Reference record for OID 1.3.6.1.4.1.318.1.1.13.6.4.2.1



parent
1.3.6.1.4.1.318.1.1.13.6.4.2 (airIRG3RDUStatusTable)
node code
1
node name
airIRG3RDUStatusEntry
dot oid
1.3.6.1.4.1.318.1.1.13.6.4.2.1
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airIRGen3(6) airIRG3RDU(4) airIRG3RDUStatusTable(2) airIRG3RDUStatusEntry(1)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airIRGen3(6) airIRG3RDU(4) airIRG3RDUStatusTable(2) airIRG3RDUStatusEntry(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airIRGen3(6) airIRG3RDU(4) airIRG3RDUStatusTable(2) airIRG3RDUStatusEntry(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airIRGen3(6) airIRG3RDU(4) airIRG3RDUStatusTable(2) airIRG3RDUStatusEntry(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airIRGen3(6) airIRG3RDU(4) airIRG3RDUStatusTable(2) airIRG3RDUStatusEntry(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airIRGen3(6) airIRG3RDU(4) airIRG3RDUStatusTable(2) airIRG3RDUStatusEntry(1)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airIRGen3/airIRG3RDU/airIRG3RDUStatusTable/airIRG3RDUStatusEntry
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airIRGen3/airIRG3RDU/airIRG3RDUStatusTable/airIRG3RDUStatusEntry
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airIRGen3/airIRG3RDU/airIRG3RDUStatusTable/airIRG3RDUStatusEntry
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airIRGen3/airIRG3RDU/airIRG3RDUStatusTable/airIRG3RDUStatusEntry
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airIRGen3/airIRG3RDU/airIRG3RDUStatusTable/airIRG3RDUStatusEntry
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airIRGen3/airIRG3RDU/airIRG3RDUStatusTable/airIRG3RDUStatusEntry
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/13/6/4/2/1

    Description by mibdepot

    The RDU status table entry.

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    The RDU status table entry.

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    airIRG3RDUStatusEntry OBJECT-TYPE SYNTAX AirIRG3RDUStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The RDU status table entry." INDEX { airIRG3RDUStatusDeviceIndex} ::= { airIRG3RDUStatusTable 1 }

    Information by oid_info

    Vendor: APC
    Module: PowerNet-MIB (powernet401.mib)
    Type: ENTRY
    Access: not-accessible
    Syntax: AirIRG3RDUStatusEntry

