inletPoleVoltage OBJECT-TYPE
SYNTAX MilliVolts
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of the line-line voltage reported in MilliVolts.
inletPoleIndex = 1; Single Phase Input Line Voltage
3-phase, L1-L2 Voltage or L1-N voltage
inletPoleIndex = 2; 3-phase L2-L3 Voltage or L2-N voltage
inletPoleaIndex = 3; 3-phase L3-L1 Voltage or L3-N voltage"
View at oid-info.com
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.13742.4.1.21.2.1.1 | inletPoleIndex | 0 | 0 | inletPoleIndex OBJECT-TYPE SYNTAX Integer32(1..256) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for ea… |
1.3.6.1.4.1.13742.4.1.21.2.1.2 | inletPoleLabel | 0 | 0 | inletPoleLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "A string identifying the Line … |
1.3.6.1.4.1.13742.4.1.21.2.1.3 | inletPoleCurrent | 0 | 0 | inletPoleCurrent OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "The value of the line current re… |
1.3.6.1.4.1.13742.4.1.21.2.1.5 | inletPoleMaxCurrent | 0 | 0 | inletPoleMaxCurrent OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the max. c… |
1.3.6.1.4.1.13742.4.1.21.2.1.7 | inletPoleActivePower | 0 | 0 | inletPoleActivePower OBJECT-TYPE SYNTAX Watts MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the active po… |
1.3.6.1.4.1.13742.4.1.21.2.1.8 | inletPoleApparentPower | 0 | 0 | inletPoleApparentPower OBJECT-TYPE SYNTAX VoltAmps MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the appa… |
1.3.6.1.4.1.13742.4.1.21.2.1.9 | inletPolePowerFactor | 0 | 0 | inletPolePowerFactor OBJECT-TYPE SYNTAX PowerFactorPercentage MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value f… |
1.3.6.1.4.1.13742.4.1.21.2.1.11 | inletPoleActiveEnergy | 0 | 0 | inletPoleActiveEnergy OBJECT-TYPE SYNTAX WattHours MAX-ACCESS read-only STATUS current DESCRIPTION "The value of the cumulative… |