Reference record for OID 1.3.6.1.4.1.318.1.1.1.11.1.1



parent
1.3.6.1.4.1.318.1.1.1.11.1 (upsBasicState)
node code
1
node name
upsBasicStateOutputState
dot oid
1.3.6.1.4.1.318.1.1.1.11.1.1
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsBasicState(1) upsBasicStateOutputState(1)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsBasicState(1) upsBasicStateOutputState(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsBasicState(1) upsBasicStateOutputState(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsBasicState(1) upsBasicStateOutputState(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsBasicState(1) upsBasicStateOutputState(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsBasicState(1) upsBasicStateOutputState(1)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsBasicState/upsBasicStateOutputState
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsBasicState/upsBasicStateOutputState
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsBasicState/upsBasicStateOutputState
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsBasicState/upsBasicStateOutputState
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsBasicState/upsBasicStateOutputState
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsBasicState/upsBasicStateOutputState
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/1/11/1/1

    Description by mibdepot

    An ASCII string containing the 64 flags representing
    the current state(s) of the UPS. If the Network Card
    is unable to determine the state of the UPS, this
    variable is set to 'UNKNOWN'.

    The flags are numbered 1 to 64, read from left to
    right. The flags are defined as follows:

    Flag 1: Abnormal Condition Present
    Flag 2: On Battery
    Flag 3: Low Battery
    Flag 4: On Line

    Flag 5: Replace Battery
    Flag 6: Serial Communication Established
    Flag 7: AVR Boost Active
    Flag 8: AVR Trim Active

    Flag 9: Overload
    Flag 10: Runtime Calibration
    Flag 11: Batteries Discharged
    Flag 12: Manual Bypass

    Flag 13: Software Bypass
    Flag 14: In Bypass due to Internal Fault
    Flag 15: In Bypass due to Supply Failure
    Flag 16: In Bypass due to Fan Failure

    Flag 17: Sleeping on a Timer
    Flag 18: Sleeping until Utility Power Returns
    Flag 19: On
    Flag 20: Rebooting

    Flag 21: Battery Communication Lost
    Flag 22: Graceful Shutdown Initiated
    Flag 23: Smart Boost or Smart Trim Fault
    Flag 24: Bad Output Voltage

    Flag 25: Battery Charger Failure
    Flag 26: High Battery Temperature
    Flag 27: Warning Battery Temperature
    Flag 28: Critical Battery Temperature

    Flag 29: Self Test In Progress
    Flag 30: Low Battery / On Battery
    Flag 31: Graceful Shutdown Issued by Upstream Device
    Flag 32: Graceful Shutdown Issued by Downstream Device

    Flag 33: No Batteries Attached
    Flag 34: Synchronized Command is in Progress
    Flag 35: Synchronized Sleeping Command is in Progress
    Flag 36: Synchronized Rebooting Command is in Progress

    Flag 37: Inverter DC Imbalance
    Flag 38: Transfer Relay Failure
    Flag 39: Shutdown or Unable to Transfer
    Flag 40: Low Battery Shutdown

    Flag 41: Electronic Unit Fan Failure
    Flag 42: Main Relay Failure
    Flag 43: Bypass Relay Failure
    Flag 44: Temporary Bypass

    Flag 45: High Internal Temperature
    Flag 46: Battery Temperature Sensor Fault
    Flag 47: Input Out of Range for Bypass
    Flag 48: DC Bus Overvoltage

    Flag 49: PFC Failure
    Flag 50: Critical Hardware Fault
    Flag 51: Green Mode/ECO Mode
    Flag 52: Hot Standby

    Flag 53: Emergency Power Off (EPO) Activated
    Flag 54: Load Alarm Violation
    Flag 55: Bypass Phase Fault
    Flag 56: UPS Internal Communication Failure

    Flag 57:
    Flag 58:
    Flag 59:
    Flag 60:

    Flag 61:
    Flag 62:
    Flag 63:
    Flag 64:

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    An ASCII string containing the 64 flags representing
    the current state(s) of the UPS. If the Network Card
    is unable to determine the state of the UPS, this
    variable is set to 'UNKNOWN'.

