acFrequencyFault NOTIFICATION-TYPE
OBJECTS { acFrequency }
STATUS current
DESCRIPTION "This alarm occurs if the Frequency of the Input AC Voltage to the Rack Power System is outside the Frequency High or Low Alarm setup specified using the Expansion 1 AC1ph or Expansion 2 AC3ph"
View at oid-info.com
Automatically extracted from a module checked by a user of the Asnp syntax-checking tool
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.20749.1.1.3.1 | acVoltageFault | 0 | 0 | acVoltageFault NOTIFICATION-TYPE OBJECTS { acVoltage } STATUS current DESCRIPTION "This alarm occurs if the Input AC Voltage to… |
1.3.6.1.4.1.20749.1.1.3.3 | batteryCellVoltageUpperDeviation | 0 | 0 | batteryCellVoltageUpperDeviation NOTIFICATION-TYPE OBJECTS { batteryCellVoltage } STATUS current DESCRIPTION "This alarm occurs… |
1.3.6.1.4.1.20749.1.1.3.4 | batteryCellLowerDeviation | 0 | 0 | batteryCellLowerDeviation NOTIFICATION-TYPE OBJECTS { batteryCellVoltage } STATUS current DESCRIPTION "This alarm occurs when a… |
1.3.6.1.4.1.20749.1.1.3.5 | batteryCellVoltageHigh | 0 | 0 | batteryCellVoltageHigh NOTIFICATION-TYPE OBJECTS { batteryCellVoltage } STATUS current DESCRIPTION "This alarm occurs when a Ba… |
1.3.6.1.4.1.20749.1.1.3.6 | batteryCellVoltageLow | 0 | 0 | batteryCellVoltageLow NOTIFICATION-TYPE STATUS current DESCRIPTION "This alarm occurs when a Battery Cell Voltage is lower the … |
1.3.6.1.4.1.20749.1.1.3.7 | batteryChargeCurrentLimit | 0 | 0 | batteryChargeCurrentLimit NOTIFICATION-TYPE OBJECTS { chargeCurren } STATUS current DESCRIPTION "This alarm occurs when a Batte… |
1.3.6.1.4.1.20749.1.1.3.8 | batteryCircuitBreakerOrSwitchOpen | 0 | 0 | batteryCircuitBreakerOrSwitchOpen NOTIFICATION-TYPE OBJECTS { batteryCellVoltage } STATUS current DESCRIPTION "This alarm occur… |
1.3.6.1.4.1.20749.1.1.3.9 | batteryDischarging | 0 | 0 | batteryDischarging NOTIFICATION-TYPE OBJECTS { batteryCellVoltage } STATUS current DESCRIPTION "The Batt Discharge Alarm (V) pa… |
1.3.6.1.4.1.20749.1.1.3.10 | batteryDischargeLowVoltage | 0 | 0 | batteryDischargeLowVoltage NOTIFICATION-TYPE OBJECTS { batteryCellVoltage } STATUS current DESCRIPTION "This alarm occurs if th… |
1.3.6.1.4.1.20749.1.1.3.11 | batteryDischargeLowVoltageWarning | 0 | 0 | batteryDischargeLowVoltageWarning NOTIFICATION-TYPE OBJECTS { chargeCurren } STATUS current DESCRIPTION "This alarm occurs if t… |
1.3.6.1.4.1.20749.1.1.3.12 | batteryDischargeCurrentSymmetry | 0 | 0 | batteryDischargeCurrentSymmetry NOTIFICATION-TYPE OBJECTS { batteryDischargeCurrent } STATUS current DESCRIPTION "This alarm oc… |
1.3.6.1.4.1.20749.1.1.3.13 | batteryDischargeTestFailed | 0 | 0 | batteryDischargeTestFailed NOTIFICATION-TYPE OBJECTS { batteryDischargeCurrent } STATUS current DESCRIPTION "This alarm occurs … |
1.3.6.1.4.1.20749.1.1.3.14 | batteryDischargeWhileACok | 0 | 0 | batteryDischargeWhileACok NOTIFICATION-TYPE OBJECTS { batteryDischargeCurrent, acVoltage, acFrequency } STATUS current DESCRIPT… |
