sensorProbeHumiditySirenOnPort OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The sensor port that the siren will listen to. If this is set to 255, then the siren will not listen to any sensor ports"
View at oid-info.com
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3854.1.2.2.1.17.1.1 | hhmsSensorArrayHumidityDescription | 0 | 0 | A Description of this sensor |
1.3.6.1.4.1.3854.1.2.2.1.17.1.2 | hhmsSensorArrayHumidityLocation | 0 | 0 | The physical location of this sensor |
1.3.6.1.4.1.3854.1.2.2.1.17.1.3 | hhmsSensorArrayHumidityPercent | 1 | 1 | The relative humidity percentage measured by this sensor |
1.3.6.1.4.1.3854.1.2.2.1.17.1.4 | hhmsSensorArrayHumidityStatus | 1 | 1 | The current status of this Sensor |
1.3.6.1.4.1.3854.1.2.2.1.17.1.5 | hhmsSensorArrayHumidityOnline | 0 | 0 | If this Sensor is currently online |
1.3.6.1.4.1.3854.1.2.2.1.17.1.6 | hhmsSensorArrayHumidityGoOnline | 0 | 0 | To put online enter a 1, to take offline enter a 2 |
1.3.6.1.4.1.3854.1.2.2.1.17.1.7 | hhmsSensorArrayHumidityHighWarning | 0 | 0 | How high the relative humidity this sensor measures before it sends a warning |
1.3.6.1.4.1.3854.1.2.2.1.17.1.8 | hhmsSensorArrayHumidityHighCritical | 0 | 0 | How high the relative humidity this sensor measures before it becomes critical |
1.3.6.1.4.1.3854.1.2.2.1.17.1.9 | hhmsSensorArrayHumidityLowWarning | 0 | 0 | How low the relative humidity this sensor measures before it sends a warning |
1.3.6.1.4.1.3854.1.2.2.1.17.1.10 | hhmsSensorArrayHumidityLowCritical | 0 | 0 | How low the relative humidity this sensor measures before it becomes critical |
1.3.6.1.4.1.3854.1.2.2.1.17.1.11 | hhmsSensorArrayHumidityRearm | 0 | 0 | The percent relative humidity to rearm the status. For example if status goes from normal to warning, the humidity must go down… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.12 | hhmsSensorArrayHumidityTestStatus | 0 | 0 | Set the status for test purposes |
1.3.6.1.4.1.3854.1.2.2.1.17.1.13 | hhmsSensorArrayHumidityTestPercent | 0 | 0 | Enter the percent of relative humidity in this sensor for test purposes |
1.3.6.1.4.1.3854.1.2.2.1.17.1.14 | hhmsSensorArrayHumidityIndex | 0 | 0 | The index into the Humidity sensor table |
1.3.6.1.4.1.3854.1.2.2.1.17.1.15 | sensorProbeHumidityHighVoltage | 0 | 0 | sensorProbeHumidityHighVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "SP Only: The high vol… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.17 | sensorProbeHumidityEmailTrapLimit | 0 | 0 | sensorProbeHumidityEmailTrapLimit OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-write STATUS mandatory DESCR… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.18 | sensorProbeHumidityEmailTrapSchedule | 0 | 0 | sensorProbeHumidityEmailTrapSchedule OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "SP Only: … |
1.3.6.1.4.1.3854.1.2.2.1.17.1.19 | sensorProbeHumidityEmailTrapInterval | 0 | 0 | sensorProbeHumidityEmailTrapInterval OBJECT-TYPE SYNTAX INTEGER (0..60) ACCESS read-write STATUS mandatory DESCRIPTION "Minimum… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.20 | sensorProbeHumiditySendNormalTrap | 0 | 0 | sensorProbeHumiditySendNormalTrap OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-write STATUS mandatory DESCR… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.21 | sensorProbeHumidityDelayError | 0 | 0 | sensorProbeHumidityDelayError OBJECT-TYPE SYNTAX INTEGER (0..65534) ACCESS read-write STATUS mandatory DESCRIPTION "Time in sec… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.22 | sensorProbeHumidityDelayNormal | 0 | 0 | sensorProbeHumidityDelayNormal OBJECT-TYPE SYNTAX INTEGER (0..65534) ACCESS read-write STATUS mandatory DESCRIPTION "Time in se… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.23 | sensorProbeHumidityIndex | 0 | 0 | sensorProbeHumidityIndex OBJECT-TYPE SYNTAX INTEGER (0..7) ACCESS read-only STATUS mandatory DESCRIPTION "The index into the Hu… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.24 | sensorProbeHumidityAtoDAmountMaxVoltage | 0 | 0 | sensorProbeHumidityAtoDAmountMaxVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The maximum … |
1.3.6.1.4.1.3854.1.2.2.1.17.1.25 | sensorProbeHumidityAtoDAmountBaseVoltage | 0 | 0 | sensorProbeHumidityAtoDAmountBaseVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The base sc… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.26 | sensorProbeHumidityAtoDTypeUnit | 0 | 0 | sensorProbeHumidityAtoDTypeUnit OBJECT-TYPE SYNTAX INTEGER { absolute(1), percent(2) } ACCESS read-write STATUS mandatory DESCR… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.27 | sensorProbeHumidityDcUnit | 0 | 0 | sensorProbeHumidityDcUnit OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Display unit in DC v… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.28 | sensorProbeHumidityAtoDJumper | 0 | 0 | sensorProbeHumidityAtoDJumper OBJECT-TYPE SYNTAX INTEGER { jumperAt-60(-600), jumperAt-40(-400), jumperAt-30(-300), jumperAt-20… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.29 | sensorProbeHumidityRelayCycleTime | 0 | 0 | sensorProbeHumidityRelayCycleTime OBJECT-TYPE SYNTAX INTEGER (1..255) ACCESS read-write STATUS mandatory DESCRIPTION "Relay tog… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.30 | sensorProbeHumidityRelayOnPort | 0 | 0 | sensorProbeHumidityRelayOnPort OBJECT-TYPE SYNTAX INTEGER (0..255) ACCESS