If the midpoint voltage divergence of a battery string is continuously over threshold for this time, the string is deemed faulty.
Sources for this description
Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
OID reference
1.3.6.1.4.1.1918.2.13.10.100.50.40
If the midpoint voltage divergence of a battery string is continuously over threshold for this time, the string is deemed faulty.
Identification
{1 3 6 1 4 1 1918 2 13 10 100 50 40}
Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.
The displayed source records contain one distinct definition. Compare its source records.
string-Fail-Recognition-Period OBJECT-TYPE
SYNTAX TimeIntervalInMinutes
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "If the midpoint voltage divergence of a battery string is continuously over threshold for this time, the string is deemed faulty."
DEFVAL { 60 }
::= { midpoint-Monitoring 40 }
Meaning
Identical descriptions are grouped. Different wording and device-specific notes are retained.
If the midpoint voltage divergence of a battery string is continuously over threshold for this time, the string is deemed faulty.
Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
Evidence
Matching descriptions are grouped; open a group to compare definitions and supporting files.
Status in source: current.
Names: string-Fail-Recognition-Period
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"string-Fail-Recognition-Period",
"OBJECT-TYPE",
"SYNTAX",
"TimeIntervalInMinutes",
"UNITS",
[
"literal",
"226d696e22"
],
"MAX-ACCESS",
"read-write",
"STATUS",
"current",
"DESCRIPTION",
"\"If the midpoint voltage divergence of a battery string is continuously over threshold for this time, the string is deemed faulty.\"",
"DEFVAL",
"{",
"60",
"}",
"::=",
"{",
"midpoint-Monitoring",
"40",
"}"
],
"syntax_tree": [
[
"row",
"TimeIntervalInMinutes"
],
[
"UNITS",
"min"
],
[
"MaxAccessPart",
"read-write"
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"If the midpoint voltage divergence of a battery string is continuously over threshold for this time, the string is deemed faulty."
],
null,
null,
null,
[
"DEFVAL",
60
]
]
}Vendor MIB copy from the LibreNMS archive.
Module: RPS-SC200-MIB
See published definition above
{'RFC-1213': ['DisplayString'], 'SNMPv2-TC': ['TEXTUAL-CONVENTION'], 'SNMPv2-SMI': ['enterprises', 'IpAddress', 'TimeTicks', 'OBJECT-TYPE', 'mib-2', 'MODULE-IDENTITY', 'NOTIFICATION-TYPE', 'OBJECT-IDENTITY', 'Integer32', 'Counter32']}Related source files and packages:
Same file in Observium Community.
Registration
| OID | Name | Direct children | Descendants | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.1918.2.13.10.100.50.20 | mpm-Lockout-Period | 0 | 0 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.30 | mpm-Convergence-Period | 0 | 0 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.50 | mpm-Start-Threshold | 0 | 0 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.60 | mpm-Stable-Threshold | 0 | 0 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.70 | midpoint-Monitoring-String-Table | 1 | 6 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.80 | mpm-State | 0 | 0 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.90 | time-In-This-State | 0 | 0 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.100 | current-MPM-Threshold | 0 | 0 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.105 | reference-Voltage | 0 | 0 | |
| 1.3.6.1.4.1.1918.2.13.10.100.50.110 | clear-String-Fail | 0 | 0 |