1.3.6.1.4.1.20749.1.1.3.15 | batteryElectrolyteLevelLow | 0 | 0 | batteryElectrolyteLevelLow NOTIFICATION-TYPE OBJECTS { batteryElectrolyte } STATUS current DESCRIPTION "This alarm occurs on Ra… |
1.3.6.1.4.1.20749.1.1.3.16 | batteryHealthWarning | 0 | 0 | batteryHealthWarning NOTIFICATION-TYPE OBJECTS { batteryDischargeCurrent } STATUS current DESCRIPTION "This alarm occurs during… |
1.3.6.1.4.1.20749.1.1.3.17 | batteryTemperatureHigh | 0 | 0 | batteryTemperatureHigh NOTIFICATION-TYPE OBJECTS { batteryTemperature } STATUS current DESCRIPTION "This alarm occurs when the … |
1.3.6.1.4.1.20749.1.1.3.18 | batteryTemperatureSensorFail | 0 | 0 | batteryTemperatureSensorFail NOTIFICATION-TYPE OBJECTS { batteryTemperature } STATUS current DESCRIPTION "This alarm occurs on … |
1.3.6.1.4.1.20749.1.1.3.19 | cabinetTemperatureHigh | 0 | 0 | cabinetTemperatureHigh NOTIFICATION-TYPE OBJECTS { cabinetTemperature } STATUS current DESCRIPTION "This alarm occurs when the … |
1.3.6.1.4.1.20749.1.1.3.20 | csuParametersOutOfRangeOrEepromFault | 0 | 0 | csuParametersOutOfRangeOrEepromFault NOTIFICATION-TYPE OBJECTS { cabinetTemperature } STATUS current DESCRIPTION "This alarm oc… |
1.3.6.1.4.1.20749.1.1.3.21 | dcBusShortCircuit | 0 | 0 | dcBusShortCircuit NOTIFICATION-TYPE OBJECTS { dcBusStatus } STATUS current DESCRIPTION "This alarm occurs on a Rack Power Syste… |
1.3.6.1.4.1.20749.1.1.3.22 | dcConverterFault | 0 | 0 | dcConverterFault NOTIFICATION-TYPE OBJECTS { converterStatus } STATUS current DESCRIPTION "This alarm occurs on Rack Power Syst… |
1.3.6.1.4.1.20749.1.1.3.23 | earthLeakage | 0 | 0 | earthLeakage NOTIFICATION-TYPE OBJECTS { earthLeakageStatus } STATUS current DESCRIPTION "This alarm occurs on Rack Power Syste… |
1.3.6.1.4.1.20749.1.1.3.24 | lvdsSwitchOpen | 0 | 0 | lvdsSwitchOpen NOTIFICATION-TYPE OBJECTS { lvdsStatus } STATUS current DESCRIPTION "This alarm occurs on Rack Power Systems fit… |
1.3.6.1.4.1.20749.1.1.3.25 | pduFuseOrLoadCircuitBreakerTrip | 0 | 0 | pduFuseOrLoadCircuitBreakerTrip NOTIFICATION-TYPE OBJECTS { pduStatus } STATUS current DESCRIPTION "This notification occurs on… |
1.3.6.1.4.1.20749.1.1.3.26 | rectifierUrgent | 0 | 0 | rectifierUrgent NOTIFICATION-TYPE OBJECTS { rectifierStatus } STATUS current DESCRIPTION "This alarm occurs on a Rack Power Sys… |
1.3.6.1.4.1.20749.1.1.3.27 | rectifierCommunications | 0 | 0 | rectifierCommunications NOTIFICATION-TYPE OBJECTS { rectifierStatus } STATUS current DESCRIPTION "This alarm occurs on a Rack P… |
1.3.6.1.4.1.20749.1.1.3.28 | rectifierHighVoltageShutDown | 0 | 0 | rectifierHighVoltageShutDown NOTIFICATION-TYPE OBJECTS { rectifierStatus } STATUS current DESCRIPTION "This alarm occurs when a… |
