Description 1
PDU Breaker Current (Peak) reading in hundreths of an amp
Sources for this description
Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
OID reference
1.3.6.1.4.1.21239.5.2.3.3.1.7
PDU Breaker Current (Peak) reading in hundreths of an amp
Identification
{1 3 6 1 4 1 21239 5 2 3 3 1 7}
Definitions may combine these properties differently.
At least one MIB declaration places this object in a table row. A value belongs to a row instance; its suffix depends on the row's INDEX or AUGMENTS definition.
In VERTIV-IMD-MIB, the row index pduBreakerIndex is declared as Integer32. A non-negative index value is encoded as one numeric subidentifier. An instance has the form .1.3.6.1.4.1.21239.5.2.3.3.1.7.<pduBreakerIndex>. Use an index value actually present on the device and permitted by its MIB. Other definitions can differ.
snmpwalk [connection options] DEVICE .1.3.6.1.4.1.21239.5.2.3.3.1.7
Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.
Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.
Available source records contain 2 distinct definitions; some records may not include a definition.
pduBreakerCurrentPeak OBJECT-TYPE
SYNTAX Gauge32
UNITS "centiamps (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "PDU Breaker Current (Peak) reading in hundreths of an amp"
::= { pduBreakerEntry 7 }pduBreakerCurrentPeak OBJECT-TYPE
SYNTAX Gauge32(0..15000)
UNITS "centiamps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Highest instantaneous current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences."
::= { pduBreakerEntry 7 }
Meaning
Identical descriptions are grouped. Different wording and device-specific notes are retained.
Description 1
PDU Breaker Current (Peak) reading in hundreths of an amp
Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
Description 2
Highest instantaneous current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences.
Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
Evidence
Matching descriptions are grouped; open a group to compare definitions and supporting files.
Status in source: current.
Names: pduBreakerCurrentPeak
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"pduBreakerCurrentPeak",
"OBJECT-TYPE",
"SYNTAX",
"Gauge32",
"UNITS",
[
"literal",
"2263656e7469616d70732028726d732922"
],
"MAX-ACCESS",
"read-only",
"STATUS",
"current",
"DESCRIPTION",
"\"PDU Breaker Current (Peak) reading in hundreths of an amp\"",
"::=",
"{",
"pduBreakerEntry",
"7",
"}"
],
"syntax_tree": [
[
"ApplicationSyntax",
"Gauge32"
],
[
"UNITS",
"centiamps (rms)"
],
[
"MaxAccessPart",
"read-only"
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"PDU Breaker Current (Peak) reading in hundreths of an amp"
],
null,
null,
null,
null
]
}Vendor MIB copy from the Observium Community archive.
Module: GEIST-IMD-MIB
See published definition above
{'SNMPv2-TC': ['DisplayString'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'IpAddress', 'enterprises', 'Integer32', 'Gauge32', 'NOTIFICATION-TYPE']}Related source files and packages:
Status in source: current.
Names: pduBreakerCurrentPeak
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"pduBreakerCurrentPeak",
"OBJECT-TYPE",
"SYNTAX",
"Gauge32",
"(",
"0",
".",
".",
"15000",
")",
"UNITS",
[
"literal",
"2263656e7469616d707322"
],
"MAX-ACCESS",
"read-only",
"STATUS",
"current",
"DESCRIPTION",
"\"Highest instantaneous current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences.\"",
"::=",
"{",
"pduBreakerEntry",
"7",
"}"
],
"syntax_tree": [
[
"ApplicationSyntax",
"Gauge32",
[
"integerSubType",
[
[
0,
15000
]
]
]
],
[
"UNITS",
"centiamps"
],
[
"MaxAccessPart",
"read-only"
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"Highest instantaneous current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences."
],
null,
null,
null,
null
]
}Vendor MIB copy from the Observium Community archive.
Module: VERTIV-IMD-MIB
See published definition above
{'SNMPv2-TC': ['DisplayString'], 'SNMPv2-MIB': ['sysName'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'OBJECT-IDENTITY', 'enterprises', 'Integer32', 'Gauge32', 'NOTIFICATION-TYPE'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}Registration
| OID | Name | Direct children | Descendants | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.21239.5.2.3.3.1.1 | pduBreakerIndex | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.2 | pduBreakerName | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.3 | pduBreakerLabel | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.4 | pduBreakerCurrent | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.5 | pduBreakerCurrentMax | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.6 | pduBreakerCurrentMin | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.8 | pduBreakerVoltage | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.12 | pduBreakerRealPower | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.13 | pduBreakerApparentPower | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.14 | pduBreakerPowerFactor | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.15 | pduBreakerEnergy | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.20 | pduBreakerResCurrentDetected | 0 | 0 | |
| 1.3.6.1.4.1.21239.5.2.3.3.1.21 | pduBreakerLossOfLoadDetected | 0 | 0 |