-- File EXIDE.MIB -- Defines XUPS-MIB (Exide's proprietary PowerMIB) -- XUPS-MIB { iso org(3) dod(6) internet(1) private(4) -- enterprises(1) exide(534) } XUPS-MIB DEFINITIONS ::= BEGIN -- Title XUPS MIB - POWERMIB -- Date January 19, 1993 -- By: Brian Hammill - Exide Electronics -- Copyright 1992-94 by Exide Electronics -- May not be used without permission from Exide Electronics -- Revised February 25, 1993 Kevin Debruhl, Brian Hammill -- Revised June 21, 1993 Brian Hammill -- Revised (Variable types of ) August 5, 1993 Brian Hammill -- Revised August 16, 1993 Dale Langer - added units of measure -- Added Event History to Alarm Group and get/set time/date. -- 8/20/93 Brian Hammill -- Cleanup for final release. 9/3/93 Brian Hammill -- Release Version 0.91 9/17/93 -- Release Version 1.00 11/16/93 Kevin DeBruhl -- Changes for Release Version 2.00 9/7/94 Tom Brennan -- 1) Renamed UPS-MIB to XUPS-MIB and all names from upsVariable -- to xupsVariable to avoid conflicts with RFC 1628 Standard UPS MIB names -- (Note: XUPS is Exide Electronic's symbol on the NASDAQ stock exchange) -- 2) Renamed all traps from upsName to xupstName to avoid conflicts with -- similar alarm names -- 3) Added well known alarms and traps: -- BreakerOpen, AlarmEntryAdded, AlarmEntryRemoved -- 4) Deprecated xupsControlOutputOnTrapDelay -- 5) Added xupsTrapControl group -- 6) enumerated the value startTest for xupsTestBattery -- 7) Defined oid values to use for sysObjectId -- Changes for Release Version 2.10 11/1/94 Tom Brennan -- 1) Corrected type of xupsAlarms, xupsAlarmNumEvents (Gauge) -- 2) Defined three trap sources, which differ in their descriptions -- of trap variables (none, Defined, defined plus Port N Interface vars) -- 3) Clarified AlarmEvent order and numbering -- Changes for Release Version 2.11 3/30/95 Tom Brennan -- 1) Removed references to version 2.00 MIB files -- 2) Added range declarations for appropriate objects -- 3) Added Object IDs for new products -- -- Customer Support: direct questions to info.exide.com -- or call End User Hot-Line (800) 365-4892 -- (919) 870-3149 IMPORTS enterprises, IpAddress, TimeTicks, Gauge, Counter FROM RFC1155-SMI DisplayString, ifIndex, ifDescr FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215; exide OBJECT IDENTIFIER ::= {enterprises 534} xups OBJECT IDENTIFIER ::= {exide 1} xupsIdent OBJECT IDENTIFIER ::= { xups 1 } xupsBattery OBJECT IDENTIFIER ::= { xups 2 } xupsInput OBJECT IDENTIFIER ::= { xups 3 } xupsOutput OBJECT IDENTIFIER ::= { xups 4 } xupsBypass OBJECT IDENTIFIER ::= { xups 5 } xupsEnvironment OBJECT IDENTIFIER ::= { xups 6 } xupsAlarm OBJECT IDENTIFIER ::= { xups 7 } xupsTest OBJECT IDENTIFIER ::= { xups 8 } xupsControl OBJECT IDENTIFIER ::= { xups 9 } xupsConfig OBJECT IDENTIFIER ::= { xups 10 } xupsTrapControl OBJECT IDENTIFIER ::= { xups 11 } -- -- The following Object Identifiers are used to distinguish Exide's -- SNMP agents: xupsObjectId OBJECT IDENTIFIER ::= {exide 2} powerwareEthernetSnmpAdapter OBJECT IDENTIFIER ::= {xupsObjectId 1} powerwareNetworkSnmpAdapterEther OBJECT IDENTIFIER ::= {xupsObjectId 2} powerwareNetworkSnmpAdapterToken OBJECT IDENTIFIER ::= {xupsObjectId 3} onlinetDaemon OBJECT IDENTIFIER ::= {xupsObjectId 4} connectUPSAdapterEthernet OBJECT IDENTIFIER ::= {xupsObjectId 5} powerwareNetworkDigitalIOEther OBJECT IDENTIFIER ::= {xupsObjectId 6} connectUPSAdapterTokenRing OBJECT IDENTIFIER ::= {xupsObjectId 7} -- -- xupsIdent group: -- xupsIdentManufacturer OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Manufacturer Name (e.g. Exide Electronics)." ::= { xupsIdent 1} xupsIdentModel OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Model (e.g. Powerware Plus Model 18)." ::= {xupsIdent 2} xupsIdentSoftwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision level(s) of the UPS microcontroller(s)." ::= {xupsIdent 3} -- -- xupsBattery group: -- xupsBatTimeRemaining OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS seconds ACCESS read-only STATUS mandatory DESCRIPTION "Battery run time in seconds before UPS turns off due to low battery." ::= { xupsBattery 1} xupsBatVoltage OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS Volts DC ACCESS read-only STATUS mandatory DESCRIPTION "Battery