airIRRP500GroupStatus OBJECT IDENTIFIER ::= { airIRRP500Group 1 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airIRRP500GroupStatus OBJECT IDENTIFIER ::= { airIRRP500Group 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.1 | airIRRP500GroupStatusAirFlowUS | 1 | 1 | Group air flow in cubic feet per minute. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.2 | airIRRP500GroupStatusAirFlowMetric | 1 | 1 | Group air flow in liters per second. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.3 | airIRRP500GroupStatusMaxRackInletTempUS | 1 | 1 | Group maximum rack inlet temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.4 | airIRRP500GroupStatusMaxRackInletTempMetric | 1 | 1 | Group maximum rack inlet temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.5 | airIRRP500GroupStatusMinRackInletTempUS | 1 | 1 | Group minimum rack inlet temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.6 | airIRRP500GroupStatusMinRackInletTempMetric | 1 | 1 | Group minimum rack inlet temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.7 | airIRRP500GroupStatusCoolDemand | 1 | 1 | Group coolant demand in tenths of kiloWatts. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.8 | airIRRP500GroupStatusCoolOutput | 1 | 1 | Group coolant output in tenths of kiloWatts. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.9 | airIRRP500GroupStatusHumidifyDemand | 1 | 1 | The amount of humidification the group is demanding from the humidifiers in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.10 | airIRRP500GroupStatusHumidifyOutput | 1 | 1 | The actual amount of humidification the group is supplying in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.11 | airIRRP500GroupStatusDehumidifyDemand | 1 | 1 | The amount of dehumidification the group is demanding from the electric heaters in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.12 | airIRRP500GroupStatusDehumidifyOutput | 1 | 1 | The actual amount of dehumidification the group is supplying in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.13 | airIRRP500GroupStatusReheatDemand | 1 | 1 | The amount of heating the group is demanding from the electric heaters in percent. |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.14 | airIRRP500GroupStatusReheatOutput | 1 | 1 | The actual amount of heating the group is supplying in percent. |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2 | airIRRP500GroupSetpoints | 11 | 22 | None |
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3 | airIRRP500GroupConfig | 15 | 25 | None |