envMonADCEvent NOTIFICATION-TYPE
OBJECTS {
systemLocation,
envMonID,
envMonADCName,
envMonADCStatus,
envMonADCCount,
envMonADCLowThresh,
envMonADCHighthresh
}
STATUS current
DESCRIPTION
"Environmental monitor analog-to-digital converter event.
If enabled, this trap is sent when the envMonADCStatus
indicates an error state (\countLow\ or \countHigh\). This
trap is repeated periodically while the envMonADCStatus
remains in an error state. If the envMonADCStatus returns
to a non-error state (\normal\), this trap is sent once more
with the non-error envMonADCStatus, and then stops being
repeated."
--#TYPE "Sentry: ADC Event."
--#SUMMARY "Status of ADC \%s\ (%s) is \%d\."
--#ARGUMENTS { 2, 1, 3 }
--#SEVERITY CRITICAL
--#GENERIC 6
--#CATEGORY "Error Events"
--#SOURCE_ID "A"
--#TIMEINDEX 255
--#HELP ""
--#HELPTAG 0
--#STATE UNKNOWN
View at oid-info.com
Environmental monitor analog-to-digital converter event.
If enabled, this trap is sent when the envMonADCStatus
indicates an error state ('countLow' or 'countHigh'). This
trap is repeated periodically while the envMonADCStatus
remains in an error state. If the envMonADCStatus returns
to a non-error state ('normal'), this trap is sent once more
with the non-error envMonADCStatus, and then stops being
repeated.
Parsed from file Sentry3_SMIv1.mib.txt
Company: None
Module: Sentry3-MIB
Environmental monitor analog-to-digital converter event.
If enabled, this trap is sent when the envMonADCStatus
indicates an error state ('countLow' or 'countHigh'). This
trap is repeated periodically while the envMonADCStatus
remains in an error state. If the envMonADCStatus returns
to a non-error state ('normal'), this trap is sent once more
with the non-error envMonADCStatus, and then stops being
repeated.
Parsed from file Sentry3-MIB.mib
Module: Sentry3-MIB
envMonADCEvent NOTIFICATION-TYPE OBJECTS { systemLocation, envMonID, envMonADCName, envMonADCStatus, envMonADCCount, envMonADCLowThresh, envMonADCHighThresh } STATUS current DESCRIPTION "Environmental monitor analog-to-digital converter event. If enabled, this trap is sent when the envMonADCStatus indicates an error state ('countLow' or 'countHigh'). This trap is repeated periodically while the envMonADCStatus remains in an error state. If the envMonADCStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonADCStatus, and then stops being repeated." ::= { events 9 }
envMonADCEvent NOTIFICATION-TYPE OBJECTS { systemLocation, envMonID, envMonADCName, envMonADCStatus, envMonADCCount, envMonADCLowThresh, envMonADCHighThresh } STATUS current DESCRIPTION "Environmental monitor analog-to-digital converter event. If enabled, this trap is sent when the envMonADCStatus indicates an error state ('countLow' or 'countHigh'). This trap is repeated periodically while the envMonADCStatus remains in an error state. If the envMonADCStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonADCStatus, and then stops being repeated." ::= { events 9 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.1718.3.100.0.1 | towerStatusEvent | 0 | 0 | Tower status event. If enabled, this trap is sent when the towerStatus indicates an error state ('noComm', 'fanFail', or 'overTe… |
1.3.6.1.4.1.1718.3.100.0.2 | infeedStatusEvent | 0 | 0 | Input feed status event. If enabled, this trap is sent when the infeedStatus indicates an error state ('offError', 'onError', or… |
1.3.6.1.4.1.1718.3.100.0.3 | infeedLoadEvent | 0 | 0 | Input feed load event. If enabled, this trap is sent when the infeedLoadStatus indicates an error state ('loadLow', 'loadHigh', … |
1.3.6.1.4.1.1718.3.100.0.4 | outletStatusEvent | 0 | 0 | Outlet status event. If enabled, this trap is sent when the outletStatus indicates an error state ('offError', 'onError', 'noCom… |
1.3.6.1.4.1.1718.3.100.0.5 | outletLoadEvent | 0 | 0 | Outlet load event. If enabled, this trap is sent when the outletLoadStatus indicates an error state ('loadLow', 'loadHigh', 'ove… |
1.3.6.1.4.1.1718.3.100.0.6 | outletChangeEvent | 0 | 0 | Outlet on/off change event. If enabled, this trap is sent when the outletStatus changes from any 'on' state ('on', 'onWait', 'on… |
1.3.6.1.4.1.1718.3.100.0.7 | envMonStatusEvent | 0 | 0 | Environmental monitor status event. If enabled, this trap is sent when the envMonStatus indicates an error state ('noComm'). Th… |
1.3.6.1.4.1.1718.3.100.0.8 | envMonWaterSensorEvent | 0 | 0 | Environmental monitor water sensor event. If enabled, this trap is sent when the envMonWaterSensorStatus indicates an error stat… |
1.3.6.1.4.1.1718.3.100.0.10 | tempHumidSensorStatusEvent | 0 | 0 | Temperature/humidity sensor status event. If enabled, this trap is sent when the tempHumidSensorStatus indicates an error state … |
1.3.6.1.4.1.1718.3.100.0.11 | tempHumidSensorTempEvent | 0 | 0 | Temperature/humidity sensor temperature event. If enabled, this trap is sent when the tempHumidSensorTempStatus indicates an err… |
1.3.6.1.4.1.1718.3.100.0.12 | tempHumidSensorHumidEvent | 0 | 0 | Temperature/humidity sensor humidity event. If enabled, this trap is sent when the tempHumidSensorHumidStatus indicates an error… |
1.3.6.1.4.1.1718.3.100.0.13 | contactClosureEvent | 0 | 0 | Contact closure event. If enabled, this trap is sent when the contactClosureStatus indicates an error state ('alarm'). This trap… |
1.3.6.1.4.1.1718.3.100.0.14 | branchStatusEvent | 0 | 0 | branchStatusEvent NOTIFICATION-TYPE OBJECTS { systemLocation, branchID, branchName, branchStatus } STATUS current DESCRIPTION "… |
1.3.6.1.4.1.1718.3.100.0.15 | branchLoadEvent | 0 | 0 | branchLoadEvent NOTIFICATION-TYPE OBJECTS { systemLocation, branchID, branchName, branchLoadStatus, branchLoadValue, branchLoad… |