read-write STATUS mandatory DESCRIPTION "The sensor p… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.31 | sensorProbeHumidityRelayActiveStatus | 0 | 0 | sensorProbeHumidityRelayActiveStatus OBJECT-TYPE SYNTAX INTEGER { highWarning(3), highCritical(4), lowWarning(5), lowCritical(6… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.32 | sensorProbeHumidityRelayAction | 0 | 0 | sensorProbeHumidityRelayAction OBJECT-TYPE SYNTAX INTEGER { cycle(2), turn-on(3), turn-off(4) } ACCESS read-write STATUS mandat… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.33 | sensorProbeHumidityEmailInterval | 0 | 0 | sensorProbeHumidityEmailInterval OBJECT-TYPE SYNTAX INTEGER (0..60) ACCESS read-write STATUS mandatory DESCRIPTION "CP8 Only: M… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.34 | sensorProbeHumidity4to20mAUnit | 0 | 0 | sensorProbeHumidity4to20mAUnit OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Display unit in… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.35 | sensorProbeHumidityIndexCount | 0 | 0 | sensorProbeHumidityIndexCount OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Number of Humidity sens… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.36 | sensorProbeHumidityOffset | 0 | 0 | sensorProbeHumidityOffset OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Humidity Offset reading" |
1.3.6.1.4.1.3854.1.2.2.1.17.1.37 | sensorProbeHumiditySirenCycleTime | 0 | 0 | sensorProbeHumiditySirenCycleTime OBJECT-TYPE SYNTAX INTEGER (1..255) ACCESS read-write STATUS mandatory DESCRIPTION "Siren tog… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.39 | sensorProbeHumiditySirenActiveStatus | 0 | 0 | sensorProbeHumiditySirenActiveStatus OBJECT-TYPE SYNTAX INTEGER { highWarning(3), highCritical(4), lowWarning(5), lowCritical(6… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.40 | sensorProbeHumiditySirenAction | 0 | 0 | sensorProbeHumiditySirenAction OBJECT-TYPE SYNTAX INTEGER { cycle(2), turn-on(3), turn-off(4) } ACCESS read-write STATUS mandat… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.41 | sensorProbeHumidityAcknowledgement | 0 | 0 | sensorProbeHumidityAcknowledgement OBJECT-TYPE SYNTAX INTEGER { ack(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Acknow… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.42 | sensorProbeHumiditySirenDelayAlarm | 0 | 0 | sensorProbeHumiditySirenDelayAlarm OBJECT-TYPE SYNTAX INTEGER (1..255) ACCESS read-write STATUS mandatory DESCRIPTION "Siren de… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.43 | sensorProbeHumidityURL | 0 | 0 | sensorProbeHumidityURL OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Sensor URL link." |
1.3.6.1.4.1.3854.1.2.2.1.17.1.44 | sensorProbeHumidityOpenURL | 0 | 0 | sensorProbeHumidityOpenURL OBJECT-TYPE SYNTAX INTEGER { cur-window(0), new-window(2) } ACCESS read-write STATUS mandatory DESCR… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.45 | sensorProbeHumidityDatacollectType | 0 | 0 | sensorProbeHumidityDatacollectType OBJECT-TYPE SYNTAX INTEGER { average(1), highest(2), lowest(3) } ACCESS read-write STATUS ma… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.46 | sensorProbeHumidityContTimeHighCritical | 0 | 0 | sensorProbeHumidityContTimeHighCritical OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-write STATUS mandatory DESCRIPTION "C… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.47 | sensorProbeHumidityContTimeHighWarning | 0 | 0 | sensorProbeHumidityContTimeHighWarning OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-write STATUS mandatory DESCRIPTION "Co… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.48 | sensorProbeHumidityContTimeNormal | 0 | 0 | sensorProbeHumidityContTimeNormal OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-write STATUS mandatory DESCRIPTION "Continu… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.49 | sensorProbeHumidityContTimeLowWarning | 0 | 0 | sensorProbeHumidityContTimeLowWarning OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-write STATUS mandatory DESCRIPTION "Con… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.50 | sensorProbeHumidityContTimeLowCritical | 0 | 0 | sensorProbeHumidityContTimeLowCritical OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-write STATUS mandatory DESCRIPTION "Co… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.51 | sensorProbeHumidityContTimeSensorError | 0 | 0 | sensorProbeHumidityContTimeSensorError OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-write STATUS mandatory DESCRIPTION "Co… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.52 | sensorProbeHumidityCalendar | 0 | 0 | sensorProbeHumidityCalendar OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-write STATUS mandatory DESCRIPTION… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.53 | sensorProbeHumiditySendNormalMail | 0 | 0 | sensorProbeHumiditySendNormalMail OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-write STATUS mandatory DESCR… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.54 | sensorProbeHumiditySendTrap | 0 | 0 | sensorProbeHumiditySendTrap OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-write STATUS mandatory DESCRIPTION… |
1.3.6.1.4.1.3854.1.2.2.1.17.1.55 | sensorProbeHumiditySendMail | 0 | 0 | sensorProbeHumiditySendMail OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-write STATUS mandatory DESCRIPTION… |