    The flags are numbered 1 to 64, read from left to
    right. The flags are defined as follows:

    Flag 1: Abnormal Condition Present
    Flag 2: On Battery
    Flag 3: Low Battery
    Flag 4: On Line

    Flag 5: Replace Battery
    Flag 6: Serial Communication Established
    Flag 7: AVR Boost Active
    Flag 8: AVR Trim Active

    Flag 9: Overload
    Flag 10: Runtime Calibration
    Flag 11: Batteries Discharged
    Flag 12: Manual Bypass

    Flag 13: Software Bypass
    Flag 14: In Bypass due to Internal Fault
    Flag 15: In Bypass due to Supply Failure
    Flag 16: In Bypass due to Fan Failure

    Flag 17: Sleeping on a Timer
    Flag 18: Sleeping until Utility Power Returns
    Flag 19: On
    Flag 20: Rebooting

    Flag 21: Battery Communication Lost
    Flag 22: Graceful Shutdown Initiated
    Flag 23: Smart Boost or Smart Trim Fault
    Flag 24: Bad Output Voltage

    Flag 25: Battery Charger Failure
    Flag 26: High Battery Temperature
    Flag 27: Warning Battery Temperature
    Flag 28: Critical Battery Temperature

    Flag 29: Self Test In Progress
    Flag 30: Low Battery / On Battery
    Flag 31: Graceful Shutdown Issued by Upstream Device
    Flag 32: Graceful Shutdown Issued by Downstream Device

    Flag 33: No Batteries Attached
    Flag 34: Synchronized Command is in Progress
    Flag 35: Synchronized Sleeping Command is in Progress
    Flag 36: Synchronized Rebooting Command is in Progress

    Flag 37: Inverter DC Imbalance
    Flag 38: Transfer Relay Failure
    Flag 39: Shutdown or Unable to Transfer
    Flag 40: Low Battery Shutdown

    Flag 41: Electronic Unit Fan Failure
    Flag 42: Main Relay Failure
    Flag 43: Bypass Relay Failure
    Flag 44: Temporary Bypass

    Flag 45: High Internal Temperature
    Flag 46: Battery Temperature Sensor Fault
    Flag 47: Input Out of Range for Bypass
    Flag 48: DC Bus Overvoltage

    Flag 49: PFC Failure
    Flag 50: Critical Hardware Fault
    Flag 51: Green Mode/ECO Mode
    Flag 52: Hot Standby

    Flag 53: Emergency Power Off (EPO) Activated
    Flag 54: Load Alarm Violation
    Flag 55: Bypass Phase Fault
    Flag 56: UPS Internal Communication Failure

    Flag 57:
    Flag 58:
    Flag 59:
    Flag 60:

    Flag 61:
    Flag 62:
    Flag 63:
    Flag 64:

