-- ***************************************************************** -- -- -- Copyright (c) 2023 by Schneider Electric. -- All rights reserved. -- -- ***************************************************************** SCHNEIDER-ELECTRIC-HDPM DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, OBJECT-TYPE, enterprises, Gauge32, Integer32, Unsigned32, Counter64, Counter32 FROM SNMPv2-SMI TEXTUAL-CONVENTION, DateAndTime FROM SNMPv2-TC OBJECT-GROUP FROM SNMPv2-CONF; hdpm MODULE-IDENTITY -- 1.3.6.1.4.1.3833.1.6000 LAST-UPDATED "202409100000Z" ORGANIZATION "Schneider Electric" CONTACT-INFO "Schneider Electric www.se.com" DESCRIPTION "This MIB module is for the HDPM6000 High Density Power Meter." REVISION "202409100000Z" DESCRIPTION "HDPM6000 v0.56.0 and later System Firmware" ::= { schneiderEnergy 6000 } -- -- OID Structure ********************************************************************** -- schneiderElectric OBJECT IDENTIFIER ::= { enterprises 3833 } -- 1.3.6.1.4.1.3833 Schneider Electric Private Enterpise Number (PEN) schneiderEnergy OBJECT IDENTIFIER ::= { schneiderElectric 1 } -- 1.3.6.1.4.1.3833.1 schneiderHDPM OBJECT IDENTIFIER ::= { hdpm 1 } -- 1.3.6.1.4.1.3833.1.6000.1 seHdpmSystem OBJECT IDENTIFIER ::= { schneiderHDPM 1 } seHdpmModules OBJECT IDENTIFIER ::= { schneiderHDPM 2 } seHdpmChannels OBJECT IDENTIFIER ::= { schneiderHDPM 3 } seHdpmACMeters OBJECT IDENTIFIER ::= { schneiderHDPM 4 } seHdpmDCMeters OBJECT IDENTIFIER ::= { schneiderHDPM 5 } seHdpmDryContacts OBJECT IDENTIFIER ::= { schneiderHDPM 6 } seHdpmCircuitSummaries OBJECT IDENTIFIER ::= { schneiderHDPM 7 } seHdpmVoltsAmpsWatts OBJECT IDENTIFIER ::= { schneiderHDPM 8 } seHdpmEnvironmentalSensors OBJECT IDENTIFIER ::= { schneiderHDPM 9 } seHdpmCircuits OBJECT IDENTIFIER ::= { schneiderHDPM 10 } seHdpmDemand OBJECT IDENTIFIER ::= { schneiderHDPM 11 } seHdpmDryInputs OBJECT IDENTIFIER ::= { schneiderHDPM 12 } -- -- Textual Conventions -- ModuleIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each tap module on the bus." SYNTAX Integer32 (1..2147483647) ChannelIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each circuit (single phase branch circuit, channel)." SYNTAX Integer32 (1..2147483647) LoadTypeIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each load type." SYNTAX Integer32 (1..2147483647) CtTypeIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each CT type." SYNTAX Integer32 (1..2147483647) ChannelCircuitNameIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each load type." SYNTAX Integer32 (1..2147483647) ChannelRackNameIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each load type." SYNTAX Integer32 (1..2147483647) ACMeterIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each AC meter in the system." SYNTAX Integer32 (1..2147483647) PhaseIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each phase in a source." SYNTAX Integer32 (1..2147483647) ChannelSummaryIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each branch summary in the system." SYNTAX Integer32 (1..2147483647) ChannelSummaryPhaseIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each phase in a summary." SYNTAX Integer32 (1..2147483647) CircuitSummaryIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each circuit." SYNTAX Integer32 (1..2147483647) CircuitSummaryPhaseIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each phase in a group." SYNTAX Integer32 (1..2147483647) DCMeterIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each DC meter in the system." SYNTAX Integer32 (1..2147483647) DryContactIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each dry contact module in the system." SYNTAX Integer32 (1..2147483647) EnvironmentalSensorIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each environmental sensor." SYNTAX Integer32 (1..2147483647) EnvironmentalTemperatureIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each temperature sensor." SYNTAX Integer32 (1..2147483647) EnvironmentalHumidityIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each humidity sensor." SYNTAX Integer32 (1..2147483647) DemandIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each entry." SYNTAX Integer32 (1..2147483647) DryInputsIndex ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "A unique value greater than zero for each dry input module in the system." SYNTAX Integer32 (1..2147483647) EnvironmentalSensorID ::= TEXTUAL-CONVENTION DISPLAY-HINT "16a" STATUS current DESCRIPTION "An environmental sensor's device ID." SYNTAX OCTET STRING (SIZE (16)) EnvironmentalSensorTAP ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "An environmental sensor's host TAP ID." SYNTAX Integer32 (1..2147483647) EnvironmentalSensorPort ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "An environmental sensor's host port." SYNTAX Integer32 (0..8) -- -- The system data -- seHdpmSystemChannelCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The total number of installed channels (branch circuits) on the bus." ::= { seHdpmSystem 1 } seHdpmSystemFirmwareVersion OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The firmware version for the communications processor in the Head Unit." ::= { seHdpmSystem 2 } seHdpmSystemMicroFirmwareVersion OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The firmware version for the metering micro-controller in the Head Unit." ::= { seHdpmSystem 3 } seHdpmSystemSerialNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The serial number for the Head Unit cpu card." ::= { seHdpmSystem 4 } seHdpmSystemSupplyType OBJECT-TYPE SYNTAX INTEGER { v120x240(0), v120x208wye(1), v120x208delta(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The current supply type: 0=120/240, 1=120/208 wye, 2=120/208 delta." ::= { seHdpmSystem 5 } seHdpmSystemEnergyScale OBJECT-TYPE SYNTAX INTEGER { wattHourThousandths(-1000), wattHourHundredths(-100), wattHourTenths(-10), wattHour(1), wattHourTens(10), wattHourHundreds(100), wattHourThousands(1000), wattHourTenThousands(10000) } MAX-ACCESS read-only STATUS current DESCRIPTION "Energy (Wh, VARh, VAh) scale factor where possible values are: -1000, -100, -10, 1, 10, 100, 1000, or 10000. For positive scales, the value of Energy returned for circuits and channels will be in units of watt hours multiplied by this value, so a value of 100 means hundreds of watt hours. For negative scales the value of energy returned for circuits will be in units of watt hours divided by this value negated, so a value of -100 means hundredths of watt hours." ::= { seHdpmSystem 6 } seHdpmSystemVoltsScale OBJECT-TYPE SYNTAX INTEGER { voltTenths(1), volt(10), voltTens(100), voltHundreds(1000), voltThousands(10000) } MAX-ACCESS read-only STATUS current DESCRIPTION "DEPRECATED, use seHdpmSystemPtRatio instead. Voltage scale factor where possible values are: 1, 10, 100, 1000, or 10000. The value of Volts returned for circuits and channels will be in units of tenths of volts multiplied by this value so a value of 100 means tens of volts. " ::= { seHdpmSystem 7 } seHdpmSystemAmpsScale OBJECT-TYPE SYNTAX INTEGER { ampereHundredths(1), ampereTenths(10), ampere(100), ampereTens(1000), ampereHundreds(10000) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current scale factor where possible values are: 1, 10, 100, 1000, or 10000. The value of amps returned for circuits and channels will be in units of hunderdths of amps multiplied by this value so a value of 1000 means tens of amps." ::= { seHdpmSystem 8 } seHdpmSystemPowerScale OBJECT-TYPE SYNTAX INTEGER { watt(1), wattTens(10), wattHundreds(100), wattThousands(1000), wattTenThousands(10000) } MAX-ACCESS read-only STATUS current DESCRIPTION "Power (W, VAR, VA) scale factor where possible values are: 1, 10, 100, 1000, or 10000. The value of power returned for circuits and channels will be in units of watts multiplied by this value so a value of 100 means hundreds of watts." ::= { seHdpmSystem 9 } seHdpmLoadTypeTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmLoadTypeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of the available load types." ::= { seHdpmSystem 10 } seHdpmLoadTypeEntry OBJECT-TYPE SYNTAX SeHdpmLoadTypeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single load type." INDEX { seHdpmLoadTypeIndex } ::= { seHdpmLoadTypeTable 1 } SeHdpmLoadTypeEntry ::= SEQUENCE { seHdpmLoadTypeIndex LoadTypeIndex, seHdpmLoadTypeName OCTET STRING, seHdpmLoadTypeTotal Integer32 } seHdpmLoadTypeIndex OBJECT-TYPE SYNTAX LoadTypeIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the load type. Between 1 and 20." ::= { seHdpmLoadTypeEntry 1 } seHdpmLoadTypeName OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Identifying name." ::= { seHdpmLoadTypeEntry 2 } seHdpmLoadTypeTotal OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total power accumulated." ::= { seHdpmLoadTypeEntry 3 } seHdpmCtTypeTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmCtTypeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of the available CT types." ::= { seHdpmSystem 11 } seHdpmCtTypeEntry OBJECT-TYPE SYNTAX SeHdpmCtTypeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single CT type." INDEX { seHdpmCtTypeIndex } ::= { seHdpmCtTypeTable 1 } SeHdpmCtTypeEntry ::= SEQUENCE { seHdpmCtTypeIndex CtTypeIndex, seHdpmCtTypeName OCTET STRING, seHdpmCtTypeFactor1 Integer32, seHdpmCtTypeFactor2 Integer32, seHdpmCtTypePHCAL1 Integer32, seHdpmCtTypePHCAL2 Integer32 } seHdpmCtTypeIndex OBJECT-TYPE SYNTAX CtTypeIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the CT type. Between 1 and 120." ::= { seHdpmCtTypeEntry 1 } seHdpmCtTypeName OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Identifying name." ::= { seHdpmCtTypeEntry 2 } seHdpmCtTypeFactor1 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "CT factor for version 1 hardware." ::= { seHdpmCtTypeEntry 3 } seHdpmCtTypeFactor2 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "CT factor for version 2 hardware." ::= { seHdpmCtTypeEntry 4 } seHdpmCtTypePHCAL1 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "CT PHCAL for version 1 hardware." ::= { seHdpmCtTypeEntry 5 } seHdpmCtTypePHCAL2 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "CT PHCAL for version 2 hardware." ::= { seHdpmCtTypeEntry 6 } seHdpmChannelCircuitNameTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmChannelCircuitNameEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of channel (single phase branch circuit) names. Circuits built from 2 or 3 channels (branch circuits) will show a circuit name in the first channel position with the following channel or two blank" ::= { seHdpmSystem 12 } seHdpmChannelCircuitNameEntry OBJECT-TYPE SYNTAX SeHdpmChannelCircuitNameEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A single channel name." INDEX { seHdpmChannelCircuitNameIndex } ::= { seHdpmChannelCircuitNameTable 1 } SeHdpmChannelCircuitNameEntry ::= SEQUENCE { seHdpmChannelCircuitNameIndex ChannelCircuitNameIndex, seHdpmChannelCircuitName OCTET STRING } seHdpmChannelCircuitNameIndex OBJECT-TYPE SYNTAX ChannelCircuitNameIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "The channel number. Between 1 and 192." ::= { seHdpmChannelCircuitNameEntry 1 } seHdpmChannelCircuitName OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Channel Circuit name." ::= { seHdpmChannelCircuitNameEntry 2 } seHdpmChannelRackNameTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmChannelRackNameEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of Rack names associated with each channel or circuit. Circuits built from 2 or 3 channels (branch circuits) will show a Rack name in the first channel position with the following channel or two blank" ::= { seHdpmSystem 13 } seHdpmChannelRackNameEntry OBJECT-TYPE SYNTAX SeHdpmChannelRackNameEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A single rack name associated with a channel or circuit." INDEX { seHdpmChannelRackNameIndex } ::= { seHdpmChannelRackNameTable 1 } SeHdpmChannelRackNameEntry ::= SEQUENCE { seHdpmChannelRackNameIndex ChannelRackNameIndex, seHdpmChannelRackName OCTET STRING } seHdpmChannelRackNameIndex OBJECT-TYPE SYNTAX ChannelRackNameIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "The channel number. Between 1 and 192." ::= { seHdpmChannelRackNameEntry 1 } seHdpmChannelRackName OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Rack name associated with the channel or circuit." ::= { seHdpmChannelRackNameEntry 2 } seHdpmSystemPtRatio OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The Potential Transformer ratio X:1 between the meter and line voltage. In units of thousandths, so the default 1000 is 1.000:1 (no PT present)." ::= { seHdpmSystem 14 } -- -- The module table -- seHdpmModuleNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of modules in the system. This is currently in the range of 1..N" ::= { seHdpmModules 1 } seHdpmModuleTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmModuleEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of data modules in the system." ::= { seHdpmModules 2 } seHdpmModuleEntry OBJECT-TYPE SYNTAX SeHdpmModuleEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single module in the system." INDEX { seHdpmModuleIndex } ::= { seHdpmModuleTable 1 } SeHdpmModuleEntry ::= SEQUENCE { seHdpmModuleIndex ModuleIndex, seHdpmModuleSerialNumber Integer32, seHdpmModuleChannels Integer32 } seHdpmModuleIndex OBJECT-TYPE SYNTAX ModuleIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the module. This will a number in the range of 1..N where each module will be assigned the next available number in the range." ::= { seHdpmModuleEntry 1 } seHdpmModuleSerialNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number for the module." ::= { seHdpmModuleEntry 2 } seHdpmModuleChannels OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of single phase channels (branch circuits) on the module. This will be a number in the range of 1..N where N is often 21. As the modules are listed in order, the channel (branch circuit)counts can be used to determine which channels are on which module without having to enumerate the channels." ::= { seHdpmModuleEntry 3 } -- -- The Channel table -- seHdpmChannelNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The total number of single phase circuits (branch circuits, channels) in the system. This is the sum of all branch circuits across all modules in the system, excluding the Head Unit and other stand alone Meters. This is a number in the range of 1..N. The total number of circuits is related to module capacity vs. connected circuits. That is, if a module has 21 channels on it but only one channel is attached to a CT, the module will still report 21 channels (branch circuits)." ::= { seHdpmChannels 1 } seHdpmChannelTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmChannelEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of single phase channels (branch circuits) in the system." ::= { seHdpmChannels 2 } seHdpmChannelEntry OBJECT-TYPE SYNTAX SeHdpmChannelEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single channel (branch circuit) on a module." INDEX { seHdpmChannelIndex } ::= { seHdpmChannelTable 1 } SeHdpmChannelEntry ::= SEQUENCE { seHdpmChannelIndex ChannelIndex, seHdpmChannelModuleIndex ModuleIndex, seHdpmChannelToCircuitAssignment Integer32, seHdpmChannelCtType INTEGER, seHdpmChannelCtFactor Integer32, seHdpmChannelPhase INTEGER, seHdpmChannelExpectedPhase INTEGER, seHdpmChannelWh Integer32, seHdpmChannelVoltsRms Integer32, seHdpmChannelVoltsRmsSqHi Integer32, seHdpmChannelVoltsRmsSqLo Integer32, seHdpmChannelAmpsRms Integer32, seHdpmChannelAmpsRmsSqHi Integer32, seHdpmChannelAmpsRmsSqLo Integer32, seHdpmChannelPF Integer32, seHdpmChannelPFSqHi Integer32, seHdpmChannelPFSqLo Integer32, seHdpmChannelWatt Integer32, seHdpmChannelWattSqHi Integer32, seHdpmChannelWattSqLo Integer32, seHdpmChannelSamples Counter32, seHdpmChannelAvgVoltsRms Integer32, seHdpmChannelAvgAmpsRms Integer32, seHdpmChannelAvgPF Integer32, seHdpmChannelAvgWatt Integer32, seHdpmChannelWattMax Integer32, seHdpmChannelWattMaxTime DateAndTime, seHdpmChannelLoadType LoadTypeIndex } seHdpmChannelIndex OBJECT-TYPE SYNTAX ChannelIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the Circuit. This is a number in the range of 1..N where N is the total number of channels. Each subsequent circuit will be assigned the next index value." ::= { seHdpmChannelEntry 1 } seHdpmChannelModuleIndex OBJECT-TYPE SYNTAX ModuleIndex MAX-ACCESS read-only STATUS current DESCRIPTION "Which module in the module table this channel (branch circuit) is associated with. This is a number in the range of 1..N" ::= { seHdpmChannelEntry 2 } seHdpmChannelToCircuitAssignment OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "A number in the range of 1..N where N is the total number of circuits in the system that indicates how circuits should be grouped into multi-phase groups. * Channels (branch circuits) that have a unique group number will be treated as single phase circuits. * If two channels have the same group number then these will be treated as a two phase circuit. * If three channels have the same group number then these will be treated as a three phase circuit." ::= { seHdpmChannelEntry 3 } seHdpmChannelCtType OBJECT-TYPE SYNTAX INTEGER { ct50amp(50), ct100amp(100), ct250amp(250), ct500amp(500), ct1000amp(1000), ct2000amp(2000), ct3000amp(3000) } MAX-ACCESS read-only STATUS current DESCRIPTION "This is a number to identify a CT and is the max current of the CT. Old style values are the current rating of the CT. Examples are: 50, 100, 250, 500, 1000, 2000, 3000. New style entries are of the form 32xxx and encode an offset into the seHdpmCtTypeName, seHdpmCtTypeFactor1 & 2, and seHdpmCtTypePHCAL1 & 2 tables. To calculate the offset, subtract the value from 32768. The result is the one based table offset." ::= { seHdpmChannelEntry 4 } seHdpmChannelCtFactor OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The CT factor associated with the CT for this circuit." ::= { seHdpmChannelEntry 5 } seHdpmChannelPhase OBJECT-TYPE SYNTAX INTEGER { notConnected(0), phase1(1), phase2(2), phase3(3), neutral(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "The voltage phase this circuit is connected to. Possible values are: 0..4 where a value of 0 indicates that the circuit is not connected." ::= { seHdpmChannelEntry 6 } seHdpmChannelExpectedPhase OBJECT-TYPE SYNTAX