1.3.6.1.4.1.20749.1.1.3.29 | rectifierNotCalibrated | 0 | 0 | rectifierNotCalibrated NOTIFICATION-TYPE OBJECTS { rectifierStatus } STATUS current DESCRIPTION "Alarm occurs when the rectifie… |
1.3.6.1.4.1.20749.1.1.3.30 | rectifierParameterOutOfRange | 0 | 0 | rectifierParameterOutOfRange NOTIFICATION-TYPE OBJECTS { rectifierStatus } STATUS current DESCRIPTION "This alarm occurs when a… |
1.3.6.1.4.1.20749.1.1.3.31 | rectifierWarning | 0 | 0 | rectifierWarning NOTIFICATION-TYPE OBJECTS { rectifierStatus } STATUS current DESCRIPTION "Notifies when the rectifier gives a … |
1.3.6.1.4.1.20749.1.1.3.32 | remoteCommunicationsFailure | 0 | 0 | remoteCommunicationsFailure NOTIFICATION-TYPE OBJECTS { commStatus } STATUS current DESCRIPTION "Alarm fires when the remote co… |
1.3.6.1.4.1.20749.1.1.3.33 | siteMonitor | 0 | 0 | siteMonitor NOTIFICATION-TYPE OBJECTS { siteStatus } STATUS current DESCRIPTION "This alarm occurs on a Rack Power System fitte… |
1.3.6.1.4.1.20749.1.1.3.34 | systemCurrentOverload | 0 | 0 | systemCurrentOverload NOTIFICATION-TYPE OBJECTS { systemCurrent } STATUS current DESCRIPTION "This alarm occurs on a Rack Power… |
1.3.6.1.4.1.20749.1.1.3.35 | systemVoltageHigh | 0 | 0 | systemVoltageHigh NOTIFICATION-TYPE OBJECTS { systemVoltage } STATUS current DESCRIPTION "This alarm occurs on a Rack Power Sys… |
1.3.6.1.4.1.20749.1.1.3.36 | systemVoltageLow | 0 | 0 | systemVoltageLow NOTIFICATION-TYPE OBJECTS { systemVoltage } STATUS current DESCRIPTION "This alarm occurs on a Rack Power Syst… |
1.3.6.1.4.1.20749.1.1.3.37 | cdtInProgress | 0 | 0 | cdtInProgress NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.38 | noDataReceived | 0 | 0 | noDataReceived NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.39 | noAlarms | 0 | 0 | noAlarms NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.40 | parametersChanged | 0 | 0 | parametersChanged NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.41 | smrIndividualAlarms | 0 | 0 | smrIndividualAlarms NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.42 | smrParametersChanged | 0 | 0 | smrParametersChanged NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.43 | failedEstablishingConnection | 0 | 0 | failedEstablishingConnection NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.44 | networkDeviceConnectionProblem | 0 | 0 | networkDeviceConnectionProblem NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.45 | csuConnectionProblem | 0 | 0 | csuConnectionProblem NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.46 | ambientTempHigh | 0 | 0 | ambientTempHigh NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.47 | heartbeat | 0 | 0 | heartbeat NOTIFICATION-TYPE STATUS current DESCRIPTION "Description" |
1.3.6.1.4.1.20749.1.1.3.48 | trapVarBinds | 13 | 13 | None |
1.3.6.1.4.1.20749.1.1.3.49 | genericTrap | 0 | 0 | genericTrap NOTIFICATION-TYPE STATUS current DESCRIPTION "If a new alarm comes from the ora db and we(OSS TECHNOLOGIES) haven i… |