cpqWcrmStatusSensorInternal OBJECT IDENTIFIER ::= { cpqWcrmStatus 3 }
Vendor: Compaq
Module: CPQWCRM-MIB
[Automatically extracted from oidview.com]
cpqWcrmStatusSensorInternal OBJECT IDENTIFIER ::= { cpqWcrmStatus 3 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.232.167.2.3.1 | cpqWcrmInternalTypeOfDevice | 0 | 0 | Type of sensor unit connected to port 1 |
1.3.6.1.4.1.232.167.2.3.2 | cpqWcrmInternalText | 0 | 0 | Descriptional text for sensor unit connected to port 1 |
1.3.6.1.4.1.232.167.2.3.3 | cpqWcrmInternalSerial | 0 | 0 | Serialnumber of sensor unit connected to port 1 |
1.3.6.1.4.1.232.167.2.3.4 | cpqWcrmInternalStatus | 0 | 0 | General Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed… |
1.3.6.1.4.1.232.167.2.3.5 | cpqWcrmStatusInternalSensors | 2 | 11 | None |
1.3.6.1.4.1.232.167.2.3.6 | cpqWcrmStatusInternalOutputs | 2 | 12 | None |
1.3.6.1.4.1.232.167.2.3.7 | cpqWcrmStatusInternalMsg | 2 | 13 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.232.167.2.1 | cpqWcrmStatusDeviceEnvironmentalController | 0 | 0 | General Status of Environmental Controller unit itself (1) failed (2) OK |
1.3.6.1.4.1.232.167.2.2 | cpqWcrmUnitsConnected | 0 | 0 | Number of sensor units connected to the Environmental Controller, Port 1 to 2 |
1.3.6.1.4.1.232.167.2.4 | cpqWcrmStatusSensorWaterCoolUnit | 7 | 43 | None |
1.3.6.1.4.1.232.167.2.7 | cpqWcrmURL | 0 | 0 | URL of the management interface in the format http[s]://ipaddr[:port#][/page] |