OID reference

fast-Charge-Ampere-Hour-Stop-Threshold

1.3.6.1.4.1.1918.2.13.10.70.40.47

Description

Fast charge will only run until the charge removed from the battery falls below this threshold. This mostly useful when fast charge is used to control a generator and the generator should be stopped before the battery has been fully charged. The value given is a percentage of the configured battery capacity. This shou…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.1918.2.13.10.70.40 (fast-Charge)
Node code
47
Node name
fast-Charge-Ampere-Hour-Stop-Threshold
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.1918.2.13.10.70.40.47
URN notation
urn:oid:1.3.6.1.4.1.1918.2.13.10.70.40.47
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 1918 2 13 10 70 40 47}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) eaton-chnz(1918) dc-Power-System(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) eaton-chnz(1918) dcPowerSystem(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) eatonChNz(1918) dc-Power-System(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) eatonChNz(1918) dcPowerSystem(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) eaton-chnz(1918) dc-Power-System(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) eaton-chnz(1918) dcPowerSystem(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) eatonChNz(1918) dc-Power-System(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) eatonChNz(1918) dcPowerSystem(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) eaton-chnz(1918) dc-Power-System(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) eaton-chnz(1918) dcPowerSystem(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) eatonChNz(1918) dc-Power-System(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) eatonChNz(1918) dcPowerSystem(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) eaton-chnz(1918) dc-Power-System(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) eaton-chnz(1918) dcPowerSystem(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) eatonChNz(1918) dc-Power-System(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) eatonChNz(1918) dcPowerSystem(2) rps-SC200(13) rps-Objects(10) control-Functions(70) fast-Charge(40) fast-Charge-Ampere-Hour-Stop-Threshold(47)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/1918/2/13/10/70/40/47
  • /ISO/Identified-Organization/6/1/4/1/1918/2/13/10/70/40/47
  • /ISO/3/6/1/4/1/1918/2/13/10/70/40/47
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/1918/dc-Power-System/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprise/1918/dcPowerSystem/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprise/eaton-chnz/dc-Power-System/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprise/eaton-chnz/dcPowerSystem/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprise/eatonChNz/dc-Power-System/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprise/eatonChNz/dcPowerSystem/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprises/1918/dc-Power-System/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprises/1918/dcPowerSystem/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprises/eaton-chnz/dc-Power-System/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprises/eaton-chnz/dcPowerSystem/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprises/eatonChNz/dc-Power-System/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/enterprises/eatonChNz/dcPowerSystem/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/1918/dc-Power-System/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/1918/dcPowerSystem/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/eaton-chnz/dc-Power-System/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/eaton-chnz/dcPowerSystem/rps-SC200/rps-Objects/control-Functions/fast-Charge/fast-Charge-Ampere-Hour-Stop-Threshold
  • Additional combinations skipped.

SNMP properties

Value type
Unsigned8
Units
%
Maximum access defined by MIB
read-write
Status in MIB
current
Default value
0

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

The displayed source records contain one distinct definition. Compare its source records.

fast-Charge-Ampere-Hour-Stop-Threshold OBJECT-TYPE
  SYNTAX Unsigned8
  UNITS "%"
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Fast charge will only run until the charge removed from the battery falls below this threshold. This mostly useful when fast charge is used to control a generator and the generator should be stopped before the battery has been fully charged. The value given is a percentage of the configured battery capacity. This should normally be set to zero."
  DEFVAL { 0 }
::= { fast-Charge 47 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Fast charge will only run until the charge removed from the battery falls below this threshold. This mostly useful when fast charge is used to control a generator and the generator should be stopped before the battery has been fully charged. The value given is a percentage of the configured battery capacity. This should normally be set to zero.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; open a group to compare definitions and supporting files.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 1

fast-Charge-Ampere-Hour-Stop-Threshold · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: current.

Names: fast-Charge-Ampere-Hour-Stop-Threshold

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "fast-Charge-Ampere-Hour-Stop-Threshold",
    "OBJECT-TYPE",
    "SYNTAX",
    "Unsigned8",
    "UNITS",
    [
      "literal",
      "222522"
    ],
    "MAX-ACCESS",
    "read-write",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Fast charge will only run until the charge removed from the battery falls below this threshold. This mostly useful when fast charge is used to control a generator and the generator should be stopped before the battery has been fully charged. The value given is a percentage of the configured battery capacity. This should normally be set to zero.\"",
    "DEFVAL",
    "{",
    "0",
    "}",
    "::=",
    "{",
    "fast-Charge",
    "47",
    "}"
  ],
  "syntax_tree": [
    [
      "row",
      "Unsigned8"
    ],
    [
      "UNITS",
      "%"
    ],
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Fast charge will only run until the charge removed from the battery falls below this threshold. This mostly useful when fast charge is used to control a generator and the generator should be stopped before the battery has been fully charged. The value given is a percentage of the configured battery capacity. This should normally be set to zero."
    ],
    null,
    null,
    null,
    [
      "DEFVAL",
      0
    ]
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.1918)

Jackson Adrian

Siblings (12)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.1918.2.13.10.70.40.5 enable-Fast-Charge00
1.3.6.1.4.1.1918.2.13.10.70.40.10 fast-Charge-State00
1.3.6.1.4.1.1918.2.13.10.70.40.12 fast-Charge-Start-Allowed00
1.3.6.1.4.1.1918.2.13.10.70.40.15 fast-Charge-Voltage00
1.3.6.1.4.1.1918.2.13.10.70.40.17 fast-Charge-Offset-Voltage00
1.3.6.1.4.1.1918.2.13.10.70.40.20 fast-Charge-Ah-Discharged00
1.3.6.1.4.1.1918.2.13.10.70.40.30 fast-Charge-Maximum-Duration00
1.3.6.1.4.1.1918.2.13.10.70.40.35 fast-Charge-Ampere-Hour-Threshold00
1.3.6.1.4.1.1918.2.13.10.70.40.40 fast-Charge-Voltage-Threshold00
1.3.6.1.4.1.1918.2.13.10.70.40.45 fast-Charge-Recharge-Percentage00
1.3.6.1.4.1.1918.2.13.10.70.40.50 fast-Charge-Maximum-Time-Remaining00
1.3.6.1.4.1.1918.2.13.10.70.40.100 stop-Fast-Charge00