Vendor: Tripp Lite
Module: TRIPPUPS1-MIB
[Automatically extracted from oidview.com]
upsConfig OBJECT IDENTIFIER ::= { ups 10 }
upsConfig OBJECT IDENTIFIER ::= { ups 10 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.850.1.1.10.11 | upsConfigInputVoltageHigh | 1 | 1 | If the value of the input voltage (in Volts) exceeds this value, a utilityVoltageHigh trap will be triggered. |
1.3.6.1.4.1.850.1.1.10.12 | upsConfigInputVoltageLow | 1 | 1 | If the value of the input voltage (in Volts) falls below this value, a utilityVoltageLow trap will be triggered. |
1.3.6.1.4.1.850.1.1.10.13 | upsConfigOutputPercLoadHigh | 1 | 1 | If the value of the output percent load exceeds this value, a upsOverload trap will be triggered. |
1.3.6.1.4.1.850.1.1.10.14 | upsConfigBatteryPercLow | 1 | 1 | If the value of the battery percent capacity falls below this value, a lowBattery trap will be triggered. |
1.3.6.1.4.1.850.1.1.10.15 | upsConfigBatteryTemperatureHigh | 1 | 1 | If the value of the battery temperature exceeds this value, a batteryTemperatureHigh trap will be triggered. |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.850.1.1.1 | upsIdent | 6 | 12 | None |
1.3.6.1.4.1.850.1.1.2 | upsBattery | 6 | 16 | None |
1.3.6.1.4.1.850.1.1.3 | upsInput | 5 | 12 | None |
1.3.6.1.4.1.850.1.1.4 | upsOutput | 5 | 15 | None |
1.3.6.1.4.1.850.1.1.6 | upsAlarm | 4 | 11 | None |
1.3.6.1.4.1.850.1.1.7 | upsWellKnownAlarms | 13 | 26 | None |
1.3.6.1.4.1.850.1.1.8 | upsTest | 2 | 4 | None |
1.3.6.1.4.1.850.1.1.9 | upsControl | 5 | 10 | None |