The well known measurement source from the
'lgpPwrWellKnownMeasurements' sub-tree that is the preferred
input source of the system.
Parsed from file LIEBERT_GP_POWER.MIB.txt
Company: None
Module: LIEBERT-GP-POWER-MIB
The well known measurement source from the
'lgpPwrWellKnownMeasurements' sub-tree that is the preferred
input source of the system.
Parsed from file LIEBERT-GP-POWER-MIB.mib
Module: LIEBERT-GP-POWER-MIB
Vendor: Emerson Computer PowerRoger Draper
Module: LIEBERT-GP-POWER-MIB
[Automatically extracted from oidview.com]
lgpPwrPreferredSource OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system." ::= { lgpPwrSettings 1 }
lgpPwrPreferredSource OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system." ::= { lgpPwrSettings 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.476.1.42.3.5.4.1.0 | lgpPwrPreferredSource | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.476.1.42.3.5.4.2 | lgpPwrLoadOnSource | 1 | 1 | The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is currently powering the output (load). |
1.3.6.1.4.1.476.1.42.3.5.4.3 | lgpPwrNominalVoltageDeviation | 1 | 1 | The nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input. |
1.3.6.1.4.1.476.1.42.3.5.4.4 | lgpPwrNominalVoltageDeviationPercent | 1 | 1 | The percentage of the nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2In… |
1.3.6.1.4.1.476.1.42.3.5.4.5 | lgpPwrPhaseDifferenceLimit | 1 | 1 | The maximum phase difference (between the well known input sources ) in which a transfer to an available input source is permitte… |
1.3.6.1.4.1.476.1.42.3.5.4.6 | lgpPwrFrequencyDeviationLimit | 1 | 1 | The maximum frequency deviation (between the well known input sources ) in which a transfer to an available input source is permi… |
1.3.6.1.4.1.476.1.42.3.5.4.7 | lgpPwrThresholdTable | 1 | 9 | A list of power thresholds for a given power measurement at a point/location in the system. The lgpPwrThresholdType in this table… |
1.3.6.1.4.1.476.1.42.3.5.4.8 | lgpPwrUpsAutoRestart | 1 | 1 | The device will automatically restart when utility power is restored following a battery discharge. |
1.3.6.1.4.1.476.1.42.3.5.4.9 | lgpPwrUpsAutoRestartDelay | 1 | 1 | The device will automatically delay a certain number of seconds and then restart after utility power is restored following a ba… |
1.3.6.1.4.1.476.1.42.3.5.4.10 | lgpPwrAutoRestartBatteryChargeThreshold | 1 | 1 | The battery charge percentage required before the device can automatically restart. |
1.3.6.1.4.1.476.1.42.3.5.4.11 | lgpPwrParallelModuleCount | 1 | 1 | The number of modules in the parallel system. |
1.3.6.1.4.1.476.1.42.3.5.4.12 | lgpPwrParallelRedundancyCount | 1 | 1 | The number of redundant modules in the parallel system. |
1.3.6.1.4.1.476.1.42.3.5.4.13 | lgpPwrLoadBusSyncMode | 1 | 1 | The configuration of Load Bus Synchronization (LBS) between independent systems. |
1.3.6.1.4.1.476.1.42.3.5.4.14 | lgpPwrEconomicOperationMode | 1 | 1 | The configuration of the economic operation mode of the system. |
1.3.6.1.4.1.476.1.42.3.5.4.15 | lgpPwrAutomaticBatteryTest | 1 | 1 | Automatic battery test option. If enabled, the battery will be tested on a fixed interval. If disabled, the battery test must … |
1.3.6.1.4.1.476.1.42.3.5.4.16 | lgpPwrMinimumRedundantPowerModule | 1 | 1 | The minimum number of redundant power modules that must be present before sending a loss of power redundancy alarm. If 0, there… |
1.3.6.1.4.1.476.1.42.3.5.4.17 | lgpPwrMinimumRedundantBatteryModule | 1 | 1 | The minimum number of redundant battery modules that before enunciating an alarm. If 0, the redundant battery module alarm is … |
1.3.6.1.4.1.476.1.42.3.5.4.18 | lgpPwrOutputToLoadUserOverloadLimit | 1 | 1 | This is the user specified maximum load the device can support without sending an alarm. |
1.3.6.1.4.1.476.1.42.3.5.4.19 | lgpPwrNoLoadWarningLimit | 1 | 1 | The minimum current draw on the output in which the device considers there to be a load present on the output. The condition lgp… |
1.3.6.1.4.1.476.1.42.3.5.4.20 | lgpPwrNoLoadWarningDelay | 1 | 1 | The amount of time to delay before annunciation of the condition lgpConditionNoLoadDetectedWarning after the output current load… |