Status in source: current.
Names: overCurrentProtectorPowerSource
Technical details
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"overCurrentProtectorPowerSource",
"OBJECT-TYPE",
"SYNTAX",
"RowPointer",
"MAX-ACCESS",
"read-only",
"STATUS",
"current",
"DESCRIPTION",
"\"This object allows discovery of how the PDU is wired. It indicates the overcurrent protector's power source which can be one of the following: - an inlet - another overcurrent protector - a transfer switch If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet tables. If the power source is an overcurrent protector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfigurationTable. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. If the power source is a transfer switch, it contains the OID of a transferSwitchLabel in the transferSwitchConfigurationTable. The indices of the OID can then be used to reference other objects in the transfer switch tables.\"",
"::=",
"{",
"overCurrentProtectorConfigurationEntry",
"10",
"}"
],
"syntax_tree": [
[
"row",
"RowPointer"
],
null,
[
"MaxAccessPart",
"read-only"
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"This object allows discovery of how the PDU is wired. It indicates the overcurrent protector's power source which can be one of the following: - an inlet - another overcurrent protector - a transfer switch If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet tables. If the power source is an overcurrent protector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfigurationTable. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. If the power source is a transfer switch, it contains the OID of a transferSwitchLabel in the transferSwitchConfigurationTable. The indices of the OID can then be used to reference other objects in the transfer switch tables."
],
null,
null,
null,
null
]
}
- Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
· Publisher's source file: PDU2-MIB
Vendor MIB copy from the LibreNMS archive.
Module: PDU2-MIB
See published definition above
Module imports
{'SNMPv2-TC': ['TEXTUAL-CONVENTION', 'DisplayString', 'MacAddress', 'TruthValue', 'RowPointer'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'NOTIFICATION-TYPE', 'enterprises', 'Integer32', 'Unsigned32', 'IpAddress'], 'RFC1213-MIB': ['sysContact', 'sysName', 'sysLocation'], 'SNMPv2-CONF': ['MODULE-COMPLIANCE', 'OBJECT-GROUP', 'NOTIFICATION-GROUP'], 'INET-ADDRESS-MIB': ['InetAddressType', 'InetAddress', 'InetPortNumber']}
· Download PDU2-MIB
Related source files and packages:
- Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
· Publisher's source file: Source package: observium-community-latest.tar.gz
Vendor MIB copy from the Observium Community archive.
Module: PDU2-MIB
Same published definition
Module imports
{'SNMPv2-TC': ['TEXTUAL-CONVENTION', 'DisplayString', 'MacAddress', 'TruthValue', 'RowPointer'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'NOTIFICATION-TYPE', 'enterprises', 'Integer32', 'Unsigned32', 'IpAddress'], 'RFC1213-MIB': ['sysContact', 'sysName', 'sysLocation'], 'SNMPv2-CONF': ['MODULE-COMPLIANCE', 'OBJECT-GROUP', 'NOTIFICATION-GROUP'], 'INET-ADDRESS-MIB': ['InetAddressType', 'InetAddress', 'InetPortNumber']}
· Download PDU2-MIB