Set the priority of the mode for alarms and events
with the nonessential stop behavior. Nonessential
modes are disabled during nonessential stop alarms
and events.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Set the priority of the mode for alarms and events
with the nonessential stop behavior. Nonessential
modes are disabled during nonessential stop alarms
and events.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
airFMSysDehumEssFunction OBJECT-TYPE SYNTAX INTEGER { notApplicable (1), yes (2), no (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and events. A value of notApplicable indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysDehumidify 2 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airFMSysDehumEssFunction OBJECT-TYPE SYNTAX INTEGER { notApplicable (1), yes (2), no (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and events. A value of notApplicable indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysDehumidify 2 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.7.2.0 | airFMSysDehumEssFunction | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.7.1 | airFMSysDehumState | 1 | 1 | Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they ar… |
1.3.6.1.4.1.318.1.1.13.1.4.7.3 | airFMSysDehumSetpoint | 1 | 1 | The target value for the selected control sensor air for this mode. It must be at least 1.0 % RH above the humidification setpoin… |
1.3.6.1.4.1.318.1.1.13.1.4.7.4 | airFMSysDehumDeadband | 1 | 1 | The humidity range above the setpoint at which the dehumidification mode will output at 100%. The deadband does not apply to PID … |
1.3.6.1.4.1.318.1.1.13.1.4.7.5 | airFMSysDehumCapacity | 1 | 1 | Set the dehumidification mode to use either half of the cooling coil or the full coil when dehumidifying the room. A value of notA… |
1.3.6.1.4.1.318.1.1.13.1.4.7.6 | airFMSysDehumPIDMethod | 1 | 1 | Set the multipliers that the PID algorithm will use to calculate the output. Proportional, Proportional + Integral, or Proportion… |
1.3.6.1.4.1.318.1.1.13.1.4.7.7 | airFMSysDehumPIDGainP | 1 | 1 | Set the proportional multiplier to correct for differences between the selected control sensor actual humidity and the setpoint. … |
1.3.6.1.4.1.318.1.1.13.1.4.7.8 | airFMSysDehumPIDResetRateI | 1 | 1 | Set the integral multiplier to correct for the proportional offset. Measured in %/(%RH * min). A value of -2147483648 indicates … |
1.3.6.1.4.1.318.1.1.13.1.4.7.9 | airFMSysDehumPIDDerivativeD | 1 | 1 | Set the derivative multiplier to counteract overshoot and droop during changes in the room humidity. Measure in %/(%RH / min). A v… |