The cooling unit operating mode.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The cooling unit operating mode.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
airIRRP100UnitStatusOperateMode OBJECT-TYPE SYNTAX INTEGER { standby (1), on (2), idle (3), prestart (4), service (5), backup (6), assist (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The cooling unit operating mode." ::= { airIRRP100UnitStatus 1 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airIRRP100UnitStatusOperateMode OBJECT-TYPE SYNTAX INTEGER { standby (1), on (2), idle (3), prestart (4), service (5), backup (6), assist (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The cooling unit operating mode." ::= { airIRRP100UnitStatus 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.1.0 | airIRRP100UnitStatusOperateMode | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.2 | airIRRP100UnitStatusRackInletTempUS | 1 | 1 | The unit rack inlet temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.3 | airIRRP100UnitStatusRackInletTempMetric | 1 | 1 | The unit rack inlet temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.4 | airIRRP100UnitStatusSupplyAirTempUS | 1 | 1 | The unit supply air temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.5 | airIRRP100UnitStatusSupplyAirTempMetric | 1 | 1 | The unit supply air temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.6 | airIRRP100UnitStatusReturnAirTempUS | 1 | 1 | The unit return air temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.7 | airIRRP100UnitStatusReturnAirTempMetric | 1 | 1 | The unit return air temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.8 | airIRRP100UnitStatusSupplyHumidity | 1 | 1 | The relative humidity of the supply air in tenths of percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.9 | airIRRP100UnitStatusReturnHumidity | 1 | 1 | The relative humidity of the return air in tenths of percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.10 | airIRRP100UnitStatusAirFlowUS | 1 | 1 | The unit air flow in cubic feet per minute. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.11 | airIRRP100UnitStatusAirFlowMetric | 1 | 1 | The unit air flow in hundredths of liters per second. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.12 | airIRRP100UnitStatusFanSpeed | 1 | 1 | The unit average fan speed in tenths of percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.13 | airIRRP100UnitStatusCoolDemand | 1 | 1 | The unit cooling demand in tenths of kiloWatts. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.14 | airIRRP100UnitStatusCoolOutput | 1 | 1 | The unit cooling output in tenths of kiloWatts. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.15 | airIRRP100UnitStatusHumidifyDemand | 1 | 1 | The amount of humidification the unit is demanding from the humidifier in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.16 | airIRRP100UnitStatusHumidifyOutput | 1 | 1 | The actual humidification output of the unit in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.17 | airIRRP100UnitStatusDehumidifyDemand | 1 | 1 | The amount of dehumidification the unit is demanding in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.18 | airIRRP100UnitStatusDehumidifyOutput | 1 | 1 | The actual dehumidification output of the unit in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.19 | airIRRP100UnitStatusReheatDemand | 1 | 1 | The amount of heating the unit is demanding from the electric heater in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.20 | airIRRP100UnitStatusReheatOutput | 1 | 1 | The actual heating output of the unit in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.21 | airIRRP100UnitStatusInputState | 1 | 1 | The state of the input contact. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.22 | airIRRP100UnitStatusOutputState | 1 | 1 | The state of the output relay. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.23 | airIRRP100UnitStatusRackInletTemperature1US | 1 | 1 | The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.24 | airIRRP100UnitStatusRackInletTemperature1Metric | 1 | 1 | The unit rack inlet temperature sensor in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.25 | airIRRP100UnitStatusRackInletTemperature2US | 1 | 1 | The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.26 | airIRRP100UnitStatusRackInletTemperature2Metric | 1 | 1 | The unit rack inlet temperature sensor in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.27 | airIRRP100UnitStatusRackInletTemperature3US | 1 | 1 | The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.28 | airIRRP100UnitStatusRackInletTemperature3Metric | 1 | 1 | The unit rack inlet temperature sensor in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.29 | airIRRP100UnitStatusFilterDPUS | 1 | 1 | The unit air filter differential pressure in hundredths of inches of water. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.30 | airIRRP100UnitStatusFilterDPMetric | 1 | 1 | The unit air filter differential pressure in Pa. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.31 | airIRRP100UnitStatusContainmtDPUS | 1 | 1 | The unit containment differential pressure in hundredths of inches of water. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.32 | airIRRP100UnitStatusContainmtDPMetric | 1 | 1 | The unit containment differential pressure in Pa. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.33 | airIRRP100UnitStatusHumidifierCurrent | 1 | 1 | The humidifier current of the unit in amperes. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.34 | airIRRP100UnitStatusHumidifierWaterConductivity | 1 | 1 | The water conductivity in the humidifier of the unit in microSiemens/cm. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.35 | airIRRP100UnitStatusCompressorDriveSpeed | 1 | 1 | The compressor drive speed in hundredths of Hertz. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.36 | airIRRP100UnitStatusCompressorDrivePower | 1 | 1 | The compressor drive power consumption in tenths of kiloWatts. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.37 | airIRRP100UnitStatusCompressorDriveVoltage | 1 | 1 | The compressor drive voltage consumption in tenths of volts. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.38 | airIRRP100UnitStatusCompressorDriveCurrent | 1 | 1 | The compressor drive voltage consumption in tenths of amperes. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.39 | airIRRP100UnitStatusCompressorDriveDCLinkVoltage | 1 | 1 | The compressor drive DC link voltage in tenths of volts. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.40 | airIRRP100UnitStatusCompressorDriveHeatSinkTempUS | 1 | 1 | The temperature of the compressor drive heatsink in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.41 | airIRRP100UnitStatusCompressorDriveHeatSinkTempMetric | 1 | 1 | The temperature of the compressor drive heatsink in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.42 | airIRRP100UnitStatusCompressorDriveControlCardTempUS | 1 | 1 | The temperature of the compressor drive control card in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.43 | airIRRP100UnitStatusCompressorDriveControlCardTempMetric | 1 | 1 | The temperature of the compressor drive control card in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.44 | airIRRP100UnitStatusCompressorDriveWarningStatus | 1 | 1 | The four byte warning status of the compressor drive in hexadecimal. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.45 | airIRRP100UnitStatusCompressorDriveAlarmStatus | 1 | 1 | The four byte alarm status of the compressor drive in hexadecimal. |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.46 | airIRRP100UnitStatusSuctionPressureUS | 1 | 1 | Unit suction pressure in pounds per square inch (PSI). |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.47 | airIRRP100UnitStatusSuctionPressureMetric | 1 | 1 | Unit suction pressure in kiloPascals (kPa). |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.48 | airIRRP100UnitStatusDischargePressureUS | 1 | 1 | Unit discharge pressure in pounds per square inch (PSI). |
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.49 | airIRRP100UnitStatusDischargePressureMetric | 1 | 1 | Unit discharge pressure in kiloPascals (kPa). |