voltage as reported by the UPS meters." ::= {xupsBattery 2} xupsBatCurrent OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS Amp DC ACCESS read-only STATUS mandatory DESCRIPTION "Battery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery." ::= {xupsBattery 3} xupsBatCapacity OBJECT-TYPE SYNTAX INTEGER (0..100) -- UNITS percent ACCESS read-only STATUS mandatory DESCRIPTION "Battery percent charge." ::= { xupsBattery 4} -- -- xupsInput group: -- xupsInputFrequency OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The utility line frequency in tenths of Hz." ::= {xupsInput 1} xupsInputLineBads OBJECT-TYPE SYNTAX Counter ACCESS read-only STATUS mandatory DESCRIPTION "The number of times the Input was out of tolerance in voltage or frequency." ::= {xupsInput 2} xupsInputNumPhases OBJECT-TYPE SYNTAX INTEGER (0..6) ACCESS read-only STATUS mandatory ::= {xupsInput 3} xupsInputTable OBJECT-TYPE SYNTAX SEQUENCE OF XupsInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Aggregate Object with number of entries equal to NumPhases and including the xupsInput group." ::= {xupsInput 4} xupsInputEntry OBJECT-TYPE SYNTAX XupsInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The input table entry containing the current, voltage, etc." INDEX { xupsInputPhase } ::= { xupsInputTable 1 } XupsInputEntry ::= SEQUENCE { xupsInputPhase INTEGER, xupsInputVoltage INTEGER, xupsInputCurrent INTEGER, xupsInputWatts INTEGER } xupsInputPhase OBJECT-TYPE SYNTAX INTEGER (0..6) ACCESS read-only STATUS mandatory DESCRIPTION "The number of the phase. Serves as index for input table." ::= {xupsInputEntry 1} xupsInputVoltage OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The measured input voltage from the UPS meters in volts." ::= {xupsInputEntry 2} xupsInputCurrent OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The measured input current from the UPS meters in amps." ::= {xupsInputEntry 3} xupsInputWatts OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The measured input real power in watts." ::= {xupsInputEntry 4} -- -- xupsOutput group: -- xupsOutputLoad OBJECT-TYPE SYNTAX INTEGER (0..200) ACCESS read-only STATUS mandatory DESCRIPTION "The UPS output load in percent of rated capacity." ::= {xupsOutput 1} xupsOutputFrequency OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The measured UPS output frequency in tenths of Hz." ::= {xupsOutput 2} xupsOutputNumPhases OBJECT-TYPE SYNTAX INTEGER (0..6) ACCESS read-only STATUS mandatory DESCRIPTION "The number of metered output phases, serves as the table index." ::= {xupsOutput 3} xupsOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF XupsOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Aggregate Object with number of entries equal to NumPhases and including the xupsOutput group." ::= {xupsOutput 4} xupsOutputEntry OBJECT-TYPE SYNTAX XupsOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Output Table Entry containing voltage, current, etc." INDEX { xupsOutputPhase } ::= {xupsOutputTable 1} XupsOutputEntry ::= SEQUENCE { xupsOutputPhase INTEGER, xupsOutputVoltage INTEGER, xupsOutputCurrent INTEGER, xupsOutputWatts INTEGER } xupsOutputPhase OBJECT-TYPE SYNTAX INTEGER (0..6) ACCESS read-only STATUS mandatory DESCRIPTION "The number {1..3} of the output phase." ::= {xupsOutputEntry 1} xupsOutputVoltage OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The measured output voltage from the UPS metering in volts." ::= {xupsOutputEntry 2} xupsOutputCurrent OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The measured UPS output current in amps." ::= {xupsOutputEntry 3} xupsOutputWatts OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The measured real output power in watts." ::= {xupsOutputEntry 4} -- -- xupsBypass group: -- xupsBypassFrequency OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The bypass frequency in tenths of Hz." ::= {xupsBypass 1} xupsBypassNumPhases OBJECT-TYPE SYNTAX INTEGER (0..6) ACCESS read-only STATUS mandatory DESCRIPTION "The number of lines in the UPS bypass table." ::= {xupsBypass 2} xupsBypassTable OBJECT-TYPE SYNTAX SEQUENCE OF XupsBypassEntry ACCESS not-accessible STATUS mandatory ::= {xupsBypass 3} xupsBypassEntry OBJECT-TYPE SYNTAX XupsBypassEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Entry in the XUPS bypass table." INDEX { xupsBypassPhase } ::= {xupsBypassTable 1} XupsBypassEntry ::= SEQUENCE { xupsBypassPhase INTEGER, xupsBypassVoltage INTEGER } xupsBypassPhase OBJECT-TYPE SYNTAX INTEGER (0..6) ACCESS read-only STATUS mandatory DESCRIPTION "The Bypass Phase, index for the table." ::= {xupsBypassEntry 1} xupsBypassVoltage OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The measured UPS bypass voltage in volts." ::= {xupsBypassEntry 2} -- -- xupsAlarm group: -- xupsAlarms OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The current number of alarm conditions." ::= {xupsAlarm 1} xupsAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF XupsAlarmEntry ACCESS not-accessible STATUS mandatory ::= {xupsAlarm 2} xupsAlarmEntry OBJECT-TYPE SYNTAX XupsAlarmEntry ACCESS not-accessible STATUS mandatory INDEX { xupsAlarmID } ::= {xupsAlarmTable 1} XupsAlarmEntry ::= SEQUENCE { xupsAlarmID INTEGER, xupsAlarmDescr OBJECT IDENTIFIER, xupsAlarmTime TimeTicks } xupsAlarmID OBJECT-TYPE SYNTAX INTEGER (1..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "A unique identifier for an alarm condition." ::= {xupsAlarmEntry 1} xupsAlarmDescr OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS mandatory DESCRIPTION "A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition." ::= {xupsAlarmEntry 2} xupsAlarmTime OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS mandatory DESCRIPTION "The value of the MIB-II variable sysUpTime when the alarm condition occurred." ::= {xupsAlarmEntry 3} -- -- Well known alarm conditions. -- xupsOnBattery OBJECT IDENTIFIER ::= {xupsAlarm 3} xupsLowBattery OBJECT IDENTIFIER ::= {xupsAlarm 4} xupsUtilityPowerRestored OBJECT IDENTIFIER ::= {xupsAlarm 5} xupsReturnFromLowBattery OBJECT IDENTIFIER ::= {xupsAlarm 6} xupsOutputOverload OBJECT IDENTIFIER ::= {xupsAlarm 7} xupsInternalFailure OBJECT IDENTIFIER ::= {xupsAlarm 8} xupsBatteryDischarged OBJECT IDENTIFIER ::= {xupsAlarm 9} xupsInverterFailure OBJECT IDENTIFIER ::= {xupsAlarm 10} xupsOnBypass OBJECT IDENTIFIER ::= {xupsAlarm 11} xupsBypassNotAvailable OBJECT IDENTIFIER ::= {xupsAlarm 12} xupsOutputOff OBJECT IDENTIFIER ::= {xupsAlarm 13} xupsInputFailure OBJECT IDENTIFIER ::= {xupsAlarm 14} xupsBuildingAlarm OBJECT IDENTIFIER ::= {xupsAlarm 15} xupsShutdownImminent OBJECT IDENTIFIER ::= {xupsAlarm 16} xupsOnInverter OBJECT IDENTIFIER ::= {xupsAlarm 17} xupsAlarmNumEvents OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The number of entries in the UPS event history queue." ::= { xupsAlarm 18 } xupsAlarmEventTable OBJECT-TYPE SYNTAX SEQUENCE OF XupsAlarmEventEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of the UPS internal event history queue." ::= { xupsAlarm 19 } xupsAlarmEventEntry OBJECT-TYPE SYNTAX XupsAlarmEventEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "One of the entries in the UPS event history queue." INDEX { xupsAlarmEventID } ::= { xupsAlarmEventTable 1 } XupsAlarmEventEntry ::= SEQUENCE { xupsAlarmEventID INTEGER, xupsAlarmEventDateAndTime DisplayString, xupsAlarmEventKind INTEGER, xupsAlarmEventDescr INTEGER } xupsAlarmEventID OBJECT-TYPE SYNTAX INTEGER (1..400) ACCESS read-only STATUS mandatory DESCRIPTION "A unique number that reflects the order in which the event occurred. The oldest event in the queue will be number 1. Subsequent events will be numbered 2, 3, 4, etc." ::= { xupsAlarmEventEntry 1 } xupsAlarmEventDateAndTime OBJECT-TYPE SYNTAX DisplayString (SIZE (0..22)) ACCESS read-only STATUS mandatory DESCRIPTION "The time and date that an event occurred as recorded in the UPS internal event queue. This string will reflect the time and date as set in the UPS itself and will not be referenced to sysUpTime. The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standard." ::= { xupsAlarmEventEntry 2 } xupsAlarmEventKind OBJECT-TYPE SYNTAX INTEGER { occurred (1), cleared (2), unknown (3) } ACCESS read-only STATUS mandatory DESCRIPTION "Enumerated value that tells whether the event is an occurrence of an alarm condition or a clearing of an alarm condition." ::= { xupsAlarmEventEntry 3 } xupsAlarmEventDescr OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "A description of the