airIRG2RDT2Status OBJECT IDENTIFIER ::= { airIRG2RDType2 1 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airIRG2RDT2Status OBJECT IDENTIFIER ::= { airIRG2RDType2 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.4.5.2.1.1 | airIRG2RDT2StatusOperateMode | 1 | 1 | The cooling unit operating mode. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.2 | airIRG2RDT2StatusCoolOutput | 1 | 1 | The unit cooling output in tenths of kilowatts (kW). |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.3 | airIRG2RDT2StatusCoolDemand | 1 | 1 | The unit cooling demand in tenths of kilowatts (kW). |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.4 | airIRG2RDT2StatusAirFlowUS | 1 | 1 | The unit air flow in cubic feet per minute. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.5 | airIRG2RDT2StatusAirFlowMetric | 1 | 1 | The unit air flow in liters per second. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.6 | airIRG2RDT2StatusRackInletTempUS | 1 | 1 | The unit rack inlet temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.7 | airIRG2RDT2StatusRackInletTempMetric | 1 | 1 | The unit rack inlet temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.8 | airIRG2RDT2StatusSupplyAirTempUS | 1 | 1 | The unit supply air temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.9 | airIRG2RDT2StatusSupplyAirTempMetric | 1 | 1 | The unit supply air temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.10 | airIRG2RDT2StatusReturnAirTempUS | 1 | 1 | The unit return air temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.11 | airIRG2RDT2StatusReturnAirTempMetric | 1 | 1 | The unit return air temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.12 | airIRG2RDT2StatusSuctionTempUS | 1 | 1 | The unit suction temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.13 | airIRG2RDT2StatusSuctionTempMetric | 1 | 1 | The unit suction temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.14 | airIRG2RDT2StatusSuperheatTempUS | 1 | 1 | The unit superheat temperature in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.15 | airIRG2RDT2StatusSuperheatTempMetric | 1 | 1 | The unit superheat temperature in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.16 | airIRG2RDT2StatusFilterDPUS | 1 | 1 | The unit air filter differential pressure in hundredths of inches of water. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.17 | airIRG2RDT2StatusFilterDPMetric | 1 | 1 | The unit air filter differential pressure in pascals (Pa). |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.18 | airIRG2RDT2StatusSuctionPressureUS | 1 | 1 | Unit suction pressure in pounds per square inch (PSI). |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.19 | airIRG2RDT2StatusSuctionPressureMetric | 1 | 1 | Unit suction pressure in kiloPascals (kPa). |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.20 | airIRG2RDT2StatusDischargePressureUS | 1 | 1 | Unit discharge pressure in pounds per square inch (PSI). |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.21 | airIRG2RDT2StatusDischargePressureMetric | 1 | 1 | Unit discharge pressure in kiloPascals (kPa). |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.22 | airIRG2RDT2StatusEvaporatorFanSpeed | 1 | 1 | The unit average evaporator fan speed in tenths of percent. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.23 | airIRG2RDT2StatusInputState | 1 | 1 | The state of the input contact. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.24 | airIRG2RDT2StatusOutputState | 1 | 1 | The state of the output relay. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.25 | airIRG2RDT2StatusOHEInputState | 1 | 1 | The state of the outside heat exchanger(OHE) input contact. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.26 | airIRG2RDT2StatusOHEOutputState | 1 | 1 | The state of the outside heat exchanger(OHE) output relay. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.27 | airIRG2RDT2StatusCompressor | 1 | 1 | The state (off/on) of the compressor. |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.28 | airIRG2RDT2StatusFluidValvePos | 1 | 1 | The position of the fluid valve in percent. This OID is only valid when airIRG2RDT2ConfigUnitType indicates fluidCooled(1). |
1.3.6.1.4.1.318.1.1.13.4.5.2.1.29 | airIRG2RDT2StatusHotGasBypassValvePos | 1 | 1 | The position of the hot gas bypass valve in hundredths of percent. |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.4.5.2.2 | airIRG2RDT2RunHours | 8 | 21 | None |
1.3.6.1.4.1.318.1.1.13.4.5.2.3 | airIRG2RDT2ServiceIntervals | 2 | 4 | None |
1.3.6.1.4.1.318.1.1.13.4.5.2.4 | airIRG2RDT2Thresholds | 6 | 12 | None |
1.3.6.1.4.1.318.1.1.13.4.5.2.5 | airIRG2RDT2Setpoints | 0 | 0 | None |
1.3.6.1.4.1.318.1.1.13.4.5.2.6 | airIRG2RDT2Config | 9 | 18 | None |