A list of parameter entries. The number of entries is always
16, and the value of upsParameterTableSize gives the number of valid
entries from the begging of the table. Invalid entries return 0.
To prevent problems with simultaneous queries from several agents,
these values MUST be accessed using several PDUs in the
same SNMP message (
Read sequence:
PDU-SET upsSetStartingAddress
PDU-SET upsParametersRead
PDU-GET upsParameterTableSize
PDU-GET upsParameterValue 1
PDU-GET upsParameterValue 2
..
PDU-GET upsParameterValue
The table is read up to requested number of events and the
management software afterwards decides which entries are
valid, as indicated by the upsParameterTableSize.
Write sequence:
PDU-SET upsSetStartingAddress
PDU-SET upsParameterValue 1
PDU-SET upsParameterValue 2
..
PDU-SET upsParameterValue
PDU-SET upsParametersWrite
Parsed from file GE_PARALLELUPS.mib.txt
Company: ge
Module: GE_PARALLELUPS
Vendor: IMV Victron bv
Module: GE_PARALLELUPS
[Automatically extracted from oidview.com]
upsParameterTable_sixth OBJECT-TYPE SYNTAX SEQUENCE OF UpsParameterEntry_sixth MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (
is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite " ::= { upsGetSet_sixth 11 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.16.10.11.1 | upsParameterEntry_sixth | 2 | 2 | An entry containing information applicable to a particular parameter. |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.16.10.1 | upsEventGetNext_sixth | 1 | 1 | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the reques… |
1.3.6.1.4.1.818.1.1.16.10.2 | upsEventGetPrevious_sixth | 1 | 1 | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the reques… |
1.3.6.1.4.1.818.1.1.16.10.3 | upsEventSetStartingTimeStamp_sixth | 1 | 1 | The timestamp which is used as starting point for downloading events from the UPS event buffer |
1.3.6.1.4.1.818.1.1.16.10.4 | upsEventRetreiveCurrentTimeStamp_sixth | 1 | 1 | The current timestamp is retreived from the UPS |
1.3.6.1.4.1.818.1.1.16.10.5 | upsEventTableSize_sixth | 1 | 1 | The number of entries in the event table. This object indicates the number of rows in the event table. |
1.3.6.1.4.1.818.1.1.16.10.6 | upsEventTable_sixth | 1 | 5 | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid… |
1.3.6.1.4.1.818.1.1.16.10.7 | upsParametersRead_sixth | 1 | 1 | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested n… |
1.3.6.1.4.1.818.1.1.16.10.8 | upsParametersWrite_sixth | 1 | 1 | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsPa… |
1.3.6.1.4.1.818.1.1.16.10.9 | upsParametersStartAddress_sixth | 1 | 1 | The address which is used as starting point for downloading parameters from the UPS |
1.3.6.1.4.1.818.1.1.16.10.10 | upsParameterTableSize_sixth | 1 | 1 | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
1.3.6.1.4.1.818.1.1.16.10.12 | upsStatus_sixth | 1 | 1 | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value ca… |
1.3.6.1.4.1.818.1.1.16.10.13 | upsMainsStatisticsMBfail_sixth | 1 | 1 | Count of main bypass failures (>200 ms), since UPS installation. |
1.3.6.1.4.1.818.1.1.16.10.14 | upsMainsStatisticsMRfail_sixth | 1 | 1 | Count of mains rectifier failures (>200 ms), since UPS installation. |
1.3.6.1.4.1.818.1.1.16.10.15 | upsMainsStatisticsB2_sixth | 1 | 1 | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
1.3.6.1.4.1.818.1.1.16.10.16 | upsMainsStatisticsB5_sixth | 1 | 1 | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
1.3.6.1.4.1.818.1.1.16.10.17 | upsMainsStatisticsB10_sixth | 1 | 1 | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
1.3.6.1.4.1.818.1.1.16.10.18 | upsMainsStatisticsB200_sixth | 1 | 1 | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
1.3.6.1.4.1.818.1.1.16.10.19 | upsMainsStatisticsBypRel_sixth | 1 | 1 | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
1.3.6.1.4.1.818.1.1.16.10.20 | upsTime_sixth | 1 | 1 | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply… |
1.3.6.1.4.1.818.1.1.16.10.21 | upsRequestPermission_sixth | 1 | 1 | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
1.3.6.1.4.1.818.1.1.16.10.22 | upsEventGetCode_sixth | 1 | 1 | The code which is used as starting point to downloading the events from the UPS event buffer. |
1.3.6.1.4.1.818.1.1.16.10.23 | upsEventSpinLock_sixth | 1 | 1 | A spin lock on the event subsystem. |
1.3.6.1.4.1.818.1.1.16.10.24 | upsParameterSpinLock_sixth | 1 | 1 | A spin lock on the parameters subsystem. |