The indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output).(*)
Parsed from file GE_PARALLELUPS.mib.txt
Company: ge
Module: GE_PARALLELUPS
Vendor: IMV Victron bv
Module: GE_PARALLELUPS
[Automatically extracted from oidview.com]
upsBatteryStatus_sixth OBJECT-TYPE SYNTAX Integer32 { unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)" ::= { upsBattery_sixth 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.16.2.1.0 | 0 | 0 | 0 | upsBatteryStatus_sixth |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.16.2.2 | upsSecondsOnBattery_sixth | 1 | 1 | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network man… |
1.3.6.1.4.1.818.1.1.16.2.3 | upsEstimatedMinutesRemaining_sixth | 1 | 1 | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off… |
1.3.6.1.4.1.818.1.1.16.2.4 | upsEstimatedChargeRemaining_sixth | 1 | 1 | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
1.3.6.1.4.1.818.1.1.16.2.5 | upsBatteryVoltage_sixth | 1 | 1 | The magnitude of the present battery voltage.(*) |
1.3.6.1.4.1.818.1.1.16.2.6 | upsBatteryCurrent_sixth | 1 | 1 | The present battery current.(*) |
1.3.6.1.4.1.818.1.1.16.2.7 | upsBatteryTemperature_sixth | 1 | 1 | The ambient temperature at or near the UPS Battery casing.(*) |