The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1)
- highLineVoltage(2)
by an over voltage greater than the high transfer vloltage.
- brownout(3)
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4)
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5)
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6)
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7)
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8)
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9)
- rateOfVoltageChange(10)
the line voltage.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1)
- highLineVoltage(2)
by an over voltage greater than the high transfer voltage.
- brownout(3)
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4)
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5)
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6)
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7)
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8)
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9)
- rateOfVoltageChange(10)
the line voltage.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
upsAdvInputLineFailCause OBJECT-TYPE SYNTAX INTEGER { noTransfer(1), highLineVoltage(2), brownout(3), blackout(4), smallMomentarySag(5), deepMomentarySag(6), smallMomentarySpike(7), largeMomentarySpike(8), selfTest(9), rateOfVoltageChnage(10) } ACCESS read-only STATUS mandatory DESCRIPTION "The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) - highLineVoltage(2) by an over voltage greater than the high transfer vloltage. - brownout(3) five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) - rateOfVoltageChange(10) the line voltage." ::= { upsAdvInput 5 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvInputLineFailCause OBJECT-TYPE SYNTAX INTEGER { noTransfer(1), highLineVoltage(2), brownout(3), blackout(4), smallMomentarySag(5), deepMomentarySag(6), smallMomentarySpike(7), largeMomentarySpike(8), selfTest(9), rateOfVoltageChange(10) } ACCESS read-only STATUS mandatory DESCRIPTION "The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) - highLineVoltage(2) by an over voltage greater than the high transfer voltage. - brownout(3) five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) - rateOfVoltageChange(10) the line voltage." ::= { upsAdvInput 5 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.3.2.5.0 | upsAdvInputLineFailCause | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.3.2.1 | upsAdvInputLineVoltage | 1 | 1 | The current utility line voltage in VAC. |
1.3.6.1.4.1.318.1.1.1.3.2.2 | upsAdvInputMaxLineVoltage | 1 | 1 | The maximum utility line voltage in VAC over the previous 1 minute period. |
1.3.6.1.4.1.318.1.1.1.3.2.3 | upsAdvInputMinLineVoltage | 1 | 1 | The minimum utility line voltage in VAC over the previous 1 minute period. |
1.3.6.1.4.1.318.1.1.1.3.2.4 | upsAdvInputFrequency | 1 | 1 | The current input frequency to the UPS system in Hz. |
1.3.6.1.4.1.318.1.1.1.3.2.6 | upsAdvInputNominalFrequency | 1 | 1 | The nominal input frequency of the UPS system in Hz. |
1.3.6.1.4.1.318.1.1.1.3.2.7 | upsAdvInputNominalVoltage | 1 | 1 | The nominal input voltage of the UPS system in VAC. |
1.3.6.1.4.1.318.1.1.1.3.2.8 | upsAdvInputBypassNominalFrequency | 1 | 1 | The nominal bypass input frequency of the UPS system in Hz. |
1.3.6.1.4.1.318.1.1.1.3.2.9 | upsAdvInputBypassNominalVoltage | 1 | 1 | The nominal bypass input voltage of the UPS system in VAC. |
1.3.6.1.4.1.318.1.1.1.3.2.10 | upsAdvInputStatisticsTable | 1 | 7 | A list of input table entries. The number of entries is given by the value of upsPhaseNumInputs. |