Battery high voltage threshold. If system battery voltage exceeds threshold
a battery high voltage alarm will occur.
Values are represented in thousandths of Volts (mV).
Attempts to set the value above or below the acceptable range of the powerplant
will cause the value to be set at the high or low point of the range respectively.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Battery high voltage threshold. If system battery voltage exceeds threshold
a battery high voltage alarm will occur.
Values are represented in thousandths of Volts (mV).
Attempts to set the value above or below the acceptable range of the powerplant
will cause the value to be set at the high or low point of the range respectively.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
dm3ConfigBattHighVoltThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery high voltage threshold. If system battery voltage exceeds threshold a battery high voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 5 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
dm3ConfigBattHighVoltThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery high voltage threshold. If system battery voltage exceeds threshold a battery high voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 5 }
| OID | Name | Sub children | Sub Nodes Total | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.318.1.1.7.2.3.5.0 | dm3ConfigBattHighVoltThresh | 0 | 0 | None |
| OID | Name | Sub children | Sub Nodes Total | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.318.1.1.7.2.3.1 | dm3ConfigBattFloatVolt | 1 | 1 | Battery Float Voltage. This setting controls the power plant voltage. Values are represented in thousandths of Volts (mV). Atte… |
| 1.3.6.1.4.1.318.1.1.7.2.3.2 | dm3ConfigBattMaxRecharge | 1 | 1 | Battery Maximum Recharge Rate. This setting controls the battery max recharge rate. The value is based on C/20 for 240 AHr bat… |
| 1.3.6.1.4.1.318.1.1.7.2.3.3 | dm3ConfigBattDischargeThresh | 1 | 1 | Battery discharge threshold. If battery output current exceeds threshold a battery discharge alarm will occur. Values are repre… |
| 1.3.6.1.4.1.318.1.1.7.2.3.4 | dm3ConfigBattDischargeAlarm | 1 | 1 | For the Battery Discharge Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this O… |
| 1.3.6.1.4.1.318.1.1.7.2.3.6 | dm3ConfigBattHighVoltAlarm | 1 | 1 | For the Battery High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting thi… |
| 1.3.6.1.4.1.318.1.1.7.2.3.7 | dm3ConfigBattLowVoltThresh | 1 | 1 | Battery low voltage threshold. If system battery voltage is under threshold a battery low voltage alarm will occur. Values are … |
| 1.3.6.1.4.1.318.1.1.7.2.3.8 | dm3ConfigBattLowVoltAlarm | 1 | 1 | For the Battery Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this… |
| 1.3.6.1.4.1.318.1.1.7.2.3.9 | dm3ConfigBattHighTempThresh | 1 | 1 | dm3ConfigBattHightempThresh |
| 1.3.6.1.4.1.318.1.1.7.2.3.10 | dm3ConfigBattHighTempAlarm | 1 | 1 | dm3ConfigBattHightempAlarm |
| 1.3.6.1.4.1.318.1.1.7.2.3.11 | dm3ConfigBattLowTempThresh | 1 | 1 | Battery low temperature threshold. If system battery temperature is under threshold a battery low temperature alarm will occur.… |
| 1.3.6.1.4.1.318.1.1.7.2.3.12 | dm3ConfigBattLowTempAlarm | 1 | 1 | For the Battery Low Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting … |
| 1.3.6.1.4.1.318.1.1.7.2.3.13 | dm3ConfigBattAmpHour | 1 | 1 | Battery Amp-Hour Size. Units are thousandths of Amp hours (mAHr). Attempts to set the value above or below the acceptable range… |
| 1.3.6.1.4.1.318.1.1.7.2.3.14 | dm3ConfigCompMethod | 1 | 1 | This OID is used to configure and get the state of the battery temperature compensation. Setting this OID to tempcompOn (1) will… |
| 1.3.6.1.4.1.318.1.1.7.2.3.15 | dm3ConfigCompTempCoeff | 1 | 1 | Compensation Temperature Coefficient. (uV/degC/cell). Units are presented in microvolts. Attempts to set the value above or belo… |
| 1.3.6.1.4.1.318.1.1.7.2.3.16 | dm3ConfigHighKneeTemp | 1 | 1 | High Knee for temperature compensation: Compensation temperature coefficient becomes 0mV/degC/cell. Values are represented in t… |
| 1.3.6.1.4.1.318.1.1.7.2.3.17 | dm3ConfigLowKneeTemp | 1 | 1 | Low Knee for temperature compensation: Compensation temperature coefficient becomes 0mV/degC/cell. Values are represented in th… |
| 1.3.6.1.4.1.318.1.1.7.2.3.18 | dm3ConfigBattHwCurrentAlarm | 1 | 1 | For the Battery Current Hardware Alarm (indicating current is outside realistic limits, or a possible measurement fault; Setting … |
| 1.3.6.1.4.1.318.1.1.7.2.3.19 | dm3ConfigBattHwTempAlarm | 1 | 1 | For the Battery Temperature Hardware Alarm (indicating temperature is outside realistic limits, or a possible measurement fault;… |