OID reference

overCurrentProtectorSensorStateChange

1.3.6.1.4.1.13742.6.0.65

Description

Overcurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 …

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.13742.6.0 (traps)
Node code
65
Node name
overCurrentProtectorSensorStateChange
Category
SNMP notification
Numeric OID
1.3.6.1.4.1.13742.6.0.65
URN notation
urn:oid:1.3.6.1.4.1.13742.6.0.65
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 13742 6 0 65}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) aphel(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) raritan(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) aphel(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) raritan(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) aphel(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) raritan(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) aphel(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) raritan(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) aphel(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) raritan(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) aphel(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) raritan(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) aphel(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) raritan(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) aphel(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) raritan(13742) pdu2(6) traps(0) overCurrentProtectorSensorStateChange(65)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/13742/6/0/65
  • /ISO/Identified-Organization/6/1/4/1/13742/6/0/65
  • /ISO/3/6/1/4/1/13742/6/0/65
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/aphel/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/identified-organization/dod/internet/private/enterprise/raritan/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/identified-organization/dod/internet/private/enterprises/aphel/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/identified-organization/dod/internet/private/enterprises/raritan/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/aphel/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/raritan/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/identified-organization/dod/internet/private/vendor-objects/aphel/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/identified-organization/dod/internet/private/vendor-objects/raritan/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/org/dod/internet/private/enterprise/aphel/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/org/dod/internet/private/enterprise/raritan/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/org/dod/internet/private/enterprises/aphel/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/org/dod/internet/private/enterprises/raritan/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/org/dod/internet/private/ldap-enterprise/aphel/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/org/dod/internet/private/ldap-enterprise/raritan/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/org/dod/internet/private/vendor-objects/aphel/pdu2/traps/overCurrentProtectorSensorStateChange
  • /iso/org/dod/internet/private/vendor-objects/raritan/pdu2/traps/overCurrentProtectorSensorStateChange
  • Additional combinations skipped.

The displayed source records contain one distinct definition. Compare its source records.

overCurrentProtectorSensorStateChange NOTIFICATION-TYPE
    OBJECTS { pduName,
              pduNumber,
              pxInetAddressType,
              pxInetIPAddress,
              agentInetPortNumber,
              overCurrentProtectorLabel,
              typeOfSensor,
              measurementsOverCurrentProtectorSensorTimeStamp,
              measurementsOverCurrentProtectorSensorValue,
              measurementsOverCurrentProtectorSensorState,
              measurementsOverCurrentProtectorSensorSignedValue,
              oldSensorState,
              sysContact,
              sysName,
              sysLocation,
              pduSerialNumber,
              suspectedTripCauseLabel }
    STATUS current
    DESCRIPTION
           "Overcurrent protector sensor state change.
            Which value field to use depends on the metadata of the sensor.
            measurementsOverCurrentProtectorSensorValue is undefined for sensors which can
            have negative readings, measurementsOverCurrentProtectorSensorSignedValue is
            undefined for sensors whose range exceeds the Integer32 range.
            Both fields do not apply to sensors without numerical readings.
            For trip sensor state changes, if a particular outlet is determined to be likely
            to have caused the OCP trip, its label is passed in suspectedTripCauseLabel.

            For an rcmState sensor transitioning to the fail state, the value is the
            residual current just before the sensor transitioned to the fail state."
    ::= { traps 65 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Overcurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For trip sensor state changes, if a particular outlet is determined to be likely to have caused the OCP trip, its label is passed in suspectedTripCauseLabel. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; representative source files are shown for each definition.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 2 sources

Description 1

overCurrentProtectorSensorStateChange · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)2 sources

Status in source: current.

Names: overCurrentProtectorSensorStateChange

Technical details
{
  "smi_kind": "NOTIFICATION-TYPE",
  "definition": [
    "overCurrentProtectorSensorStateChange",
    "NOTIFICATION-TYPE",
    "OBJECTS",
    "{",
    "pduName",
    ",",
    "pduNumber",
    ",",
    "pxInetAddressType",
    ",",
    "pxInetIPAddress",
    ",",
    "agentInetPortNumber",
    ",",
    "overCurrentProtectorLabel",
    ",",
    "typeOfSensor",
    ",",
    "measurementsOverCurrentProtectorSensorTimeStamp",
    ",",
    "measurementsOverCurrentProtectorSensorValue",
    ",",
    "measurementsOverCurrentProtectorSensorState",
    ",",
    "measurementsOverCurrentProtectorSensorSignedValue",
    ",",
    "oldSensorState",
    ",",
    "sysContact",
    ",",
    "sysName",
    ",",
    "sysLocation",
    ",",
    "pduSerialNumber",
    ",",
    "suspectedTripCauseLabel",
    "}",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Overcurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For trip sensor state changes, if a particular outlet is determined to be likely to have caused the OCP trip, its label is passed in suspectedTripCauseLabel. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state.\"",
    "::=",
    "{",
    "traps",
    "65",
    "}"
  ],
  "syntax_tree": [
    [
      "Objects",
      [
        "pduName",
        "pduNumber",
        "pxInetAddressType",
        "pxInetIPAddress",
        "agentInetPortNumber",
        "overCurrentProtectorLabel",
        "typeOfSensor",
        "measurementsOverCurrentProtectorSensorTimeStamp",
        "measurementsOverCurrentProtectorSensorValue",
        "measurementsOverCurrentProtectorSensorState",
        "measurementsOverCurrentProtectorSensorSignedValue",
        "oldSensorState",
        "sysContact",
        "sysName",
        "sysLocation",
        "pduSerialNumber",
        "suspectedTripCauseLabel"
      ]
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Overcurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For trip sensor state changes, if a particular outlet is determined to be likely to have caused the OCP trip, its label is passed in suspectedTripCauseLabel. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state."
    ],
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.13742)

