nvramEnvAlert

1.3.6.1.4.1.19746.2.0.6505

Description

Description: The temperature sensor on the NVRAM card or the remote battery detected a temperature that is higher than the warning threshold. If there are other environmental alerts, this may indicate a cooling problem where the system is installed. If there are no other environmental alerts, this may indicate a probl…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.19746.2.0 (dataDomainMibTraps)
Node code
6505
Node name
nvramEnvAlert
Category
SNMP notification
Numeric OID
1.3.6.1.4.1.19746.2.0.6505
URN notation
urn:oid:1.3.6.1.4.1.19746.2.0.6505
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 19746 2 0 6505}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
OID-IRI notation
  • /1/3/6/1/4/1/19746/2/0/6505
  • /ISO/Identified-Organization/6/1/4/1/19746/2/0/6505
  • /ISO/3/6/1/4/1/19746/2/0/6505
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/identified-organization/dod/internet/private/enterprises/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/identified-organization/dod/internet/private/vendor-objects/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/org/dod/internet/private/enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/org/dod/internet/private/enterprises/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/org/dod/internet/private/ldap-enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/org/dod/internet/private/vendor-objects/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-identified-organization/dod/internet/private/enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-identified-organization/dod/internet/private/enterprises/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-identified-organization/dod/internet/private/ldap-enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-identified-organization/dod/internet/private/vendor-objects/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-organization/dod/internet/private/enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-organization/dod/internet/private/enterprises/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-organization/dod/internet/private/ldap-enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-organization/dod/internet/private/vendor-objects/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert

The displayed source records contain one distinct definition. Compare its source records.

nvramEnvAlert NOTIFICATION-TYPE
   OBJECTS { systemSerialNumber, alertInfoDescription }
STATUS current
   DESCRIPTION
   "Description: 
	The temperature sensor on the NVRAM card or the remote battery detected a temperature 
        that is higher than the warning threshold.  If there are other environmental alerts, 
        this may indicate a cooling problem where the system is installed.  
        If there are no other environmental alerts, this may indicate a problem with this component.  
        When the temperature is reduced, this alert will clear.
    
   Action: 
        Check cooling and airflow around the system unit.  Remove any blockage, or ensure 
        the environmental systems are operating correctly, and the environment is at a normal 
        temperature.  If there is no problem in the environment, or if only the NVRAM or 
        remote battery are reporting this problem, contact your contracted support provider or visit us online at https://support.emc.com.
    "
::= { dataDomainMibTraps 6505 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Description: The temperature sensor on the NVRAM card or the remote battery detected a temperature that is higher than the warning threshold. If there are other environmental alerts, this may indicate a cooling problem where the system is installed. If there are no other environmental alerts, this may indicate a problem with this component. When the temperature is reduced, this alert will clear. Action: Check cooling and airflow around the system unit. Remove any blockage, or ensure the environmental systems are operating correctly, and the environment is at a normal temperature. If there is no problem in the environment, or if only the NVRAM or remote battery are reporting this problem, contact your contracted support provider or visit us online at https://support.emc.com.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; representative source files are shown for each definition.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 2 sources

Description 1

nvramEnvAlert · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)2 sources

Status in source: current.

Names: nvramEnvAlert

Technical details
{
  "smi_kind": "NOTIFICATION-TYPE",
  "definition": [
    "nvramEnvAlert",
    "NOTIFICATION-TYPE",
    "OBJECTS",
    "{",
    "systemSerialNumber",
    ",",
    "alertInfoDescription",
    "}",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Description: The temperature sensor on the NVRAM card or the remote battery detected a temperature that is higher than the warning threshold. If there are other environmental alerts, this may indicate a cooling problem where the system is installed. If there are no other environmental alerts, this may indicate a problem with this component. When the temperature is reduced, this alert will clear. Action: Check cooling and airflow around the system unit. Remove any blockage, or ensure the environmental systems are operating correctly, and the environment is at a normal temperature. If there is no problem in the environment, or if only the NVRAM or remote battery are reporting this problem, contact your contracted support provider or visit us online at https://support.emc.com. \"",
    "::=",
    "{",
    "dataDomainMibTraps",
    "6505",
    "}"
  ],
  "syntax_tree": [
    [
      "Objects",
      [
        "systemSerialNumber",
        "alertInfoDescription"
      ]
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Description: The temperature sensor on the NVRAM card or the remote battery detected a temperature that is higher than the warning threshold. If there are other environmental alerts, this may indicate a cooling problem where the system is installed. If there are no other environmental alerts, this may indicate a problem with this component. When the temperature is reduced, this alert will clear. Action: Check cooling and airflow around the system unit. Remove any blockage, or ensure the environmental systems are operating correctly, and the environment is at a normal temperature. If there is no problem in the environment, or if only the NVRAM or remote battery are reporting this problem, contact your contracted support provider or visit us online at https://support.emc.com."
    ],
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.19746)