    Automatically extracted from www.mibdepot.com

    Information by circitor

    airIRG3RDUStatusEntry OBJECT-TYPE SYNTAX AirIRG3RDUStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The RDU status table entry." INDEX { airIRG3RDUStatusDeviceIndex} ::= { airIRG3RDUStatusTable 1 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Children (43)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.1 airIRG3RDUStatusDeviceIndex 0 0 Index of RDU status table.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.2 airIRG3RDUID 0 0 The current RDU ID (1 to F).
    Configured RDU only shall display ID, else return -1.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.3 airIRG3RDUStatusOnReadyStandby 0 0 The RDU current status.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.4 airIRG3RDUStatusOperatingMode 0 0 The RDU actual operating mode.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.5 airIRG3RDUStatusLeadPump 0 0 The RDU lead pump.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.6 airIRG3RDUStatusStartupDelay 0 0 The RDU start up delay in seconds.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.7 airIRG3RDUStatusPumpChangeOverInterval 0 0 The RDU pump change over interval in days.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.8 airIRG3RDUStatusStopOnLeakDetect 0 0 The RDU status of stop on leak detect.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.9 airIRG3RDUStatusPowerSource 0 0 The RDU power source status.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.10 airIRG3RDUStatusTotalRDUOutputPower 0 0 The RDU output power in tenths of kilowatts (kW).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.11 airIRG3RDUStatusInletWaterTempUS 0 0 The RDU inlet water temperature in tenths of
    degrees Fahrenheit.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.12 airIRG3RDUStatusInletWaterTempMetric 0 0 The RDU inlet water temperature in tenths of
    degrees Celsius.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.13 airIRG3RDUStatusOutletWaterTempUS 0 0 The RDU outlet water temperature in tenths of
    degrees Fahrenheit.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.14 airIRG3RDUStatusOutletWaterTempMetric 0 0 The RDU outlet water temperature in tenths of
    degrees Celsius.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.15 airIRG3RDUStatusCondenserSaturationTempUS 0 0 The RDU condenser saturation temperature in tenths of
    degrees Fahrenheit.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.16 airIRG3RDUStatusCondenserSaturationTempMetric 0 0 The RDU condenser saturation temperature in tenths of
    degrees Celsius.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.17 airIRG3RDUStatusDewPointTempUS 0 0 The RDU dew point temperature in tenths of
    degrees Fahrenheit.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.18 airIRG3RDUStatusDewPointTempMetric 0 0 The RDU dew point temperature in tenths of
    degrees Celsius.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.19 airIRG3RDUStatusPumpOutletTempUS 0 0 The RDU pump outlet temperature in tenths of
    degrees Fahrenheit.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.20 airIRG3RDUStatusPumpOutletTempMetric 0 0 The RDU pump outlet temperature in tenths of
    degrees Celsius.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.21 airIRG3RDUStatusSubcoolerOutletTempUS 0 0 The RDU sub cooler outlet temperature in tenths of
    degrees Fahrenheit.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.22 airIRG3RDUStatusSubcoolerOutletTempMetric 0 0 The RDU sub cooler outlet temperature in tenths of
    degrees Celsius.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.23 airIRG3RDUStatusCondenserOutletTempUS 0 0 The RDU condenser outlet temperature in tenths of
    degrees Fahrenheit.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.24 airIRG3RDUStatusCondenserOutletTempMetric 0 0 The RDU condenser outlet temperature in tenths of
    degrees Celsius.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.25 airIRG3RDUStatusCondenserInletTempUS 0 0 The RDU condenser inlet temperature in tenths of
    degrees Fahrenheit.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.26 airIRG3RDUStatusCondenserInletTempMetric 0 0 The RDU condenser inlet temperature in tenths of
    degrees Celsius.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.27 airIRG3RDUStatusCondenserOutletPressureUS 0 0 The RDU condenser outlet pressure in
    pounds per square inch (PSI).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.28 airIRG3RDUStatusCondenserOutletPressureMetric 0 0 The RDU condenser outlet pressure in kiloPascals (KPa).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.29 airIRG3RDUStatusPump1HeadPressureUS 0 0 The RDU Pump 1 head pressure in pounds per square inch (PSI).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.30 airIRG3RDUStatusPump1HeadPressureMetric 0 0 The RDU Pump 1 head pressure in kiloPascals (KPa).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.31 airIRG3RDUStatusPump2HeadPressureUS 0 0 The RDU Pump 2 head pressure in pounds per square inch (PSI).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.32 airIRG3RDUStatusPump2HeadPressureMetric 0 0 The RDU Pump 2 head pressure in kiloPascals (KPa).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.33 airIRG3RDUStatusPump1Speed 0 0 The RDU Pump 1 speed in revolutions per minute (RPM).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.34 airIRG3RDUStatusPump2Speed 0 0 The RDU Pump 2 speed in revolutions per minute (RPM).
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.35 airIRG3RDUStatusCWValvePosition 0 0 The RDU CW Valve position in % open
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.36 airIRG3RDUStatusReceiverLiquidLevel 0 0 The RDU receiver liquid level in % Full
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.37 airIRG3RDUStatusDCPowerSupply1Current 0 0 The RDU DC Power Supply 1 Current in Amps
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.38 airIRG3RDUStatusDCPowerSupply2Current 0 0 The RDU DC Power Supply 2 Current in Amps
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.39 airIRG3RDUStatusTotalDCPowerSupplyCurrent 0 0 The RDU Total DC Power Supply Current in Amps
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.40 airIRG3RDUStatusInputState 0 0 The RDU Input state.
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.41 airIRG3RDUStatusOutputState 0 0 The RDU Output state
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.42 airIRG3RDUStatusByPassValvePosition 0 0 The RDU By Pass Valve position in % open
    1.3.6.1.4.1.318.1.1.13.6.4.2.1.43 airIRG3RDUStatusRefrigerantLeakDetector 0 0 The RDU refrigerant leak detector status.