INTEGER { notConnected(0), phase1(1), phase2(2), phase3(3), neutral(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "The voltage phase this circuit is supposed to be connected to as set during initial board setup. When properly configured, this should have the same value as seHdpmChannelPhase. Possible values are: 0..4" ::= { seHdpmChannelEntry 7 } seHdpmChannelWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated Real (Active, Ph) Energy in units of watt hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 watt hours)." ::= { seHdpmChannelEntry 8 } seHdpmChannelVoltsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Volts RMS in units of tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmChannelEntry 9 } seHdpmChannelVoltsRmsSqHi OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Upper 32bits of the sum of squared Volts RMS samples (useful for stardard deviation)." ::= { seHdpmChannelEntry 10 } seHdpmChannelVoltsRmsSqLo OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Lower 32bits of the sum of squared Volts RMS samples (useful for stardard deviation)." ::= { seHdpmChannelEntry 11 } seHdpmChannelAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Amps RMS in hundredths of an amp divided by the value of seHdpmSystemAmpsScale (ie. when AmpsScale=10, this counter is in units of tenths of an amp)." ::= { seHdpmChannelEntry 12 } seHdpmChannelAmpsRmsSqHi OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Upper 32bits of the sum of squared Amps RMS samples (useful for standard deviation)." ::= { seHdpmChannelEntry 13 } seHdpmChannelAmpsRmsSqLo OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Lower 32bits of the Sum of squared Amps RMS samples (useful for standard deviation)." ::= { seHdpmChannelEntry 14 } seHdpmChannelPF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of (power factor * 1000) samples." ::= { seHdpmChannelEntry 15 } seHdpmChannelPFSqHi OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Upper 32bits of the sum of squared (power factor * 1000) samples (useful for standard deviation)." ::= { seHdpmChannelEntry 16 } seHdpmChannelPFSqLo OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Lower 32bits of the sum of squared (power factor * 1000) samples (useful for standard deviation)." ::= { seHdpmChannelEntry 17 } seHdpmChannelWatt OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Watts divided by the value of seHdpmSystemPowerScale (ie. when PowerScale=10, this counter is in units of 10 watts)." ::= { seHdpmChannelEntry 18 } seHdpmChannelWattSqHi OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Upper 32bits of the sum of squared watt samples (useful for standard deviation)." ::= { seHdpmChannelEntry 19 } seHdpmChannelWattSqLo OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Lower 32bits of the sum of squared watt samples (useful for standard deviation)." ::= { seHdpmChannelEntry 20 } seHdpmChannelSamples OBJECT-TYPE SYNTAX Counter32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of samples performed. Used to normalize other summing counters." ::= { seHdpmChannelEntry 21 } seHdpmChannelAvgVoltsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Running average of Volts RMS in tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this is in units of 10 volts)." ::= { seHdpmChannelEntry 22 } seHdpmChannelAvgAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Running average of Amps RMS in hundredths of an amp divided by the value of seHdpmSystemAmpsScale (ie. when AmpsScale=10, this is in units of tenths of an amp.)." ::= { seHdpmChannelEntry 23 } seHdpmChannelAvgPF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Running average of (power factor * 1000)" ::= { seHdpmChannelEntry 24 } seHdpmChannelAvgWatt OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Running average of Watts." ::= { seHdpmChannelEntry 25 } seHdpmChannelWattMax OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum Watt seen." ::= { seHdpmChannelEntry 26 } seHdpmChannelWattMaxTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "Time of maximum Watts seen." ::= { seHdpmChannelEntry 27 } seHdpmChannelLoadType OBJECT-TYPE SYNTAX LoadTypeIndex MAX-ACCESS read-only STATUS current DESCRIPTION "The index of the load type. Between 1 and 20 specifies the load type, 0 means there is no load type." ::= { seHdpmChannelEntry 28 } -- -- AC sources -- seHdpmACMeterNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of AC meters the system is configured for. This is a number in the range of 1..N. Modules on the bus are not included." ::= { seHdpmACMeters 1 } seHdpmACMetersTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmACMetersEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of 3-phase AC meters in the system. The first entry in the Head Unit PQM" ::= { seHdpmACMeters 2 } seHdpmACMetersPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmACMetersPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of voltage phases in the system. Each AC meter typically has 3 entries, one for each phase. The first three phases are the Head Unit PQM" ::= { seHdpmACMeters 3 } seHdpmACMetersEntry OBJECT-TYPE SYNTAX SeHdpmACMetersEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single AC meter in the system, typically three phase." INDEX { seHdpmACMeterIndex } ::= { seHdpmACMetersTable 1 } seHdpmACMetersPhaseEntry OBJECT-TYPE SYNTAX SeHdpmACMetersPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single phase of an AC meter in the system. The first three entries are the Head Unit PQM. The next three entries are the estimated parameters for the primary side of a step down transformer, if enabled." INDEX { seHdpmACMeterIndex, seHdpmACMeterNumberOfPhases } ::= { seHdpmACMetersPhaseTable 1 } SeHdpmACMetersEntry ::= SEQUENCE { seHdpmACMeterIndex ACMeterIndex, seHdpmACMeterNumberOfPhases PhaseIndex, seHdpmACMeterVoltsRms Integer32, seHdpmACMeterAmpsRms Integer32, seHdpmACMeterPF Integer32, seHdpmACMeterWatt Integer32, seHdpmACMeterVAR Integer32, seHdpmACMeterTHDv Integer32, seHdpmACMeterTHDi Integer32, seHdpmACMeterWh Integer32, seHdpmACMeterVARh Integer32, seHdpmACMeterFreq Integer32, seHdpmACMeterAmpsRmsavg Integer32, seHdpmACMeterVAh Integer32, seHdpmACMeterCurrentImbalance Integer32, seHdpmACMeterVoltageImbalance Integer32, seHdpmACMeterTotalDemandDistortion Integer32 } seHdpmACMeterIndex OBJECT-TYPE SYNTAX ACMeterIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the AC source. This is a number in the range of 1..N. Each subsequent source will be assigned the next index value." ::= { seHdpmACMetersEntry 1 } seHdpmACMeterNumberOfPhases OBJECT-TYPE SYNTAX PhaseIndex MAX-ACCESS read-only STATUS current DESCRIPTION "The number of phases in an AC source." ::= { seHdpmACMetersEntry 2 } seHdpmACMeterVoltsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average of Phase Volts RMS in units of tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmACMetersEntry 3 } seHdpmACMeterAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total of Phase Amps RMS in units of milliamps." ::= { seHdpmACMetersEntry 4 } seHdpmACMeterPF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Meter Power Factor * 1000." ::= { seHdpmACMetersEntry 5 } seHdpmACMeterWatt OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total of Phase Watts (Real Active Power, P)." ::= { seHdpmACMetersEntry 6 } seHdpmACMeterVAR OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total of Phase VAR (Reactive Energy, Q)." ::= { seHdpmACMetersEntry 7 } seHdpmACMeterTHDv OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average of Voltage Total Harmonic Distortion on the Phases." ::= { seHdpmACMetersEntry 8 } seHdpmACMeterTHDi OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average of Current Total Harmonic Distortion on the Phases." ::= { seHdpmACMetersEntry 9 } seHdpmACMeterWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated Real Energy (watt hours, Ph) in units of watt hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 watt hours)." ::= { seHdpmACMetersEntry 10 } seHdpmACMeterVARh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated Reactive Energy (VAR hours, Qh) in units of VAR hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 VAR hours)." ::= { seHdpmACMetersEntry 11 } seHdpmACMeterFreq OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Line Frequency." ::= { seHdpmACMetersEntry 12 } seHdpmACMeterAmpsRmsavg OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average of Phase Amps RMS in units of milliamps." ::= { seHdpmACMetersEntry 13 } seHdpmACMeterVAh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated Apparent Energy (VA hours, Sh) in units of watt hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 watt hours)." ::= { seHdpmACMetersEntry 14 } seHdpmACMeterCurrentImbalance OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current Imbalance = (In - Iave) / Iave, where In is the phase with the largest difference from the average of the phase currents Iave." ::= { seHdpmACMetersEntry 15 } seHdpmACMeterVoltageImbalance OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage Imbalance = (Vn - Vave) / Vave, where Vn is the phase with the largest difference from the average of the phase voltages