Reading this variable returns bit mask indicating which
UPSs in a parallel system are alive. Management
software should poll only these UPSs on their snmp
branches 11-18 as follows:
1 FirstUPS alive
2 SecondUPS alive
4 ThirdUPS alive
8 FourthUPS alive
16 FifthUPS alive
32 SixthUPS alive
64 SeventhUPS alive
128 EigthUPS alive
Since the management software should always monitor
the GenericUPS branch (10), this value has no meaning
for single upses (which provide values on that snmp
branch), and should be set to zero in that case.
Parsed from file GE_SINGLEUPS.mib.txt
Company: ge
Module: GE_SINGLEUPS
Vendor: IMV Victron bv
Module: GE_PARALLELUPS
[Automatically extracted from oidview.com]
geDiscoveredUPSsMask OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Reading this variable returns bit mask indicating which UPSs in a parallel system are alive. Management software should poll only these UPSs on their snmp branches 11-18 as follows: 1 FirstUPS alive 2 SecondUPS alive 4 ThirdUPS alive 8 FourthUPS alive 16 FifthUPS alive 32 SixthUPS alive 64 SeventhUPS alive 128 EigthUPS alive Since the management software should always monitor the GenericUPS branch (10), this value has no meaning for single upses (which provide values on that snmp branch), and should be set to zero in that case." ::= { geUPS 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.1.0 | geDiscoveredUPSsMask | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.2 | geRequestPacket | 1 | 1 | Put the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus. This OID could be used for accede directly to t… |
1.3.6.1.4.1.818.1.1.3 | geReplyPacket | 1 | 1 | Contain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket. Every time that a write command has be made … |
1.3.6.1.4.1.818.1.1.10 | geGenericUPS | 11 | 293 | None |
1.3.6.1.4.1.818.1.1.11 | geFirstUPS | 11 | 293 | None |
1.3.6.1.4.1.818.1.1.12 | geSecondUPS | 11 | 293 | None |
1.3.6.1.4.1.818.1.1.13 | geThirdUPS | 11 | 293 | None |
1.3.6.1.4.1.818.1.1.14 | geFourthUPS | 11 | 293 | None |
1.3.6.1.4.1.818.1.1.15 | geFifthUPS | 11 | 293 | None |
1.3.6.1.4.1.818.1.1.16 | geSixthUPS | 11 | 293 | None |
1.3.6.1.4.1.818.1.1.17 | geSeventhUPS | 11 | 293 | None |
1.3.6.1.4.1.818.1.1.18 | geEighthUPS | 11 | 293 | None |