-- ************************************************* -- TridiumR3 - M I B . m y -- -- Revision History: -- 25 March 99 Robert Adams Original Niagara R2 code -- 18 Dec 2002 Scott Hoye Modified for Niagara -- R3 SNMP implementation. -- -- Copyright 1999 Tridium, Inc. -- ************************************************* -- TRIDIUMR3-MIB DEFINITIONS ::= BEGIN -- MIB II Extension Definitions for hub management IMPORTS OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215 enterprises FROM RFC1155-SMI DisplayString FROM RFC1213-MIB; tridium OBJECT IDENTIFIER ::= { enterprises 4131 } tridiumStation OBJECT IDENTIFIER ::= { tridium 1 } version OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Current software version" ::= { tridiumStation 1 } action OBJECT-TYPE SYNTAX INTEGER{ noAction(0), ackAll(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Provides means for manager to perform actions on the alarm table. 0 (no action) or 1 (acknowledge all)." ::= { tridiumStation 2 } -- *********************************** -- * -- * Alarm table declarations -- * -- *********************************** alarmTable OBJECT-TYPE SYNTAX SEQUENCE OF AlarmTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of alarms in the station which have an snmp recipient (configured to store received alarms)." ::= { tridiumStation 3 } alarmTableEntry OBJECT-TYPE SYNTAX AlarmTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An alarm table entry containing data for a specific alarm." INDEX { IMPLIED uuid } ::= { alarmTable 1 } AlarmTableEntry ::= SEQUENCE { timestamp DisplayString, uuid OCTET STRING, sourceState INTEGER, ackState INTEGER, ackRequired INTEGER, source DisplayString, alarmClass DisplayString, priority INTEGER, normalTime DisplayString, ackTime DisplayString, user DisplayString, alarmData DisplayString, alarmTransition INTEGER, lastUpdate DisplayString } timestamp OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the time when the alarm occurred." ::= { alarmTableEntry 1 } uuid OBJECT-TYPE SYNTAX OCTET STRING(SIZE(0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "The unique universal identifier of the alarm." ::= { alarmTableEntry 2 } sourceState OBJECT-TYPE SYNTAX INTEGER { normal(0), offnormal(1), fault(2), alert(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the source. normal(0), offnormal(1), fault(2), or alert(3)." ::= { alarmTableEntry 3 } ackState OBJECT-TYPE SYNTAX INTEGER { acked(0), unacked(1), ackPending(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Indicates if the alarm has been acknowledged. acked(0), unacked(1), or ackPending(2). Alarm can be acknowledged by setting ackState to 'acked'(0)" ::= { alarmTableEntry 4 } ackRequired OBJECT-TYPE SYNTAX INTEGER { false(0), true(1) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates if an acknowledgement is required for the alarm. false(0), or true(1)." ::= { alarmTableEntry 5 } source OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the path to the station object which generated the alarm." ::= { alarmTableEntry 6 } alarmClass OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The alarm class for the alarm." ::= { alarmTableEntry 7 } priority OBJECT-TYPE SYNTAX INTEGER(0..255) ACCESS read-only STATUS mandatory DESCRIPTION "The priority of the alarm (0=high, 255=low)." ::= { alarmTableEntry 8 } normalTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The time at which the alarm goes back to normal state." ::= { alarmTableEntry 9 } ackTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The time at which the alarm is acked. Note that interpretation of this value depends upon the state of the alarm." ::= { alarmTableEntry 10 } user OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the user who acknowledged the alarm." ::= { alarmTableEntry 11 } alarmData OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A string containing dynamic alarm data, in key-value pairs." ::= { alarmTableEntry 12 } alarmTransition OBJECT-TYPE SYNTAX INTEGER { normal(0), offnormal(1), fault(2), alert(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The initial state of the source. normal(0), offnormal(1), fault(2), or alert(3)." ::= { alarmTableEntry 13 } lastUpdate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The time at which the alarm was last updated. Updates occur at creation, acknowlegement, and changes to alarmData such as notes." ::= { alarmTableEntry 14 } -- *********************************** -- * -- * Input table declarations -- * -- *********************************** inputTable OBJECT-TYPE SYNTAX SEQUENCE OF InputTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of snmp input object values." ::= { tridiumStation 4 } inputTableEntry OBJECT-TYPE SYNTAX InputTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An input table entry containing data for a specific input." INDEX { inputIndex } ::= { inputTable 1 } InputTableEntry ::= SEQUENCE { inputIndex INTEGER, inputName DisplayString, inputValue DisplayString } inputIndex OBJECT-TYPE SYNTAX INTEGER(0..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "The index in the input table for a particular snmp input object. Used to address table entries." ::= { inputTableEntry 1 } inputName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Name of station object." ::= { inputTableEntry 2 } inputValue OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Current value of station object. Is writeable." ::= { inputTableEntry 3 } -- *********************************** -- * -- * Output table declarations -- * -- *********************************** outputTable OBJECT-TYPE SYNTAX SEQUENCE OF OutputTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of snmp output (read-only) object values." ::= { tridiumStation 5 } outputTableEntry OBJECT-TYPE SYNTAX OutputTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An output table entry containing data for a specific output." INDEX { outputIndex } ::= { outputTable 1 } OutputTableEntry ::= SEQUENCE { outputIndex INTEGER, outputName DisplayString, outputValue DisplayString } outputIndex OBJECT-TYPE SYNTAX INTEGER(0..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "The index in the output table for a particular snmp output object. Used to address table entries." ::= { outputTableEntry 1 } outputName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Name of station object." ::= { outputTableEntry 2 } outputValue OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Current value of station object. Is read-only." ::= { outputTableEntry 3 } -- *********************************** -- * -- * Alarm trap declarations -- * -- *********************************** stationAlarm TRAP-TYPE -- Non-reverse mappable trap ENTERPRISE tridiumStation VARIABLES { timestamp, uuid, sourceState, ackState, ackRequired, source, alarmClass, priority, normalTime, ackTime, user, alarmData, alarmTransition, lastUpdate } -- Status -- mandatory DESCRIPTION "The stationAlarm trap is generated when a Niagara alarm is received by an snmp recipient which has routing alarms to a network manager enabled. It contains useful information from the alarm record." ::= 1 END