event stored in the UPS event queue. This description will be a sixteen bit integer value representing one of the defined alarms in the Exide Binary Computer Mode communication specification; for example, a value of 0 represents the 'Inverter AC Over Voltage' alarm (byte 1, bit 0 in the BCM Alarm Map)." ::= { xupsAlarmEventEntry 4 } -- -- More Well known alarm conditions. -- xupsBreakerOpen OBJECT IDENTIFIER ::= {xupsAlarm 20} xupsAlarmEntryAdded OBJECT IDENTIFIER ::= {xupsAlarm 21} xupsAlarmEntryRemoved OBJECT IDENTIFIER ::= {xupsAlarm 22} -- -- xupsTest group: -- xupsTestBattery OBJECT-TYPE SYNTAX INTEGER { startTest (1) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to startTest initiates the battery test. All other set values are invalid." ::= {xupsTest 1} xupsTestBatteryStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), passed (2), failed (3), inProgress (4), notSupported (5), inhibited (6) } ACCESS read-only STATUS mandatory DESCRIPTION "Reading this enumerated value gives an indication of the UPS Battery test status." ::= {xupsTest 2} -- -- xupsControl group: -- xupsControlOutputOffDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483648) -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "Setting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pending shutdown." ::= {xupsControl 1} xupsControlOutputOnDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483648) -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "Setting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pending startup." ::= {xupsControl 2} xupsControlOutputOffTrapDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483648) -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "When xupsControlOutputOffDelay reaches this value, a trap will be sent." ::= {xupsControl 3} xupsControlOutputOnTrapDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483648) -- UNITS seconds ACCESS read-write STATUS deprecated DESCRIPTION "When xupsControlOutputOnDelay reaches this value, a xupsOutputOff trap will be sent." ::= {xupsControl 4} -- -- xupsConfig group: -- xupsConfigOutputVoltage OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The nominal UPS Output voltage per phase in volts." ::= {xupsConfig 1} xupsConfigInputVoltage OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The nominal UPS Input voltage per phase in volts." ::= {xupsConfig 2} xupsConfigOutputWatts OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The nominal UPS available real power output in watts." ::= {xupsConfig 3} xupsConfigOutputFreq OBJECT-TYPE SYNTAX INTEGER (0..2147483647) -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The nominal output frequency in tenths of Hz." ::= {xupsConfig 4} xupsConfigDateAndTime OBJECT-TYPE SYNTAX DisplayString (SIZE (0..22)) ACCESS read-write STATUS mandatory DESCRIPTION "Date and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS time and date. This value is not referenced to sysUpTime. It is simply the clock value from the UPS real time clock. Format is as follows: MM/DD/YYYY:HH:MM:SS." ::= { xupsConfig 5 } -- -- xupsTrapControl group: -- xupsMaxTrapLevel OBJECT-TYPE SYNTAX INTEGER { none (1), critical (2), major (3), allTraps (4) } ACCESS read-write STATUS mandatory DESCRIPTION "The level of severity of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. Values are: (1) none: no traps will be sent to this host; (2) critical: only traps for Critical alarm conditions will be sent to this host; (3) major: Critical and Major traps will be sent; (4) allTraps: all Traps will be sent to this host (Critical, Major, Minor, Informational)." ::= {xupsTrapControl 1} xupsSendTrapType OBJECT-TYPE SYNTAX INTEGER { stnd (1), xups (2), stndPlus (3), xupsPlus (4) } ACCESS read-write STATUS mandatory DESCRIPTION "The type of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. The additional variables in types (3) and (4) are useful for determining which UPS is the source on multi-port network adapters, and for getting additional descriptive information. Types (1) through (4) are all SNMP version 1 trap PDUs. Values are: (1) stnd: Traps as defined in the Standard UPS MIB (RFC1628) and Generic (MIB II) traps as defined in RFC 1215. (2) xups: xupsTrapDefined Traps