Vave." ::= { seHdpmACMetersEntry 16 } seHdpmACMeterTotalDemandDistortion OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Demand distortion is the Root Mean Square of each phase current multiplied by the phase THDi. This is then divided by the Circuit Breaker Rating." ::= { seHdpmACMetersEntry 17 } SeHdpmACMetersPhaseEntry ::= SEQUENCE { seHdpmACMeterPhaseIndex PhaseIndex, seHdpmACMeterPhaseVoltsRms Integer32, seHdpmACMeterPhaseAmpsRms Integer32, seHdpmACMeterPhasePF Integer32, seHdpmACMeterPhaseWatt Integer32, seHdpmACMeterPhaseVAR Integer32, seHdpmACMeterPhaseTHDv Integer32, seHdpmACMeterPhaseTHDi Integer32, seHdpmACMeterPhaseWh Integer32, seHdpmACMeterPhaseVARh Integer32, seHdpmACMeterPhaseFreq Integer32, seHdpmACMeterPhaseWattMax Integer32, seHdpmACMeterPhaseWattMaxTime DateAndTime, seHdpmACMeterPhaseVAh Integer32, seHdpmACMeterPhaseDPF Integer32 } seHdpmACMeterPhaseIndex OBJECT-TYPE SYNTAX PhaseIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the phase. This is a number in the range of 1..4. A value of 4 is the neutral phase." ::= { seHdpmACMetersPhaseEntry 1 } seHdpmACMeterPhaseVoltsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of VoltsRms samples in units of tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmACMetersPhaseEntry 2 } seHdpmACMeterPhaseAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Amps RMS on a Meter Phase in units of milliamps." ::= { seHdpmACMetersPhaseEntry 3 } seHdpmACMeterPhasePF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Power Factor * 1000 on a meter phase." ::= { seHdpmACMetersPhaseEntry 4 } seHdpmACMeterPhaseWatt OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Watts (Real Active Power, P) on a meter phase." ::= { seHdpmACMetersPhaseEntry 5 } seHdpmACMeterPhaseVAR OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "VAR (Reactive Power, Q) on a meter phase." ::= { seHdpmACMetersPhaseEntry 6 } seHdpmACMeterPhaseTHDv OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage THD." ::= { seHdpmACMetersPhaseEntry 7 } seHdpmACMeterPhaseTHDi OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current THD." ::= { seHdpmACMetersPhaseEntry 8 } seHdpmACMeterPhaseWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated Watt hours (Real Energy, Ph) in units of watt hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 watt hours)." ::= { seHdpmACMetersPhaseEntry 9 } seHdpmACMeterPhaseVARh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated VAR hours (Reactive Energy, Qh) in units of VAR hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 VAR hours)." ::= { seHdpmACMetersPhaseEntry 10 } seHdpmACMeterPhaseFreq OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of frequency samples." ::= { seHdpmACMetersPhaseEntry 11 } seHdpmACMeterPhaseWattMax OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum watts seen." ::= { seHdpmACMetersPhaseEntry 12 } seHdpmACMeterPhaseWattMaxTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "Time of maximum watts seen." ::= { seHdpmACMetersPhaseEntry 13 } seHdpmACMeterPhaseVAh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated VAh (Apparent Energy, Sh) in units of VA hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 VA hours)." ::= { seHdpmACMetersPhaseEntry 14 } seHdpmACMeterPhaseDPF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Displacement Power Factor * 1000 on a meter phase." ::= { seHdpmACMetersPhaseEntry 15 } -- -- Circuit Summaries -- seHdpmCircuitSummariesNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of Circuit (branch circuit) summaries in the system. This is a number in the range of 1..N. If 1, all Circuits are presented in a single summary. The system may be configured to create summaries for each Tap Module, where each Module is assumed to instrument a single panel." ::= { seHdpmCircuitSummaries 1 } seHdpmCircuitSummaryTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmCircuitSummaryEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of Circuit (branch circuit) summaries in the system." ::= { seHdpmCircuitSummaries 2 } seHdpmCircuitSummaryPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmCircuitSummaryPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of phases for each circuit summary in the system. Each Circuit Summary typically has four entries for phases ABCN. The first group of four entries will be the from the first Circuit Summary, the second group of four would be from the second circuit summary, ..." ::= { seHdpmCircuitSummaries 3 } seHdpmCircuitSummaryEntry OBJECT-TYPE SYNTAX SeHdpmCircuitSummaryEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single circuit summary in the system. This may be for the entire system, or a summary for each module & panel in the system." INDEX { seHdpmCircuitSummaryIndex } ::= { seHdpmCircuitSummaryTable 1 } seHdpmCircuitSummaryPhaseEntry OBJECT-TYPE SYNTAX SeHdpmCircuitSummaryPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single phase in a circuit summary in the system." INDEX { seHdpmCircuitSummaryIndex, seHdpmCircuitSummaryPhaseIndex } ::= { seHdpmCircuitSummaryPhaseTable 1 } SeHdpmCircuitSummaryEntry ::= SEQUENCE { seHdpmCircuitSummaryIndex ChannelSummaryIndex, seHdpmCircuitSummaryPhasesNumber ChannelSummaryPhaseIndex, seHdpmCircuitSummaryAveVoltsRms Integer32, seHdpmCircuitSummaryTotalAmpsRms Integer32, seHdpmCircuitSummaryAvePF Integer32, seHdpmCircuitSummaryTotalWatts Integer32, seHdpmCircuitSummaryTotalWh Integer32, seHdpmCircuitSummaryAveAmpsRms Integer32 } seHdpmCircuitSummaryIndex OBJECT-TYPE SYNTAX ChannelSummaryIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the channel (branch circuit) summary. This is a number in the range of 1..N. Each subsequent summary will be assigned the next index value." ::= { seHdpmCircuitSummaryEntry 1 } seHdpmCircuitSummaryPhasesNumber OBJECT-TYPE SYNTAX ChannelSummaryPhaseIndex MAX-ACCESS read-only STATUS current DESCRIPTION "The number of phases in a circuit summary. Includes Neutral if supported" ::= { seHdpmCircuitSummaryEntry 2 } seHdpmCircuitSummaryAveVoltsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of the RMS Voltage samples in units of tenths of a volt. Divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmCircuitSummaryEntry 3 } seHdpmCircuitSummaryTotalAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total of RMS current on all circuits in units of milliamps." ::= { seHdpmCircuitSummaryEntry 4 } seHdpmCircuitSummaryAvePF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average of the PF on all circuits (power factor * 1000)." ::= { seHdpmCircuitSummaryEntry 5 } seHdpmCircuitSummaryTotalWatts OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of watts on all circuits. Unit is Watts" ::= { seHdpmCircuitSummaryEntry 6 } seHdpmCircuitSummaryTotalWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated Real Energy (watt hours, Ph) in units of watt hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 watt hours)." ::= { seHdpmCircuitSummaryEntry 7 } seHdpmCircuitSummaryAveAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Avg of RMS current across the phases in a summary, in units of milliamps." ::= { seHdpmCircuitSummaryEntry 8 } SeHdpmCircuitSummaryPhaseEntry ::= SEQUENCE { seHdpmCircuitSummaryPhaseIndex CircuitSummaryPhaseIndex, seHdpmCircuitSummaryPhaseVoltsRms Integer32, seHdpmCircuitSummaryPhaseAmpsRms Integer32, seHdpmCircuitSummaryPhasePF Integer32, seHdpmCircuitSummaryPhaseWatt Integer32, seHdpmCircuitSummaryPhaseWh Integer32 } seHdpmCircuitSummaryPhaseIndex OBJECT-TYPE SYNTAX CircuitSummaryPhaseIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the phase. This is a number in the range of 1..4. A value of 4 is the neutral phase." ::= { seHdpmCircuitSummaryPhaseEntry 1 } seHdpmCircuitSummaryPhaseVoltsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average of VoltsRms in units of tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmCircuitSummaryPhaseEntry 2 } seHdpmCircuitSummaryPhaseAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of the currents on all channels on a single phase in units of milliamps." ::= { seHdpmCircuitSummaryPhaseEntry 3 } seHdpmCircuitSummaryPhasePF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average power factor * 1000 of the channels on a single phase." ::= { seHdpmCircuitSummaryPhaseEntry 4 } seHdpmCircuitSummaryPhaseWatt OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total watts on all channels associated with a single phase in units of watts." ::= { seHdpmCircuitSummaryPhaseEntry 5 } seHdpmCircuitSummaryPhaseWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated Real Energy (watt hours, Ph) for all channels in units of watt hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 watt hours)." ::= { seHdpmCircuitSummaryPhaseEntry 6 } -- -- DC sources -- seHdpmDCMeterNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of DC sources in the system. This is a number in the range of 1..N." ::= { seHdpmDCMeters 1 } seHdpmDCMeterTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmDCMeterEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of DC sources in the system." ::= { seHdpmDCMeters 2 } seHdpmDCMeterEntry OBJECT-TYPE SYNTAX SeHdpmDCMeterEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single