Reference record for OID 1.3.6.1.4.1.850.1.1.9.3


parent
1.3.6.1.4.1.850.1.1.9 (upsControl)
node code
3
node name
upsStartupAfterDelay
dot oid
1.3.6.1.4.1.850.1.1.9.3
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) tripplite(850) trippUPS1(1) ups(1) upsControl(9) upsStartupAfterDelay(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) tripplite(850) trippUPS1(1) ups(1) upsControl(9) upsStartupAfterDelay(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) tripplite(850) trippUPS1(1) ups(1) upsControl(9) upsStartupAfterDelay(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) tripplite(850) trippUPS1(1) ups(1) upsControl(9) upsStartupAfterDelay(3)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) tripplite(850) trippUPS1(1) ups(1) upsControl(9) upsStartupAfterDelay(3)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) tripplite(850) trippUPS1(1) ups(1) upsControl(9) upsStartupAfterDelay(3)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/tripplite/trippUPS1/ups/upsControl/upsStartupAfterDelay
  • /iso/identified-organization/dod/internet/private/enterprises/tripplite/trippUPS1/ups/upsControl/upsStartupAfterDelay
  • /iso/org/dod/internet/private/enterprise/tripplite/trippUPS1/ups/upsControl/upsStartupAfterDelay
  • /iso/org/dod/internet/private/enterprises/tripplite/trippUPS1/ups/upsControl/upsStartupAfterDelay
  • /iso/iso-identified-organization/dod/internet/private/enterprise/tripplite/trippUPS1/ups/upsControl/upsStartupAfterDelay
  • /iso/iso-identified-organization/dod/internet/private/enterprises/tripplite/trippUPS1/ups/upsControl/upsStartupAfterDelay
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/850/1/1/9/3

    Description by mibdepot

    Setting this object will start the output after the
    indicated number of seconds, includeing starting the
    UPS, if necessary. Setting this object to 0 will
    cause the start to occur immediately. Setting this
    object to -1 will abort the countdown. If the output
    is already on at the time the countdown reaches 0,
    nothing will happen. Sets to this object
    override the effect of any upsStartupAfterDelay
    countdown or upsRebootDuration countdown in progress.
    When read, upsStartupAfterDelay will return the number
    of seconds until start, or -1 if no startup
    countdown is in effect. If the countdown expires
    during a utility failure, the startup shall depend
    upon the value of upsAutoRestart at that time. On
    some systems, if the agent is restarted while a
    startup countdown is in effect, the countdown is
    aborted.
    UNITS seconds

    Parsed from file tripplite_ups.mib.txt
    Company: None
    Module: TRIPPUPS1-MIB

    Description by circitor

    Setting this object will start the output after the
    indicated number of seconds, includeing starting the
    UPS, if necessary. Setting this object to 0 will
    cause the start to occur immediately. Setting this
    object to -1 will abort the countdown. If the output
    is already on at the time the countdown reaches 0,
    nothing will happen. Sets to this object
    override the effect of any upsStartupAfterDelay
    countdown or upsRebootDuration countdown in progress.
    When read, upsStartupAfterDelay will return the number
    of seconds until start, or -1 if no startup
    countdown is in effect. If the countdown expires
    during a utility failure, the startup shall depend
    upon the value of upsAutoRestart at that time. On
    some systems, if the agent is restarted while a
    startup countdown is in effect, the countdown is
    aborted.
    UNITS seconds

    Parsed from file TRIPPUPS1-MIB.mib
    Module: TRIPPUPS1-MIB

    Information by oid_info

    Vendor: Tripp Lite
    Module: TRIPPUPS1-MIB

    [Automatically extracted from oidview.com]

    Information by mibdepot

    upsStartupAfterDelay OBJECT-TYPE SYNTAX INTEGER (-1..32767) ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object will start the output after the indicated number of seconds, includeing starting the UPS, if necessary. Setting this object to 0 will cause the start to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until start, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall depend upon the value of upsAutoRestart at that time. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted. UNITS seconds" ::= { upsControl 3 }

    Information by circitor

    upsStartupAfterDelay OBJECT-TYPE SYNTAX INTEGER (-1..32767) ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object will start the output after the indicated number of seconds, includeing starting the UPS, if necessary. Setting this object to 0 will cause the start to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until start, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall depend upon the value of upsAutoRestart at that time. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted. UNITS seconds" ::= { upsControl 3 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.850)

    Markle Lawren

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.850.1.1.9.3.0 upsStartupAfterDelay 0 0 None

    Brothers (4)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.850.1.1.9.1 upsShutdownType 1 1 Setting this object will start the output after the
    indicated number of seconds. Setting this object to 0
    will cause the UPS to …
    1.3.6.1.4.1.850.1.1.9.2 upsShutdownAfterDelay 1 1 Setting this object will shutdown (i.e., turn off)
    either the UPS output or the UPS system (as determined
    by the value of upsShhu…
    1.3.6.1.4.1.850.1.1.9.4 upsRebootDuration 1 1 Setting this object will immediately shutdown (i.e.,
    turn off) either the UPS output or the UPS system (as
    determined by the valu…
    1.3.6.1.4.1.850.1.1.9.5 upsAutoRestart 1 1 Setting this object to 'on' will cause the UPS system
    to restart after a shutdown if/when utility power is present.