Seconds must be in a range to be an alarm
Parsed from file SL10-MIB.mib
Module: SL10-MIB
Vendor: Asentria Corporation
Module: S410-MIB
[Automatically extracted from oidview.com]
tempAlarmThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Seconds must be in a range to be an alarm" ::= { tempsensor 7 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3052.40.4.1 | tempValue | 0 | 0 | Current Temperature Value, in C or F based on 1.3.6.1.4.1.3052.40.4.10 |
1.3.6.1.4.1.3052.40.4.2 | tempAlarmEnable | 0 | 0 | 0=alarms disabled, 1=alarms enabled |
1.3.6.1.4.1.3052.40.4.3 | tempHighLevel | 0 | 0 | Level at which the High alarm goes active |
1.3.6.1.4.1.3052.40.4.4 | tempVeryHighLevel | 0 | 0 | Level at which the Very High alarm goes active |
1.3.6.1.4.1.3052.40.4.5 | tempLowLevel | 0 | 0 | Level at which the Low alarm goes active |
1.3.6.1.4.1.3052.40.4.6 | tempVeryLowLevel | 0 | 0 | Level at which the Very Low alarm goes active |
1.3.6.1.4.1.3052.40.4.8 | tempReturnNormalTrap | 0 | 0 | 0-not sent, 1-send trap on return to normal range |
1.3.6.1.4.1.3052.40.4.9 | tempTrapRepeat | 0 | 0 | 0-no repeats. 1-255 number of minutes between repeats of alarm traps. |
1.3.6.1.4.1.3052.40.4.10 | tempMode | 0 | 0 | 0=all temp readings and levels in degrees F, 1=in degrees C |
1.3.6.1.4.1.3052.40.4.11 | tempHighSeverity | 0 | 0 | High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning |
1.3.6.1.4.1.3052.40.4.12 | tempVeryHighSeverity | 0 | 0 | Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning |
1.3.6.1.4.1.3052.40.4.13 | tempLowSeverity | 0 | 0 | Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning |
1.3.6.1.4.1.3052.40.4.14 | tempVeryLowSeverity | 0 | 0 | Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning |
1.3.6.1.4.1.3052.40.4.15 | tempName | 0 | 0 | Name for temperature sensor, up to 30 characters |