DC source in the system." INDEX { seHdpmDCMeterIndex } ::= { seHdpmDCMeterTable 1 } SeHdpmDCMeterEntry ::= SEQUENCE { seHdpmDCMeterIndex DCMeterIndex, seHdpmDCMeterV Integer32 } seHdpmDCMeterIndex OBJECT-TYPE SYNTAX DCMeterIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the DC source. This is a number in the range of 1..N. Each subsequent source will be assigned the next index value." ::= { seHdpmDCMeterEntry 1 } seHdpmDCMeterV OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of V samples in tenths of a volt." ::= { seHdpmDCMeterEntry 2 } -- -- DryContact sources -- seHdpmDryContactsNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of dry contact modules in the system. This is a number in the range of 1..N." ::= { seHdpmDryContacts 1 } seHdpmDryContactTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmDryContactEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of dry contact modules in the system." ::= { seHdpmDryContacts 2 } seHdpmDryContactEntry OBJECT-TYPE SYNTAX SeHdpmDryContactEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single dry contact module in the system." INDEX { seHdpmDryContactIndex } ::= { seHdpmDryContactTable 1 } SeHdpmDryContactEntry ::= SEQUENCE { seHdpmDryContactIndex DryContactIndex, seHdpmDryContactV Integer32, seHdpmDryContactAmpsRms Integer32, seHdpmDryContactDigIn Integer32 } seHdpmDryContactIndex OBJECT-TYPE SYNTAX DryContactIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the dry contact module. This is a number in the range of 1..N. Each subsequent source will be assigned the next index value." ::= { seHdpmDryContactEntry 1 } seHdpmDryContactV OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of V samples in hundredths of a volt." ::= { seHdpmDryContactEntry 2 } seHdpmDryContactAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of AmpsRms samples in hundredths of an amp." ::= { seHdpmDryContactEntry 3 } seHdpmDryContactDigIn OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Bitfield of dry contact module's digital inputs." ::= { seHdpmDryContactEntry 4 } -- -- Volts/Amps/Watts tables. -- Fast access to instantaneous parameters. Particularly useful with fast update rates. -- seHdpmCircuitVoltsAmpsWatts OBJECT IDENTIFIER ::= { seHdpmVoltsAmpsWatts 1 } seHdpmMeterPhaseVoltsAmpsWatts OBJECT IDENTIFIER ::= { seHdpmVoltsAmpsWatts 2 } -- -- Volts/Amps/Watts table by Circuit -- seHdpmCircuitVoltsAmpsWattsCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "This is a number in the range of 1..N, the number of branch circuits (channels) in the system. This is the sum of all circuits across all modules in the system. The total number of channels is related to module capacity vs. connected circuits. That is, if a module has 21 channels on it but only one channel is attached to a CT, the module will still report 21 channels (single phase branch circuits)." ::= { seHdpmCircuitVoltsAmpsWatts 1 } seHdpmCircuitVoltsAmpsWattsTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmCircuitVoltsAmpsWattsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of circuits in the system." ::= { seHdpmCircuitVoltsAmpsWatts 2 } seHdpmCircuitVoltsAmpsWattsEntry OBJECT-TYPE SYNTAX SeHdpmCircuitVoltsAmpsWattsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single circuit in the system." INDEX { seHdpmCircuitVoltsAmpsWattsIndex } ::= { seHdpmCircuitVoltsAmpsWattsTable 1 } SeHdpmCircuitVoltsAmpsWattsEntry ::= SEQUENCE { seHdpmCircuitVoltsAmpsWattsIndex ChannelIndex, seHdpmCircuitVoltsRMS Integer32, seHdpmCircuitAmpsRMS Integer32, seHdpmCircuitWatts Integer32 } seHdpmCircuitVoltsAmpsWattsIndex OBJECT-TYPE SYNTAX ChannelIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the circuit. This is a number in the range of 1..N where N is the total number of circuits. Each subsequent circuit will be assigned the next index value." ::= { seHdpmCircuitVoltsAmpsWattsEntry 1 } seHdpmCircuitVoltsRMS OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Volts RMS in tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmCircuitVoltsAmpsWattsEntry 2 } seHdpmCircuitAmpsRMS OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Amps RMS in hundredths of an amp divided by the value of seHdpmSystemAmpsScale (ie. when AmpsScale=10, this counter is in units of tenths of an amp)." ::= { seHdpmCircuitVoltsAmpsWattsEntry 3 } seHdpmCircuitWatts OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Watts divided by the value of seHdpmSystemPowerScale (ie. when PowerScale=10, this counter is in units of 10 watts)." ::= { seHdpmCircuitVoltsAmpsWattsEntry 4 } -- -- AC Meter Phase Volts Amps Watts -- seHdpmMeterPhaseVoltsAmpsWattsNumber OBJECT-TYPE SYNTAX PhaseIndex MAX-ACCESS read-only STATUS current DESCRIPTION "The number of phases in an AC Meter." ::= { seHdpmMeterPhaseVoltsAmpsWatts 1 } seHdpmMeterPhaseVoltsAmpsWattsTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmMeterPhaseVoltsAmpsWattsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of phases in the system." ::= { seHdpmMeterPhaseVoltsAmpsWatts 2 } seHdpmMeterPhaseVoltsAmpsWattsEntry OBJECT-TYPE SYNTAX SeHdpmMeterPhaseVoltsAmpsWattsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single phase in the system." INDEX { seHdpmMeterPhaseVoltsAmpsWattsIndex } ::= { seHdpmMeterPhaseVoltsAmpsWattsTable 1 } SeHdpmMeterPhaseVoltsAmpsWattsEntry ::= SEQUENCE { seHdpmMeterPhaseVoltsAmpsWattsIndex PhaseIndex, seHdpmMeterPhaseVoltsRMS Integer32, seHdpmMeterPhaseAmpsRMS Integer32, seHdpmMeterPhaseWatts Integer32 } seHdpmMeterPhaseVoltsAmpsWattsIndex OBJECT-TYPE SYNTAX PhaseIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the phase. This is a number in the range of 1..4. A value of 4 is the neutral phase." ::= { seHdpmMeterPhaseVoltsAmpsWattsEntry 1 } seHdpmMeterPhaseVoltsRMS OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "VoltsRms in tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmMeterPhaseVoltsAmpsWattsEntry 2 } seHdpmMeterPhaseAmpsRMS OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "AmpsRms in milliamps." ::= { seHdpmMeterPhaseVoltsAmpsWattsEntry 3 } seHdpmMeterPhaseWatts OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Watts." ::= { seHdpmMeterPhaseVoltsAmpsWattsEntry 4 } -- -- The environmental sensors tables -- seHdpmEnvironmentalSensorsNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of environmental sensors in the system." ::= { seHdpmEnvironmentalSensors 1 } seHdpmEnvironmentalSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmEnvironmentalSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of environmental sensors in the system." ::= { seHdpmEnvironmentalSensors 2 } seHdpmEnvironmentalSensorEntry OBJECT-TYPE SYNTAX SeHdpmEnvironmentalSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single environmental sensor." INDEX { seHdpmEnvironmentalSensorIndex } ::= { seHdpmEnvironmentalSensorTable 1 } SeHdpmEnvironmentalSensorEntry ::= SEQUENCE { seHdpmEnvironmentalSensorIndex EnvironmentalSensorIndex, seHdpmEnvironmentalSensorID EnvironmentalSensorID, seHdpmEnvironmentalSensorTemperatureNumber Counter32, seHdpmEnvironmentalSensorHumidityNumber Counter32, seHdpmEnvironmentalSensorTAP EnvironmentalSensorTAP, seHdpmEnvironmentalSensorPort EnvironmentalSensorPort } seHdpmEnvironmentalSensorIndex OBJECT-TYPE SYNTAX EnvironmentalSensorIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the environmental sensor. This is a number in the range of 1..N where N is the total number of sensors. Each subsequent sensor will be assigned the next index value." ::= { seHdpmEnvironmentalSensorEntry 1 } seHdpmEnvironmentalSensorID OBJECT-TYPE SYNTAX EnvironmentalSensorID MAX-ACCESS read-only STATUS current DESCRIPTION "D1W ID of the environmental sensor." ::= { seHdpmEnvironmentalSensorEntry 2 } seHdpmEnvironmentalSensorTemperatureNumber OBJECT-TYPE SYNTAX Counter32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of temperature data points provided by the environmental sensor." ::= { seHdpmEnvironmentalSensorEntry 3 } seHdpmEnvironmentalSensorHumidityNumber OBJECT-TYPE SYNTAX Counter32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of humidity data points provided by the environmental sensor." ::= { seHdpmEnvironmentalSensorEntry 4 } seHdpmEnvironmentalSensorTAP OBJECT-TYPE SYNTAX EnvironmentalSensorTAP MAX-ACCESS read-only STATUS current DESCRIPTION "Host TAP ID of the environmental sensor." ::= { seHdpmEnvironmentalSensorEntry 5 } seHdpmEnvironmentalSensorPort OBJECT-TYPE SYNTAX EnvironmentalSensorPort MAX-ACCESS read-only STATUS current DESCRIPTION "Host port of the environmental sensor." ::= { seHdpmEnvironmentalSensorEntry 6 } seHdpmEnvironmentalTemperatureDataPointsNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of temperature data points per sensor." ::= { seHdpmEnvironmentalSensors 3 } seHdpmEnvironmentalTemperatureTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmEnvironmentalTemperatureEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of environmental temperature data points." ::= { seHdpmEnvironmentalSensors 4 } seHdpmEnvironmentalTemperatureEntry OBJECT-TYPE SYNTAX SeHdpmEnvironmentalTemperatureEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single environmental temperature