as defined in the PowerMIB and Generic (MIB II) traps as defined in RFC 1215. (3) stndPlus: same as stnd plus variables from the interface group and, where appropriate, xupsTrapMessage. (4) xupsPlus: xupsTrapPortN Traps (same as xups plus variables from the interface group) and, for authFail, xupsTrapMessage." ::= {xupsTrapControl 2} xupsTrapMessage OBJECT-TYPE SYNTAX DisplayString (SIZE (0..79)) ACCESS not-accessible STATUS mandatory DESCRIPTION "A descriptive message which may be sent with traps to further explain the reason for the trap." ::= {xupsTrapControl 3} -- -- Traps (xupst) -- -- 1) Exide's traps are defined in this MIB for three different sources: -- a) Basic Agents for which the trap variables have not been defined, -- though trap variables are included with the trap PDU -- b) Agents with exactly Defined trap variables, which may be -- used as input to trap response macros on management stations -- c) Agents with Defined traps including ifIndex and ifDescr, -- which can be used to determine which UPS of a multi-port -- agent (eg, Powerware Network SNMP Adapter) sent the trap -- The trap definitions for the three sources are very similar, -- and use the same alarms as their triggers; their names are prefaced -- by xupstb, xupstd, and xupstp to distinguish the three types -- -- 2) Trap Severity Level is given as a comment to indicate which -- xupsMaxTrapLevel will result in this trap being sent; levels -- are (in order): Critical, Major, Minor, Informational -- -- 3) The following Object Identifiers are used to distinguish Exide's -- Trap sources: -- a) The first is for traps without defined trap variables xupsNull OBJECT IDENTIFIER ::= { xups 0 } xupsTrapBasic OBJECT IDENTIFIER ::= { xupsNull 0 } -- b) The second is for traps with defined variables, -- without ifIndex & ifDescr xupsTrapSource OBJECT IDENTIFIER ::= {xupsTrapControl 4} xupsTrapDefined OBJECT IDENTIFIER ::= {xupsTrapSource 1} -- c) The third is for traps with defined variables -- plus ifIndex & ifDescr xupsTrapPortN OBJECT IDENTIFIER ::= {xupsTrapSource 2} -- -- Traps from xupsTrapBasic source (xupstb): -- xupstbControlOff TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The UPS output power will turn off in a number of seconds equal to upsControlOutputOffTrapDelay." --#SEVERITY CRITICAL ::= 1 xupstbControlOn TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The UPS output power will turn on in a number of seconds equal to upsControlOutputOnTrapDelay." --#SEVERITY INFORMATIONAL ::= 2 xupstbOnBattery TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The UPS has no AC input power and is running on battery." --#SEVERITY MAJOR ::= 3 xupstbLowBattery TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The UPS batteries are low. Tied to low battery alarm condition." --#SEVERITY CRITICAL ::= 4 xupstbUtilityPowerRestored TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "Input power has been restored after running on battery." --#SEVERITY INFORMATIONAL ::= 5 xupstbReturnFromLowBattery TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The battery has recovered from a low battery condition." --#SEVERITY INFORMATIONAL ::= 6 xupstbOutputOverload TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The ups has sensed an overload of greater than 106 percent. Tied to the 106% overload alarm." --#SEVERITY MINOR ::= 7 xupstbInternalFailure TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "Some component of the ups - rectifier, inverter, control panel has failed. Tied to alarms indi- cating failure." --#SEVERITY CRITICAL ::= 8 xupstbBatteryDischarged TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The Battery Totally Discharged Alarm has occurred." --#SEVERITY CRITICAL ::= 9 xupstbInverterFailure TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The ups inverter is unavailable due to an internal failure." --#SEVERITY CRITICAL ::= 10 xupstbOnBypass TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The ups has gone on bypass for some reason." --#SEVERITY CRITICAL ::= 11 xupstbBypassNotAvailable TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The ups bypass is unavailable" --#SEVERITY MAJOR ::= 12 xupstbOutputOff TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The