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    upsBasicStateOutputState OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 64 flags representing the current state(s) of the UPS. If the Network Card is unable to determine the state of the UPS, this variable is set to 'UNKNOWN'. The flags are numbered 1 to 64, read from left to right. The flags are defined as follows: Flag 1: Abnormal Condition Present Flag 2: On Battery Flag 3: Low Battery Flag 4: On Line Flag 5: Replace Battery Flag 6: Serial Communication Established Flag 7: AVR Boost Active Flag 8: AVR Trim Active Flag 9: Overload Flag 10: Runtime Calibration Flag 11: Batteries Discharged Flag 12: Manual Bypass Flag 13: Software Bypass Flag 14: In Bypass due to Internal Fault Flag 15: In Bypass due to Supply Failure Flag 16: In Bypass due to Fan Failure Flag 17: Sleeping on a Timer Flag 18: Sleeping until Utility Power Returns Flag 19: On Flag 20: Rebooting Flag 21: Battery Communication Lost Flag 22: Graceful Shutdown Initiated Flag 23: Smart Boost or Smart Trim Fault Flag 24: Bad Output Voltage Flag 25: Battery Charger Failure Flag 26: High Battery Temperature Flag 27: Warning Battery Temperature Flag 28: Critical Battery Temperature Flag 29: Self Test In Progress Flag 30: Low Battery / On Battery Flag 31: Graceful Shutdown Issued by Upstream Device Flag 32: Graceful Shutdown Issued by Downstream Device Flag 33: No Batteries Attached Flag 34: Synchronized Command is in Progress Flag 35: Synchronized Sleeping Command is in Progress Flag 36: Synchronized Rebooting Command is in Progress Flag 37: Inverter DC Imbalance Flag 38: Transfer Relay Failure Flag 39: Shutdown or Unable to Transfer Flag 40: Low Battery Shutdown Flag 41: Electronic Unit Fan Failure Flag 42: Main Relay Failure Flag 43: Bypass Relay Failure Flag 44: Temporary Bypass Flag 45: High Internal Temperature Flag 46: Battery Temperature Sensor Fault Flag 47: Input Out of Range for Bypass Flag 48: DC Bus Overvoltage Flag 49: PFC Failure Flag 50: Critical Hardware Fault Flag 51: Green Mode/ECO Mode Flag 52: Hot Standby Flag 53: Emergency Power Off (EPO) Activated Flag 54: Load Alarm Violation Flag 55: Bypass Phase Fault Flag 56: UPS Internal Communication Failure Flag 57: Flag 58: Flag 59: Flag 60: Flag 61: Flag 62: Flag 63: Flag 64: " ::= { upsBasicState 1 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    upsBasicStateOutputState OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 64 flags representing the current state(s) of the UPS. If the Network Card is unable to determine the state of the UPS, this variable is set to 'UNKNOWN'. The flags are numbered 1 to 64, read from left to right. The flags are defined as follows: Flag 1: Abnormal Condition Present Flag 2: On Battery Flag 3: Low Battery Flag 4: On Line Flag 5: Replace Battery Flag 6: Serial Communication Established Flag 7: AVR Boost Active Flag 8: AVR Trim Active Flag 9: Overload Flag 10: Runtime Calibration Flag 11: Batteries Discharged Flag 12: Manual Bypass Flag 13: Software Bypass Flag 14: In Bypass due to Internal Fault Flag 15: In Bypass due to Supply Failure Flag 16: In Bypass due to Fan Failure Flag 17: Sleeping on a Timer Flag 18: Sleeping until Utility Power Returns Flag 19: On Flag 20: Rebooting Flag 21: Battery Communication Lost Flag 22: Graceful Shutdown Initiated Flag 23: Smart Boost or Smart Trim Fault Flag 24: Bad Output Voltage Flag 25: Battery Charger Failure Flag 26: High Battery Temperature Flag 27: Warning Battery Temperature Flag 28: Critical Battery Temperature Flag 29: Self Test In Progress Flag 30: Low Battery / On Battery Flag 31: Graceful Shutdown Issued by Upstream Device Flag 32: Graceful Shutdown Issued by Downstream Device Flag 33: No Batteries Attached Flag 34: Synchronized Command is in Progress Flag 35: Synchronized Sleeping Command is in Progress Flag 36: Synchronized Rebooting Command is in Progress Flag 37: Inverter DC Imbalance Flag 38: Transfer Relay Failure Flag 39: Shutdown or Unable to Transfer Flag 40: Low Battery Shutdown Flag 41: Electronic Unit Fan Failure Flag 42: Main Relay Failure Flag 43: Bypass Relay Failure Flag 44: Temporary Bypass Flag 45: High Internal Temperature Flag 46: Battery Temperature Sensor Fault Flag 47: Input Out of Range for Bypass Flag 48: DC Bus Overvoltage Flag 49: PFC Failure Flag 50: Critical Hardware Fault Flag 51: Green Mode/ECO Mode Flag 52: Hot Standby Flag 53: Emergency Power Off (EPO) Activated Flag 54: Load Alarm Violation Flag 55: Bypass Phase Fault Flag 56: UPS Internal Communication Failure Flag 57: Flag 58: Flag 59: Flag 60: Flag 61: Flag 62: Flag 63: Flag 64: " ::= { upsBasicState 1 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.11.1.1.0 upsBasicStateOutputState 0 0 None