Yang Allen

Siblings (111)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.13742.6.0.90 webcamInserted00
1.3.6.1.4.1.13742.6.0.91 webcamRemoved00
1.3.6.1.4.1.13742.6.0.92 inletEnabled00
1.3.6.1.4.1.13742.6.0.93 inletDisabled00
1.3.6.1.4.1.13742.6.0.94 serverConnectivityUnrecoverable00
1.3.6.1.4.1.13742.6.0.95 radiusError00
1.3.6.1.4.1.13742.6.0.96 serverReachabilityError00
1.3.6.1.4.1.13742.6.0.97 inletSensorReset00
1.3.6.1.4.1.13742.6.0.98 outletSensorReset00
1.3.6.1.4.1.13742.6.0.99 unknownPeripheralDeviceAttached00
1.3.6.1.4.1.13742.6.0.100 peripheralDeviceFirmwareUpdate00
1.3.6.1.4.1.13742.6.0.101 unitSensorReset00
1.3.6.1.4.1.13742.6.0.102 unitSensorStateChange00
1.3.6.1.4.1.13742.6.0.103 circuitSensorStateChange00
1.3.6.1.4.1.13742.6.0.104 circuitPoleSensorStateChange00
1.3.6.1.4.1.13742.6.0.105 circuitAdded00
1.3.6.1.4.1.13742.6.0.106 circuitDeleted00
1.3.6.1.4.1.13742.6.0.107 circuitModified00
1.3.6.1.4.1.13742.6.0.108 circuitSensorReset00
1.3.6.1.4.1.13742.6.0.109 powerMeterAdded00
1.3.6.1.4.1.13742.6.0.110 powerMeterDeleted00
1.3.6.1.4.1.13742.6.0.111 powerMeterModified00
1.3.6.1.4.1.13742.6.0.112 smsMessageTransmissionFailure00
1.3.6.1.4.1.13742.6.0.113 smartCardInserted00
1.3.6.1.4.1.13742.6.0.114 smartCardRemoved00
1.3.6.1.4.1.13742.6.0.115 rawConfigurationDownloaded00
1.3.6.1.4.1.13742.6.0.116 rawConfigurationUpdated00
1.3.6.1.4.1.13742.6.0.117 hwFailureStatusChanged00
1.3.6.1.4.1.13742.6.0.118 outletGroupAdded00
1.3.6.1.4.1.13742.6.0.119 outletGroupModified00
1.3.6.1.4.1.13742.6.0.120 outletGroupDeleted00
1.3.6.1.4.1.13742.6.0.121 outletGroupSensorStateChange00
1.3.6.1.4.1.13742.6.0.122 outletGroupSensorReset00
1.3.6.1.4.1.13742.6.0.123 outletGroupPowerControl00
1.3.6.1.4.1.13742.6.0.124 serverPowerControlInitiated00
1.3.6.1.4.1.13742.6.0.125 serverPowerControlCompleted00
1.3.6.1.4.1.13742.6.0.126 webcamStorageUploadStarted00
1.3.6.1.4.1.13742.6.0.127 testEventTriggered00
1.3.6.1.4.1.13742.6.0.128 actuatorSwitched00
1.3.6.1.4.1.13742.6.0.129 keypadPinEntered00
1.3.6.1.4.1.13742.6.0.130 doorAccessGranted00
1.3.6.1.4.1.13742.6.0.131 doorAccessDenied00
1.3.6.1.4.1.13742.6.0.132 doorAccessRuleAdded00
1.3.6.1.4.1.13742.6.0.133 doorAccessRuleChanged00
1.3.6.1.4.1.13742.6.0.134 doorAccessRuleDeleted00
1.3.6.1.4.1.13742.6.0.135 inletLinePairSensorStateChange00
1.3.6.1.4.1.13742.6.0.136 tacPlusError00
1.3.6.1.4.1.13742.6.0.137 outletSuspended00
1.3.6.1.4.1.13742.6.0.138 userRenamed00
1.3.6.1.4.1.13742.6.0.151 inletDipEvent00