data point." INDEX { seHdpmEnvironmentalTemperatureIndex } ::= { seHdpmEnvironmentalTemperatureTable 1 } SeHdpmEnvironmentalTemperatureEntry ::= SEQUENCE { seHdpmEnvironmentalTemperatureIndex EnvironmentalTemperatureIndex, seHdpmEnvironmentalTemperatureSensorID EnvironmentalSensorID, seHdpmEnvironmentalSensorTemperatureIndex Integer32, seHdpmTemperature Integer32 } seHdpmEnvironmentalTemperatureIndex OBJECT-TYPE SYNTAX EnvironmentalTemperatureIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the environmental temperature data point." ::= { seHdpmEnvironmentalTemperatureEntry 1 } seHdpmEnvironmentalTemperatureSensorID OBJECT-TYPE SYNTAX EnvironmentalSensorID MAX-ACCESS read-only STATUS current DESCRIPTION "D1W ID of the environmental sensor." ::= { seHdpmEnvironmentalTemperatureEntry 2 } seHdpmEnvironmentalSensorTemperatureIndex OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Index of sensor's temperature data points 1-N where N is the number of temperature data points provided by the sensor." ::= { seHdpmEnvironmentalTemperatureEntry 3 } seHdpmTemperature OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature in tenths of a Celsius." ::= { seHdpmEnvironmentalTemperatureEntry 4 } seHdpmEnvironmentalHumidityDataPointsNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of temperature data points per sensor." ::= { seHdpmEnvironmentalSensors 5 } seHdpmEnvironmentalHumidityTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmEnvironmentalHumidityEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of environmental temperature data points." ::= { seHdpmEnvironmentalSensors 6 } seHdpmEnvironmentalHumidityEntry OBJECT-TYPE SYNTAX SeHdpmEnvironmentalHumidityEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single environmental temperature data point." INDEX { seHdpmEnvironmentalHumidityIndex } ::= { seHdpmEnvironmentalHumidityTable 1 } SeHdpmEnvironmentalHumidityEntry ::= SEQUENCE { seHdpmEnvironmentalHumidityIndex EnvironmentalHumidityIndex, seHdpmEnvironmentalHumiditySensorID EnvironmentalSensorID, seHdpmEnvironmentalSensorHumidityIndex Integer32, seHdpmHumidity Integer32 } seHdpmEnvironmentalHumidityIndex OBJECT-TYPE SYNTAX EnvironmentalHumidityIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the environmental temperature data point." ::= { seHdpmEnvironmentalHumidityEntry 1 } seHdpmEnvironmentalHumiditySensorID OBJECT-TYPE SYNTAX EnvironmentalSensorID MAX-ACCESS read-only STATUS current DESCRIPTION "D1W ID of the environmental sensor." ::= { seHdpmEnvironmentalHumidityEntry 2 } seHdpmEnvironmentalSensorHumidityIndex OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Index of sensor's humidity data points 1-N where N is the number of humidity data points provided by the sensor." ::= { seHdpmEnvironmentalHumidityEntry 3 } seHdpmHumidity OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Humidity in tenths of a percent." ::= { seHdpmEnvironmentalHumidityEntry 4 } -- -- Circuits -- seHdpmCircuitsNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of circuits in the system. This is a number in the range of 1..N." ::= { seHdpmCircuits 1 } seHdpmCircuitTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmCircuitEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of circuits in the system. Each circuit is composed from one to three channels (branch circuits)." ::= { seHdpmCircuits 2 } seHdpmCircuitPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmCircuitPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of phases in the circuit." ::= { seHdpmCircuits 3 } seHdpmCircuitEntry OBJECT-TYPE SYNTAX SeHdpmCircuitEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single circuit summary in the group." INDEX { seHdpmCircuitIndex } ::= { seHdpmCircuitTable 1 } seHdpmCircuitPhaseEntry OBJECT-TYPE SYNTAX SeHdpmCircuitPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single phase in the circuit." INDEX { seHdpmCircuitIndex, seHdpmCircuitPhaseIndex } ::= { seHdpmCircuitPhaseTable 1 } SeHdpmCircuitEntry ::= SEQUENCE { seHdpmCircuitIndex CircuitSummaryIndex, seHdpmCircuitNumber Integer32, seHdpmCircuitNumPhases Integer32, seHdpmCircuitAveVoltsRms Integer32, seHdpmCircuitSumAmpsRms Integer32, seHdpmCircuitPF Integer32, seHdpmCircuitSumWatts Integer32, seHdpmCircuitSumVAR Integer32, seHdpmCircuitSumVA Integer32, seHdpmCircuitAveTHDi Integer32, seHdpmCircuitTotalWh Integer32, seHdpmCircuitAveAmpsRms Integer32, seHdpmCircuitAveVLLRMS Integer32, seHdpmCircuitSumWattMax Integer32, seHdpmCircuitSumWattMaxTime DateAndTime, seHdpmCircuitCurrentImbalance Integer32 } seHdpmCircuitIndex OBJECT-TYPE SYNTAX CircuitSummaryIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the circuit summary. This is a number in the range of 1..N. Each subsequent summary will be assigned the next index value." ::= { seHdpmCircuitEntry 1 } seHdpmCircuitNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The unique group number assigned to the channels (branch circuits) forming the group." ::= { seHdpmCircuitEntry 2 } seHdpmCircuitNumPhases OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of phases (channels) in each circuit." ::= { seHdpmCircuitEntry 3 } seHdpmCircuitAveVoltsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average of Volts RMS of the phases assigned to a circuit. In units of tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmCircuitEntry 4 } seHdpmCircuitSumAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of the phase currents in a circuit, in units of millamps." ::= { seHdpmCircuitEntry 5 } seHdpmCircuitPF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "PF (power factor * 1000) for the entire circuit." ::= { seHdpmCircuitEntry 6 } seHdpmCircuitSumWatts OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of watts (Real Power) for the phases in a circuit, in units of watts." ::= { seHdpmCircuitEntry 7 } seHdpmCircuitSumVAR OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of VAR (Reactive Power) for the phases in a circuit, in units of VAR." ::= { seHdpmCircuitEntry 8 } seHdpmCircuitSumVA OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Sum of VA (Apparent Power) for the phases in a circuit, in units of VA." ::= { seHdpmCircuitEntry 9 } seHdpmCircuitAveTHDi OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average current harmonic distortion for the phases in a circuit." ::= { seHdpmCircuitEntry 10 } seHdpmCircuitTotalWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The total accumulated Reak Energy (watt hours, Ph) for the phases in a circuit. In units of watt hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 watt hours)." ::= { seHdpmCircuitEntry 11 } seHdpmCircuitAveAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average current for the phases in a circuit. In units of milliamps." ::= { seHdpmCircuitEntry 12 } seHdpmCircuitAveVLLRMS OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Average Line to Line Voltage for the phases in a circuit. In tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmCircuitEntry 13 } seHdpmCircuitSumWattMax OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum sum of watts for the phases in a circuit." ::= { seHdpmCircuitEntry 14 } seHdpmCircuitSumWattMaxTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "Time of the Maximum sum of watts for the phases in a circuit." ::= { seHdpmCircuitEntry 15 } seHdpmCircuitCurrentImbalance OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current Imbalance = (In - Iave) / Iave, where In is the phase with the largest difference from the average of the phase currents Iave." ::= { seHdpmCircuitEntry 16 } SeHdpmCircuitPhaseEntry ::= SEQUENCE { seHdpmCircuitPhaseIndex CircuitSummaryPhaseIndex, seHdpmCircuitPhaseCircuitNumber Integer32, seHdpmCircuitPhaseNumber INTEGER, seHdpmCircuitPhaseVoltsRms Integer32, seHdpmCircuitPhaseAmpsRms Integer32, seHdpmCircuitPhasePF Integer32, seHdpmCircuitPhaseWatt Integer32, seHdpmCircuitPhaseVAR Integer32, seHdpmCircuitPhaseVA Integer32, seHdpmCircuitPhaseTHDi Integer32, seHdpmCircuitPhaseWh Integer32, seHdpmCircuitPhaseVLLRMS Integer32, seHdpmCircuitPhaseWattMax Integer32, seHdpmCircuitPhaseWattMaxTime DateAndTime } seHdpmCircuitPhaseIndex OBJECT-TYPE SYNTAX CircuitSummaryPhaseIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the phase. This is a number in the range of 1..4. A value of 4 is the neutral phase." ::= { seHdpmCircuitPhaseEntry 1 } seHdpmCircuitPhaseCircuitNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The unique group number assigned to the circuits forming the group." ::= { seHdpmCircuitPhaseEntry 2 } seHdpmCircuitPhaseNumber OBJECT-TYPE SYNTAX INTEGER { notConnected(0), phase1(1), phase2(2), phase3(3), neutral(4), phase12(12), phase23(23), phase31(31) } MAX-ACCESS read-only STATUS current DESCRIPTION "The phase this circuit is connected to. Possible values are: 0..4 where a value of 0 indicates that the circuit is not connected." ::= { seHdpmCircuitPhaseEntry 3 } seHdpmCircuitPhaseVoltsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Line to Neutral RMS Volts for the voltage phase associated with a channel. In units of tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts)." ::= { seHdpmCircuitPhaseEntry 4 } seHdpmCircuitPhaseAmpsRms OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "RMS current for a channel in units of milliamps." ::= { seHdpmCircuitPhaseEntry 5 } seHdpmCircuitPhasePF OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Power Factor for a channel (power factor * 1000)." ::= { seHdpmCircuitPhaseEntry 6 } seHdpmCircuitPhaseWatt OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Watts for a channel." ::= { seHdpmCircuitPhaseEntry 7 } seHdpmCircuitPhaseVAR OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Reactive Power (Q) in VAR for a channel." ::= { seHdpmCircuitPhaseEntry 8 } seHdpmCircuitPhaseVA OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Apparent Power (S) in VA for a channel." ::= { seHdpmCircuitPhaseEntry 9 } seHdpmCircuitPhaseTHDi OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current Total Harmonic Distortion (THDi)." ::= { seHdpmCircuitPhaseEntry 10 } seHdpmCircuitPhaseWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The accumulated Real Energy (watt hours, Ph) in units of watt hours divided by the value of seHdpmSystemEnergyScale (ie. when EnergyScale=10, this counter is in units of 10 watt hours)." ::= { seHdpmCircuitPhaseEntry 11 } seHdpmCircuitPhaseVLLRMS OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "RMS Line to Line Volts in tenths of a volt divided by the value of seHdpmSystemVoltsScale (ie. when VoltsScale=100, this counter is in units of 10 volts). Phases are V12, V23, V31" ::= { seHdpmCircuitPhaseEntry 12 } seHdpmCircuitPhaseWattMax OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum watt sample seen." ::= { seHdpmCircuitPhaseEntry 13 } seHdpmCircuitPhaseWattMaxTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "Time of maximum watt sample seen." ::= { seHdpmCircuitPhaseEntry 14 } -- -- Demand data -- seHdpmDemandInterval OBJECT-TYPE SYNTAX Integer32 UNITS "minutes" MAX-ACCESS read-only STATUS current DESCRIPTION "The demand block interval" ::= { seHdpmDemand 1 } seHdpmDemandSubinterval OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The demand subinterval" ::= { seHdpmDemand 2 } seHdpmDemandLastInterval OBJECT-TYPE SYNTAX Integer32 UNITS "minutes" MAX-ACCESS read-only STATUS current DESCRIPTION "The demand block interval used with the last demand reading" ::= { seHdpmDemand 3 } seHdpmDemandLastSubinterval OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The demand subinterval used with the last demand reading" ::= { seHdpmDemand 4 } seHdpmDemandLastTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "The date and time of the last demand reading" ::= { seHdpmDemand 5 } seHdpmDemandACMetersPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmDemandACMetersPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of Demand for individual phases of AC Meters in the system. The first three entries are the Head Unit PQM" ::= { seHdpmDemand 6 } seHdpmDemandACMetersPhaseEntry OBJECT-TYPE SYNTAX SeHdpmDemandACMetersPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Demand for a individual phase of an AC Meters in the system. The first three entries are the Head Unit PQM" INDEX { seHdpmDemandACMeterPhaseIndex } ::= { seHdpmDemandACMetersPhaseTable 1 } seHdpmDemandACMetersTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmDemandACMetersEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Demand for 3 phase AC Meters in the system. The first entry is the Head Unit PQM total demand." ::= { seHdpmDemand 7 } seHdpmDemandACMetersEntry OBJECT-TYPE SYNTAX SeHdpmDemandACMetersEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Demand for the 3 phase AC Meters in the system. The first entry is the Head Unit PQM" INDEX { seHdpmDemandACMeterIndex } ::= { seHdpmDemandACMetersTable 1 } seHdpmDemandACMetersPhasePeakTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmDemandACMetersPhasePeakEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of Timestamped Peak demand for individual AC meters phases. The first group of three entries are the Head Unit PQM phases 1, 2 and 3." ::= { seHdpmDemand 8 } seHdpmDemandACMetersPhasePeakEntry OBJECT-TYPE SYNTAX SeHdpmDemandACMetersPhasePeakEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry of Timestamped Peak demand for an individual AC meters phase. The first group of three phases is the Head Unit PQM phases 1, 2 and 3." INDEX { seHdpmDemandACMeterPhasePeakIndex } ::= { seHdpmDemandACMetersPhasePeakTable 1 } seHdpmDemandACMetersPeakTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmDemandACMetersPeakEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of Timestamped Peak demand for 3 phase AC meters. The first meter is the Head Unit PQM" ::= { seHdpmDemand 9 } seHdpmDemandACMetersPeakEntry OBJECT-TYPE SYNTAX SeHdpmDemandACMetersPeakEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry of Timestamped Peak demand for 3 phase AC meters. The first meter is the Head Unit PQM" INDEX { seHdpmDemandACMeterPeakIndex } ::= { seHdpmDemandACMetersPeakTable 1 } seHdpmDemandCircuitTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmDemandCircuitEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of Demands for Circuits in the system. Each Circuit is composed of one or more Branch Circuits (Module Channels)." ::= { seHdpmDemand 10 } seHdpmDemandCircuitEntry OBJECT-TYPE SYNTAX SeHdpmDemandCircuitEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry of Demands for a Circuit in the system. Each Circuit is composed of one or more Branch Circuits (Module Channels)." INDEX { seHdpmDemandCircuitIndex } ::= { seHdpmDemandCircuitTable 1 } SeHdpmDemandACMetersPhaseEntry ::= SEQUENCE { seHdpmDemandACMeterPhaseIndex DemandIndex, seHdpmDemandACMeterPhaseRealPowerAvg Integer32, seHdpmDemandACMeterPhaseRealPowerMin Integer32, seHdpmDemandACMeterPhaseRealPowerMax Integer32, seHdpmDemandACMeterPhaseApparentPowerAvg Integer32, seHdpmDemandACMeterPhaseApparentPowerMin Integer32, seHdpmDemandACMeterPhaseApparentPowerMax Integer32, seHdpmDemandACMeterPhaseReactivePowerAvg Integer32, seHdpmDemandACMeterPhaseReactivePowerMin Integer32, seHdpmDemandACMeterPhaseReactivePowerMax Integer32, seHdpmDemandACMeterPhaseCurrentAvg Integer32, seHdpmDemandACMeterPhaseCurrentMin Integer32, seHdpmDemandACMeterPhaseCurrentMax Integer32, seHdpmDemandACMeterPhaseVLNMin Integer32, seHdpmDemandACMeterPhaseVLNMax Integer32, seHdpmDemandACMeterPhaseVLNAvg Integer32, seHdpmDemandACMeterPhaseVLLMin Integer32, seHdpmDemandACMeterPhaseVLLMax Integer32, seHdpmDemandACMeterPhaseVLLAvg Integer32 } seHdpmDemandACMeterPhaseIndex OBJECT-TYPE SYNTAX DemandIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for each entry. This is a number in the range of 1..N where N is the total number of entries. Each subsequent entry will be assigned the next index value." ::= { seHdpmDemandACMetersPhaseEntry 1 } seHdpmDemandACMeterPhaseRealPowerAvg OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The average Real Power (P) in Watts on a channel" ::= { seHdpmDemandACMetersPhaseEntry 2 } seHdpmDemandACMeterPhaseRealPowerMin OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The minimum Real Power (P) in Watts for a channel" ::= { seHdpmDemandACMetersPhaseEntry 3 } seHdpmDemandACMeterPhaseRealPowerMax OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum Real Power (P) in Watts for a channel" ::= { seHdpmDemandACMetersPhaseEntry 4 } seHdpmDemandACMeterPhaseApparentPowerAvg OBJECT-TYPE SYNTAX Integer32 UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "The average Apparent Power (S) in VAs for a channel" ::= { seHdpmDemandACMetersPhaseEntry 5 } seHdpmDemandACMeterPhaseApparentPowerMin OBJECT-TYPE SYNTAX Integer32 UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "The minimum Apparent Power (S) in VAs for a channel" ::= { seHdpmDemandACMetersPhaseEntry 6 } seHdpmDemandACMeterPhaseApparentPowerMax OBJECT-TYPE SYNTAX Integer32 UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum Apparent Power (S) in VAs for a channel" ::= { seHdpmDemandACMetersPhaseEntry 7 } seHdpmDemandACMeterPhaseReactivePowerAvg OBJECT-TYPE SYNTAX Integer32 UNITS "VAR" MAX-ACCESS read-only STATUS current DESCRIPTION "The average Reactive Power (Q) in VAR for a channel" ::= { seHdpmDemandACMetersPhaseEntry 8 } seHdpmDemandACMeterPhaseReactivePowerMin OBJECT-TYPE SYNTAX Integer32 UNITS "VAR" MAX-ACCESS read-only STATUS current DESCRIPTION "The minimum Reactive Power (Q) in VAR for a channel" ::= { seHdpmDemandACMetersPhaseEntry 9 } seHdpmDemandACMeterPhaseReactivePowerMax OBJECT-TYPE SYNTAX Integer32 UNITS "VAR" MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum Reactive Power (Q) in VAR for a channel" ::= { seHdpmDemandACMetersPhaseEntry 10 } seHdpmDemandACMeterPhaseCurrentAvg OBJECT-TYPE SYNTAX Integer32 UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "The average current" ::= { seHdpmDemandACMetersPhaseEntry 11 } seHdpmDemandACMeterPhaseCurrentMin OBJECT-TYPE SYNTAX Integer32 UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "The minimum current" ::= { seHdpmDemandACMetersPhaseEntry 12 } seHdpmDemandACMeterPhaseCurrentMax OBJECT-TYPE SYNTAX Integer32 UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum current" ::= { seHdpmDemandACMetersPhaseEntry 13 } seHdpmDemandACMeterPhaseVLNMin