Haile J. Mitchell

Siblings (246)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.19746.2.0.5018 unCorrectECCWarning00
1.3.6.1.4.1.19746.2.0.5020 chassisSensorCritical00
1.3.6.1.4.1.19746.2.0.5021 chassisTempWarning00
1.3.6.1.4.1.19746.2.0.5022 chassisTempCritical00
1.3.6.1.4.1.19746.2.0.5023 cPUFailureWarning00
1.3.6.1.4.1.19746.2.0.5024 legacyBMCHangCritical00
1.3.6.1.4.1.19746.2.0.5025 bMCHangCritical00
1.3.6.1.4.1.19746.2.0.5026 abnormalShutdown00
1.3.6.1.4.1.19746.2.0.5027 tooManyRelaunches00
1.3.6.1.4.1.19746.2.0.5028 filesystemProblem00
1.3.6.1.4.1.19746.2.0.5030 dDFSFailedInShutdown00
1.3.6.1.4.1.19746.2.0.5034 dDFSNoHeartbeat00
1.3.6.1.4.1.19746.2.0.5036 dDFSDiedAfterReboot00
1.3.6.1.4.1.19746.2.0.5037 dDFSDied00
1.3.6.1.4.1.19746.2.0.5038 dDFSRebooted00
1.3.6.1.4.1.19746.2.0.5039 dDFSRebootedDisabled00
1.3.6.1.4.1.19746.2.0.5040 indexRebuildComplete00
1.3.6.1.4.1.19746.2.0.5041 historicalDatabaseRecoverError00
1.3.6.1.4.1.19746.2.0.5042 historicalDatabaseBackupError00
1.3.6.1.4.1.19746.2.0.5043 historicalDatabaseUpgradeError00
1.3.6.1.4.1.19746.2.0.5044 historicalDatabasePruneError00
1.3.6.1.4.1.19746.2.0.5045 noHistoricalDatabaseError00
1.3.6.1.4.1.19746.2.0.5046 hDTFileTransferFailed00
1.3.6.1.4.1.19746.2.0.5047 hDTSystemError00
1.3.6.1.4.1.19746.2.0.5048 dIMMFailureAlert00
1.3.6.1.4.1.19746.2.0.5049 memoryAlert00
1.3.6.1.4.1.19746.2.0.5050 portPathDisabled00
1.3.6.1.4.1.19746.2.0.5051 diskPathRedundancy00
1.3.6.1.4.1.19746.2.0.5052 missingPortConnection00
1.3.6.1.4.1.19746.2.0.5053 missingLunPath00
1.3.6.1.4.1.19746.2.0.5054 missingDiskPath00
1.3.6.1.4.1.19746.2.0.5055 missingEnclosurePath00
1.3.6.1.4.1.19746.2.0.5059 nvramWarning00
1.3.6.1.4.1.19746.2.0.5060 nvramBatteryAlert00
1.3.6.1.4.1.19746.2.0.5061 nvramErrorAlert00
1.3.6.1.4.1.19746.2.0.5062 phyalert00
1.3.6.1.4.1.19746.2.0.5063 replProgressThreshholdReached00
1.3.6.1.4.1.19746.2.0.5064 replNeedResync00
1.3.6.1.4.1.19746.2.0.5065 replLogFull00
1.3.6.1.4.1.19746.2.0.5066 replIncompatibleWorm00
1.3.6.1.4.1.19746.2.0.5067 replDestNotConfigured00
1.3.6.1.4.1.19746.2.0.5068 replLagThreshholdReached00
1.3.6.1.4.1.19746.2.0.5069 sASEnclosureCheck00
1.3.6.1.4.1.19746.2.0.5070 sASTopologyCheck00
1.3.6.1.4.1.19746.2.0.5071 sASPortDisabled00
1.3.6.1.4.1.19746.2.0.5072 sSLCertificateCorrupted00
1.3.6.1.4.1.19746.2.0.5075 snapshotOver90Percent00
1.3.6.1.4.1.19746.2.0.5076 snapshotLimitReached00
1.3.6.1.4.1.19746.2.0.5077 sNTZMultipleIterations00
1.3.6.1.4.1.19746.2.0.5078 coredumpWarning00