Status in source: current.
Names: upsBatteryReplace
Technical details
{
"smi_kind": "NOTIFICATION-TYPE",
"definition": [
"upsBatteryReplace",
"NOTIFICATION-TYPE",
"OBJECTS",
"{",
"trapArg1",
",",
"trapArg2",
"}",
"STATUS",
"current",
"DESCRIPTION",
"\" Model, ConnectStatus Input feed load event. If enabled, this trap is sent when the infeedLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the infeedLoadStatus remains in an error state. If the infeedLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error infeedLoadStatus, and then stops being repeated.\"",
"::=",
"{",
"trap",
"705",
"}"
],
"syntax_tree": [
[
"Objects",
[
"trapArg1",
"trapArg2"
]
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"Model, ConnectStatus Input feed load event. If enabled, this trap is sent when the infeedLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the infeedLoadStatus remains in an error state. If the infeedLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error infeedLoadStatus, and then stops being repeated."
],
null
]
}