ups output is switched off." --#SEVERITY CRITICAL ::= 13 xupstbInputFailure TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The ups input power is incorrect in voltage, frequency, or phase rotation." --#SEVERITY MINOR ::= 14 xupstbBuildingAlarm TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "One of the defined building alarms has occurred." --#SEVERITY MAJOR ::= 15 xupstbShutdownImminent TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The ups shutdown imminent alarm has occurred." --#SEVERITY CRITICAL ::= 16 xupstbOnInverter TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "The ups is returned to utility power running the inverter after either a transfer to bypass or a run on battery." --#SEVERITY INFORMATIONAL ::= 17 xupstbBreakerOpen TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "One of the UPS breakers or contactors has been opened." --#SEVERITY MAJOR ::= 20 xupstbAlarmEntryAdded TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "An alarm not defined in the xups Well Known Alarms (eg, an alarm defined in RFC1628) has been added to the Alarm Table." --#SEVERITY MAJOR ::= 21 xupstbAlarmEntryRemoved TRAP-TYPE ENTERPRISE xupsTrapBasic DESCRIPTION "An alarm not defined in the xups Well Known Alarms has been removed from the Alarm Table." --#SEVERITY INFORMATIONAL ::= 22 -- -- Traps from xupsTrapDefined source (xupstd): -- xupstdControlOff TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The UPS output power will turn off in a number of seconds equal to upsControlOutputOffTrapDelay." --#SEVERITY CRITICAL ::= 1 xupstdControlOn TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The UPS output power will turn on in a number of seconds equal to upsControlOutputOnTrapDelay." --#SEVERITY INFORMATIONAL ::= 2 xupstdOnBattery TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The UPS has no AC input power and is running on battery." --#SEVERITY MAJOR ::= 3 xupstdLowBattery TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The UPS batteries are low. Tied to low battery alarm condition." --#SEVERITY CRITICAL ::= 4 xupstdUtilityPowerRestored TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "Input power has been restored after running on battery." --#SEVERITY INFORMATIONAL ::= 5 xupstdReturnFromLowBattery TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The battery has recovered from a low battery condition." --#SEVERITY INFORMATIONAL ::= 6 xupstdOutputOverload TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The ups has sensed an overload of greater than 106 percent. Tied to the 106% overload alarm." --#SEVERITY MINOR ::= 7 xupstdInternalFailure TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "Some component of the ups - rectifier, inverter, control panel has failed. Tied to alarms indi- cating failure." --#SEVERITY CRITICAL ::= 8 xupstdBatteryDischarged TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The Battery Totally Discharged Alarm has occurred." --#SEVERITY CRITICAL ::= 9 xupstdInverterFailure TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The ups inverter is unavailable due to an internal failure." --#SEVERITY CRITICAL ::= 10 xupstdOnBypass TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The ups has gone on bypass for some reason." --#SEVERITY CRITICAL ::= 11 xupstdBypassNotAvailable TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The ups bypass is unavailable" --#SEVERITY MAJOR ::= 12 xupstdOutputOff TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The ups output is switched off." --#SEVERITY CRITICAL ::= 13 xupstdInputFailure TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The ups input power is incorrect in voltage, frequency, or phase rotation." --#SEVERITY MINOR ::= 14 xupstdBuildingAlarm TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "One of the defined building alarms has occurred." --#SEVERITY MAJOR ::= 15 xupstdShutdownImminent TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The ups shutdown imminent alarm has occurred." --#SEVERITY CRITICAL ::= 16 xupstdOnInverter TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "The ups is returned to utility power running the inverter after either a transfer to bypass or a run on battery." --#SEVERITY