OBJECT-TYPE SYNTAX Integer32 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "The minimum Line to Neutral Voltage" ::= { seHdpmDemandACMetersPhaseEntry 14 } seHdpmDemandACMeterPhaseVLNMax OBJECT-TYPE SYNTAX Integer32 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum Line to Neutral Voltage" ::= { seHdpmDemandACMetersPhaseEntry 15 } seHdpmDemandACMeterPhaseVLNAvg OBJECT-TYPE SYNTAX Integer32 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "The average Line to Neutral Voltage" ::= { seHdpmDemandACMetersPhaseEntry 16 } seHdpmDemandACMeterPhaseVLLMin OBJECT-TYPE SYNTAX Integer32 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "The minimum Line to Line Voltage" ::= { seHdpmDemandACMetersPhaseEntry 17 } seHdpmDemandACMeterPhaseVLLMax OBJECT-TYPE SYNTAX Integer32 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum Line to Line Voltage" ::= { seHdpmDemandACMetersPhaseEntry 18 } seHdpmDemandACMeterPhaseVLLAvg OBJECT-TYPE SYNTAX Integer32 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "The average Line to Line Voltage" ::= { seHdpmDemandACMetersPhaseEntry 19 } SeHdpmDemandACMetersEntry ::= SEQUENCE { seHdpmDemandACMeterIndex DemandIndex, seHdpmDemandACMeterRealPowerAvg Integer32, seHdpmDemandACMeterRealPowerMin Integer32, seHdpmDemandACMeterRealPowerMax Integer32, seHdpmDemandACMeterApparentPowerAvg Integer32, seHdpmDemandACMeterApparentPowerMin Integer32, seHdpmDemandACMeterApparentPowerMax Integer32, seHdpmDemandACMeterReactivePowerAvg Integer32, seHdpmDemandACMeterReactivePowerMin Integer32, seHdpmDemandACMeterReactivePowerMax Integer32, seHdpmDemandACMeterCurrentAvg Integer32, seHdpmDemandACMeterCurrentMin Integer32, seHdpmDemandACMeterCurrentMax Integer32 } seHdpmDemandACMeterIndex OBJECT-TYPE SYNTAX DemandIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for each entry. This is a number in the range of 1..N where N is the total number of entries. Each subsequent entry will be assigned the next index value." ::= { seHdpmDemandACMetersEntry 1 } seHdpmDemandACMeterRealPowerAvg OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The total average Real Power (P) in Watts" ::= { seHdpmDemandACMetersEntry 2 } seHdpmDemandACMeterRealPowerMin OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The total minimum Real Power (P) in Watts" ::= { seHdpmDemandACMetersEntry 3 } seHdpmDemandACMeterRealPowerMax OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The total maximum Real Power (P) in Watts" ::= { seHdpmDemandACMetersEntry 4 } seHdpmDemandACMeterApparentPowerAvg OBJECT-TYPE SYNTAX Integer32 UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "The total average Apparent Power (S) in VAs" ::= { seHdpmDemandACMetersEntry 5 } seHdpmDemandACMeterApparentPowerMin OBJECT-TYPE SYNTAX Integer32 UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "The total minimum Apparent Power (S) in VAs" ::= { seHdpmDemandACMetersEntry 6 } seHdpmDemandACMeterApparentPowerMax OBJECT-TYPE SYNTAX Integer32 UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "The total maximum Apparent Power (S) in VAs" ::= { seHdpmDemandACMetersEntry 7 } seHdpmDemandACMeterReactivePowerAvg OBJECT-TYPE SYNTAX Integer32 UNITS "VAR" MAX-ACCESS read-only STATUS current DESCRIPTION "The average Reactive Power (Q) in VAR" ::= { seHdpmDemandACMetersEntry 8 } seHdpmDemandACMeterReactivePowerMin OBJECT-TYPE SYNTAX Integer32 UNITS "VAR" MAX-ACCESS read-only STATUS current DESCRIPTION "The minimum Reactive Power (Q) in VAR" ::= { seHdpmDemandACMetersEntry 9 } seHdpmDemandACMeterReactivePowerMax OBJECT-TYPE SYNTAX Integer32 UNITS "VAR" MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum Reactive Power (Q) in VAR" ::= { seHdpmDemandACMetersEntry 10 } seHdpmDemandACMeterCurrentAvg OBJECT-TYPE SYNTAX Integer32 UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "The average current" ::= { seHdpmDemandACMetersEntry 11 } seHdpmDemandACMeterCurrentMin OBJECT-TYPE SYNTAX Integer32 UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "The minimum current" ::= { seHdpmDemandACMetersEntry 12 } seHdpmDemandACMeterCurrentMax OBJECT-TYPE SYNTAX Integer32 UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum current" ::= { seHdpmDemandACMetersEntry 13 } SeHdpmDemandACMetersPhasePeakEntry ::= SEQUENCE { seHdpmDemandACMeterPhasePeakIndex DemandIndex, seHdpmDemandACMeterPhasePeakTime DateAndTime, seHdpmDemandACMeterPhasePeakPower Integer32, seHdpmDemandACMeterPhasePeakDailyTime DateAndTime, seHdpmDemandACMeterPhasePeakDailyPower Integer32 } seHdpmDemandACMeterPhasePeakIndex OBJECT-TYPE SYNTAX DemandIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for each entry. This is a number in the range of 1..N where N is the total number of phases. Each subsequent entry will be assigned the next index value." ::= { seHdpmDemandACMetersPhasePeakEntry 1 } seHdpmDemandACMeterPhasePeakTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "The date and time of the peak power" ::= { seHdpmDemandACMetersPhasePeakEntry 2 } seHdpmDemandACMeterPhasePeakPower OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The peak Real Power (P) in Watts" ::= { seHdpmDemandACMetersPhasePeakEntry 3 } seHdpmDemandACMeterPhasePeakDailyTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "The date and time of the daily peak Real Power" ::= { seHdpmDemandACMetersPhasePeakEntry 4 } seHdpmDemandACMeterPhasePeakDailyPower OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily peak real power (P) in watts" ::= { seHdpmDemandACMetersPhasePeakEntry 5 } SeHdpmDemandACMetersPeakEntry ::= SEQUENCE { seHdpmDemandACMeterPeakIndex DemandIndex, seHdpmDemandACMeterPeakTime DateAndTime, seHdpmDemandACMeterPeakPower Integer32, seHdpmDemandACMeterPeakDailyTime DateAndTime, seHdpmDemandACMeterPeakDailyPower Integer32 } seHdpmDemandACMeterPeakIndex OBJECT-TYPE SYNTAX DemandIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for each entry. This is a number in the range of 1..N where N is the total number of supplies. Each subsequent entry will be assigned the next index value." ::= { seHdpmDemandACMetersPeakEntry 1 } seHdpmDemandACMeterPeakTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "The date and time of the peak Real Power" ::= { seHdpmDemandACMetersPeakEntry 2 } seHdpmDemandACMeterPeakPower OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The peak power" ::= { seHdpmDemandACMetersPeakEntry 3 } seHdpmDemandACMeterPeakDailyTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "The date and time of the daily peak power" ::= { seHdpmDemandACMetersPeakEntry 4 } seHdpmDemandACMeterPeakDailyPower OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily peak Real Power" ::= { seHdpmDemandACMetersPeakEntry 5 } SeHdpmDemandCircuitEntry ::= SEQUENCE { seHdpmDemandCircuitIndex DemandIndex, seHdpmDemandCircuitPower Integer32, seHdpmDemandCircuitPeakTime DateAndTime, seHdpmDemandCircuitPeakPower Integer32, seHdpmDemandCircuitPeakDailyTime DateAndTime, seHdpmDemandCircuitPeakDailyPower Integer32 } seHdpmDemandCircuitIndex OBJECT-TYPE SYNTAX DemandIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for each entry. This is a number in the range of 1..N where N is the total number of circuits. Each subsequent entry will be assigned the next index value." ::= { seHdpmDemandCircuitEntry 1 } seHdpmDemandCircuitPower OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The average Real Power" ::= { seHdpmDemandCircuitEntry 2 } seHdpmDemandCircuitPeakTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "The date and time of the peak Real Power" ::= { seHdpmDemandCircuitEntry 3 } seHdpmDemandCircuitPeakPower OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The peak Real Power" ::= { seHdpmDemandCircuitEntry 4 } seHdpmDemandCircuitPeakDailyTime OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-only STATUS current DESCRIPTION "The date and time of the daily peak power" ::= { seHdpmDemandCircuitEntry 5 } seHdpmDemandCircuitPeakDailyPower OBJECT-TYPE SYNTAX Integer32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily peak Real Power" ::= { seHdpmDemandCircuitEntry 6 } -- -- Dry Input sources -- seHdpmDryInputsNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of dry input modules in the system. This is a number in the range of 1..N." ::= { seHdpmDryInputs 1 } seHdpmDryInputsTable OBJECT-TYPE SYNTAX SEQUENCE OF SeHdpmDryInputsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of dry input modules in the system." ::= { seHdpmDryInputs 2 } seHdpmDryInputsEntry OBJECT-TYPE SYNTAX SeHdpmDryInputsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information about a single dry input module in the system." INDEX { seHdpmDryInputsIndex } ::= { seHdpmDryInputsTable 1 } SeHdpmDryInputsEntry ::= SEQUENCE { seHdpmDryInputsIndex DryInputsIndex, seHdpmDryInputBitMap Integer32 } seHdpmDryInputsIndex OBJECT-TYPE SYNTAX DryInputsIndex MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique number for the dry input module. This is a number in the range of 1..N. Each subsequent source will be assigned the next index value." ::= { seHdpmDryInputsEntry 1 } seHdpmDryInputBitMap OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Bitfield of dry contact module's digital inputs." ::= { seHdpmDryInputsEntry 2 } END