This OID defines the desired base airflow of the ARU, and sets the
speed of the ARU fans when the temperature override is inactive.
Values specified in cfm (cubic feet per minute) can be converted
to metric values using the conversion factor:
1 cfm = 1.70 m^3/hr (cubic meters per hour).
Values (1) through (9) are for support of legacy (1st generation) ARUs.
Writing these values to a 2nd generation ARU will result in the following:
A value greater than (9) will be ignored by a 1st generation ARU.
aruOff (1) - Ignored
aru85F-29C (2) - 1200 cfm
aru90F-32C (3) - 800 cfm
aru95F-35C (4) - 500 cfm
aru100F-38C (5) - 400 cfm
aru7kW (6) - 1200 cfm
aru5kW (7) - 800 cfm
aru3kW (8) - 500 cfm
aru2kW (9) - 400 cfm
NOTE: -1 will be returned if the ARU is not communicating.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
This OID defines the desired base airflow of the ARU, and sets the
speed of the ARU fans when the temperature override is inactive.
Values specified in cfm (cubic feet per minute) can be converted
to metric values using the conversion factor:
1 cfm = 1.70 m^3/hr (cubic meters per hour).
Values (1) through (9) are for support of legacy (1st generation) ARUs.
Writing these values to a 2nd generation ARU will result in the following:
A value greater than (9) will be ignored by a 1st generation ARU.
aruOff (1) - Ignored
aru85F-29C (2) - 1200 cfm
aru90F-32C (3) - 800 cfm
aru95F-35C (4) - 500 cfm
aru100F-38C (5) - 400 cfm
aru7kW (6) - 1200 cfm
aru5kW (7) - 800 cfm
aru3kW (8) - 500 cfm
aru2kW (9) - 400 cfm
NOTE: -1 will be returned if the ARU is not communicating.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
rARUConfigAruRemoteSetpoint OBJECT-TYPE SYNTAX INTEGER { aruOff (1), aru85F-29C (2), aru90F-32C (3), aru95F-35C (4), aru100F-38C (5), aru7kW-1200cfm (6), aru5kW-800cfm (7), aru3kW-500cfm (8), aru2kW-300cfm (9), aru400cfm (10), aru600cfm (11), aru700cfm (12), aru900cfm (13), aru1000cfm (14), aru1400cfm (15), aru1600cfm (16), aru1800cfm (17), aru2000cfm (18) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID defines the desired base airflow of the ARU, and sets the speed of the ARU fans when the temperature override is inactive. Values specified in cfm (cubic feet per minute) can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour). Values (1) through (9) are for support of legacy (1st generation) ARUs. Writing these values to a 2nd generation ARU will result in the following: A value greater than (9) will be ignored by a 1st generation ARU. aruOff (1) - Ignored aru85F-29C (2) - 1200 cfm aru90F-32C (3) - 800 cfm aru95F-35C (4) - 500 cfm aru100F-38C (5) - 400 cfm aru7kW (6) - 1200 cfm aru5kW (7) - 800 cfm aru3kW (8) - 500 cfm aru2kW (9) - 400 cfm NOTE: -1 will be returned if the ARU is not communicating." ::= { rARUConfigEntry 3 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
rARUConfigAruRemoteSetpoint OBJECT-TYPE SYNTAX INTEGER { aruOff (1), aru85F-29C (2), aru90F-32C (3), aru95F-35C (4), aru100F-38C (5), aru7kW-1200cfm (6), aru5kW-800cfm (7), aru3kW-500cfm (8), aru2kW-300cfm (9), aru400cfm (10), aru600cfm (11), aru700cfm (12), aru900cfm (13), aru1000cfm (14), aru1400cfm (15), aru1600cfm (16), aru1800cfm (17), aru2000cfm (18) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID defines the desired base airflow of the ARU, and sets the speed of the ARU fans when the temperature override is inactive. Values specified in cfm (cubic feet per minute) can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour). Values (1) through (9) are for support of legacy (1st generation) ARUs. Writing these values to a 2nd generation ARU will result in the following: A value greater than (9) will be ignored by a 1st generation ARU. aruOff (1) - Ignored aru85F-29C (2) - 1200 cfm aru90F-32C (3) - 800 cfm aru95F-35C (4) - 500 cfm aru100F-38C (5) - 400 cfm aru7kW (6) - 1200 cfm aru5kW (7) - 800 cfm aru3kW (8) - 500 cfm aru2kW (9) - 400 cfm NOTE: -1 will be returned if the ARU is not communicating." ::= { rARUConfigEntry 3 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.14.2.1.1.1 | rARUConfigAruIndex | 0 | 0 | The index to the ARU entry. |
1.3.6.1.4.1.318.1.1.14.2.1.1.2 | rARUConfigAruName | 0 | 0 | The name of the ARU. |
1.3.6.1.4.1.318.1.1.14.2.1.1.4 | rARUConfigAruTempOvrdEnableDisable | 0 | 0 | This OID is used to enable/disable the remote temperature override setting of the ARU. If this OID is set to 1, the remote sett… |
1.3.6.1.4.1.318.1.1.14.2.1.1.5 | rARUConfigAruTempOvrdSetpoint | 0 | 0 | This OID is the Temperature Override setpoint of the ARU. NOTE: -1 will be returned if the ARU is not communicating. Values are r… |
1.3.6.1.4.1.318.1.1.14.2.1.1.6 | rARUConfigAruMasterControl | 0 | 0 | This is the master on/off control for the ARU. |