INFORMATIONAL ::= 17 xupstdBreakerOpen TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "One of the UPS breakers or contactors has been opened." --#SEVERITY MAJOR ::= 20 xupstdAlarmEntryAdded TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "An alarm not defined in the xups Well Known Alarms (eg, an alarm defined in RFC1628) has been added to the Alarm Table." --#SEVERITY MAJOR ::= 21 xupstdAlarmEntryRemoved TRAP-TYPE ENTERPRISE xupsTrapDefined VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage } DESCRIPTION "An alarm not defined in the xups Well Known Alarms has been removed from the Alarm Table." --#SEVERITY INFORMATIONAL ::= 22 -- -- Traps from xupsTrapPortN source (xupstp): -- xupstpControlOff TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The UPS output power will turn off in a number of seconds equal to upsControlOutputOffTrapDelay." --#SEVERITY CRITICAL ::= 1 xupstpControlOn TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The UPS output power will turn on in a number of seconds equal to upsControlOutputOnTrapDelay." --#SEVERITY INFORMATIONAL ::= 2 xupstpOnBattery TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The UPS has no AC input power and is running on battery." --#SEVERITY MAJOR ::= 3 xupstpLowBattery TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The UPS batteries are low. Tied to low battery alarm condition." --#SEVERITY CRITICAL ::= 4 xupstpUtilityPowerRestored TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "Input power has been restored after running on battery." --#SEVERITY INFORMATIONAL ::= 5 xupstpReturnFromLowBattery TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The battery has recovered from a low battery condition." --#SEVERITY INFORMATIONAL ::= 6 xupstpOutputOverload TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The ups has sensed an overload of greater than 106 percent. Tied to the 106% overload alarm." --#SEVERITY MINOR ::= 7 xupstpInternalFailure TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "Some component of the ups - rectifier, inverter, control panel has failed. Tied to alarms indi- cating failure." --#SEVERITY CRITICAL ::= 8 xupstpBatteryDischarged TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The Battery Totally Discharged Alarm has occurred." --#SEVERITY CRITICAL ::= 9 xupstpInverterFailure TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The ups inverter is unavailable due to an internal failure." --#SEVERITY CRITICAL ::= 10 xupstpOnBypass TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The ups has gone on bypass for some reason." --#SEVERITY CRITICAL ::= 11 xupstpBypassNotAvailable TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The ups bypass is unavailable" --#SEVERITY MAJOR ::= 12 xupstpOutputOff TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The ups output is switched off." --#SEVERITY CRITICAL ::= 13 xupstpInputFailure TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The ups input power is incorrect in voltage, frequency, or phase rotation." --#SEVERITY MINOR ::= 14 xupstpBuildingAlarm TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "One of the defined building alarms has occurred." --#SEVERITY MAJOR ::= 15 xupstpShutdownImminent TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The ups shutdown imminent alarm has occurred." --#SEVERITY CRITICAL ::= 16 xupstpOnInverter TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "The ups is returned to utility power running the inverter after either a transfer to bypass or a run on battery." --#SEVERITY INFORMATIONAL ::= 17 xupstpBreakerOpen TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "One of the UPS breakers or contactors has been opened." --#SEVERITY MAJOR ::= 20 xupstpAlarmEntryAdded TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "An alarm not defined in the xups Well Known Alarms (eg, an alarm defined in RFC1628) has been added to the Alarm Table." --#SEVERITY MAJOR ::= 21 xupstpAlarmEntryRemoved TRAP-TYPE ENTERPRISE xupsTrapPortN VARIABLES { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr } DESCRIPTION "An alarm not defined in the xups Well Known Alarms has been removed from the Alarm Table." --#SEVERITY INFORMATIONAL ::= 22 END