDeadbandRange | 1 | 1 | The system configuration parameter to enable or disable the use of the sleep interval deadband range in the sleep mode temperatu… |
1.3.6.1.4.1.476.1.42.3.4.4.25 | lgpEnvConfigAutoConfiguration | 1 | 1 | The system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and… |
1.3.6.1.4.1.476.1.42.3.4.4.26 | lgpEnvConfigDeltaGlycolType | 1 | 1 | The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cool… |
1.3.6.1.4.1.476.1.42.3.4.4.27 | lgpEnvConfigChillWaterControl | 1 | 1 | The system configuration parameter to enable or disable the minimum chill water temperature control. |
1.3.6.1.4.1.476.1.42.3.4.4.28 | lgpEnvConfigInfaredFlushRate | 1 | 1 | The Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan whe… |
1.3.6.1.4.1.476.1.42.3.4.4.29 | lgpEnvConfigHumidityControl | 1 | 1 | The present configured state of the automatic humidity compensation algorithm. |
1.3.6.1.4.1.476.1.42.3.4.4.30 | lgpEnvConfigCompressorLockout | 1 | 1 | The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for … |
1.3.6.1.4.1.476.1.42.3.4.4.31 | lgpEnvConfigReheatAndHumidifierLockout | 1 | 1 | The system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the co… |
1.3.6.1.4.1.476.1.42.3.4.4.32 | lgpEnvOperationalTimeTable | 1 | 7 | A list of environmental operational time ranges for a given envionmental unit. The entries in this table may be duplicated from… |
1.3.6.1.4.1.476.1.42.3.4.4.33 | lgpEnvConfigTempControlAlgorithm | 1 | 1 | Selects the algorithm for controlling temperature. |
1.3.6.1.4.1.476.1.42.3.4.4.34 | lgpEnvConfigFanSpeedMode | 1 | 1 | Changes the function of the fanspeed output. If auto, then the fan speed is modulated. If manual, the fanspeed output follows l… |
1.3.6.1.4.1.476.1.42.3.4.4.35 | lgpEnvConfigFanSpeedCapacity | 1 | 1 | Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ran… |
1.3.6.1.4.1.476.1.42.3.4.4.36 | lgpEnvConfigBmsResetTimer | 1 | 1 | The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpCond… |
1.3.6.1.4.1.476.1.42.3.4.4.37 | lgpEnvConfigDisableSensorOffsetDegC | 1 | 1 | If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, t… |
1.3.6.1.4.1.476.1.42.3.4.4.38 | lgpEnvConfigDisableSensorOffsetDegF | 1 | 1 | If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, t… |
1.3.6.1.4.1.476.1.42.3.4.4.39 | lgpEnvConfigCabinetSensorAlarms | 1 | 1 | Enable or Disable Cabinet Sensor Alarms. |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.476.1.42.3.4.1 | lgpEnvTemperature | 4 | 76 | This sub-tree is used to register Liebert temperature object identifiers. |
1.3.6.1.4.1.476.1.42.3.4.2 | lgpEnvHumidity | 2 | 28 | This sub-tree is used to register Liebert humidity object identifiers. |
1.3.6.1.4.1.476.1.42.3.4.3 | lgpEnvState | 22 | 58 | This sub-tree is used to register Liebert environmental state object identifiers. |
1.3.6.1.4.1.476.1.42.3.4.5 | lgpEnvControl | 4 | 17 | This sub-tree is used to register Liebert environmental control object identifiers. |
1.3.6.1.4.1.476.1.42.3.4.6 | lgpEnvStatistics | 16 | 32 | This sub-tree is used to register Liebert environmental statistic object identifiers. |
1.3.6.1.4.1.476.1.42.3.4.7 | lgpEnvPoints | 1 | 11 | This sub-tree is used to register Liebert environmental point object identifiers. |