OID reference

trapEventTypeNumber

1.3.6.1.4.1.3052.18.3.4

Description

The user-defined trap variable for the type of event that happened. Definitions: 4 Scheduled 7 Serial Handshaking Low 8 Serial Handshaking High 10 Contact Closure Active 11 Contact Closure Inactive 12 Temperature High 13 Temperature Very High 14 Temperature Low 15 Temperature Very Low 16 Temperature Return to Normal 1…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.3052.18.3 (productIds)
Node code
4
Node name
trapEventTypeNumber
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.3052.18.3.4
URN notation
urn:oid:1.3.6.1.4.1.3052.18.3.4
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 3052 18 3 4}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) asentria(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) omnitronix(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) asentria(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) omnitronix(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) asentria(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) omnitronix(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) asentria(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) omnitronix(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) asentria(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) omnitronix(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) asentria(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) omnitronix(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) asentria(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) omnitronix(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) asentria(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) omnitronix(3052) s350(18) productIds(3) trapEventTypeNumber(4)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/3052/18/3/4
  • /ISO/Identified-Organization/6/1/4/1/3052/18/3/4
  • /ISO/3/6/1/4/1/3052/18/3/4
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/asentria/s350/productIds/trapEventTypeNumber
  • /iso/identified-organization/dod/internet/private/enterprise/omnitronix/s350/productIds/trapEventTypeNumber
  • /iso/identified-organization/dod/internet/private/enterprises/asentria/s350/productIds/trapEventTypeNumber
  • /iso/identified-organization/dod/internet/private/enterprises/omnitronix/s350/productIds/trapEventTypeNumber
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/asentria/s350/productIds/trapEventTypeNumber
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/omnitronix/s350/productIds/trapEventTypeNumber
  • /iso/identified-organization/dod/internet/private/vendor-objects/asentria/s350/productIds/trapEventTypeNumber
  • /iso/identified-organization/dod/internet/private/vendor-objects/omnitronix/s350/productIds/trapEventTypeNumber
  • /iso/org/dod/internet/private/enterprise/asentria/s350/productIds/trapEventTypeNumber
  • /iso/org/dod/internet/private/enterprise/omnitronix/s350/productIds/trapEventTypeNumber
  • /iso/org/dod/internet/private/enterprises/asentria/s350/productIds/trapEventTypeNumber
  • /iso/org/dod/internet/private/enterprises/omnitronix/s350/productIds/trapEventTypeNumber
  • /iso/org/dod/internet/private/ldap-enterprise/asentria/s350/productIds/trapEventTypeNumber
  • /iso/org/dod/internet/private/ldap-enterprise/omnitronix/s350/productIds/trapEventTypeNumber
  • /iso/org/dod/internet/private/vendor-objects/asentria/s350/productIds/trapEventTypeNumber
  • /iso/org/dod/internet/private/vendor-objects/omnitronix/s350/productIds/trapEventTypeNumber
  • Additional combinations skipped.

SNMP properties

Value type
Integer32
Maximum access defined by MIB
read-only
Status in MIB
current

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.3052.18.3.4.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

The displayed source records contain one distinct definition. Compare its source records.

trapEventTypeNumber OBJECT-TYPE
    SYNTAX Integer32
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "The user-defined trap variable for the type of
        event that happened.  Definitions:
           4    Scheduled
           7    Serial Handshaking Low
           8    Serial Handshaking High
           10   Contact Closure Active
           11   Contact Closure Inactive
           12   Temperature High
           13   Temperature Very High
           14   Temperature Low
           15   Temperature Very Low
           16   Temperature Return to Normal
           17   Humidity High
           18   Humidity Very High
           19   Humidity Low
           20   Humidity Very Low
           21   Humidity Return to Normal
           26   Analog High
           27   Analog Very High
           28   Analog Low
           29   Analog Very Low
           30   Analog Normal
           40   EventSensor Unresponsive
           41   Custom
           42   CPE Down
           44   CPE Normal
           49   Fuel Sensor Disconnect
           50   Fuel Sensor Disconnect Return to Normal
           56   Fuel Sensor
           57   AC Power Monitor Average Voltage Very Low
           58   AC Power Monitor Average Voltage Low
           59   AC Power Monitor Average Voltage Return to Normal
           60   AC Power Monitor Average Voltage High
           61   AC Power Monitor Average Voltage Very High
           62   AC Power Monitor Average Current Very Low
           63   AC Power Monitor Average Current Low
           64   AC Power Monitor Average Current Return to Normal
           65   AC Power Monitor Average Current High
           66   AC Power Monitor Average Current Very High
           67   AC Power Monitor Frequency Very Low
           68   AC Power Monitor Frequency Low
           69   AC Power Monitor Frequency Return to Normal
           70   AC Power Monitor Frequency High
           71   AC Power Monitor Frequency Very High
           72   AC Power Monitor Total Real Power Very Low
           73   AC Power Monitor Total Real Power Low
           74   AC Power Monitor Total Real Power Return to Normal
           75   AC Power Monitor Total Real Power High
           76   AC Power Monitor Total Real Power Very High
           77   AC Power Monitor Disconnect
           78   AC Power Monitor Disconnect Return to Normal
           81   Fuel Sensor Volume Sudden Change
           82   Fuel Sensor Volume Slow Change
           83   CPE Down Reminder
           84   AC Power Monitor Total Power Factor Very Low
           85   AC Power Monitor Total Power Factor Low
           86   AC Power Monitor Total Power Factor Return to Normal
           100  Contact Closure Active Reminder
           101  Temperature High Reminder
           102  Temperature High Very Reminder
           103  Temperature Low Reminder
           104  Temperature Very Low Reminder
           105  Humidity High Reminder
           106  Humidity Very High Reminder
           107  Humidity Low Reminder
           108  Humidity Very Low Reminder
           109  Analog High Reminder
           110  Analog Very High Reminder
           111  Analog Low Reminder
           112  Analog Very Low Reminder
           130  Relay Output Active
           131  Relay Output Inactive
           132  Power Output On
           133  Power Output Off
           134  Battery Monitor Temperature High
           135  Battery Monitor Temperature Return to Normal
           136  Battery Monitor Temperature Low
           137  Battery Monitor Differential Temperature High
           138  Battery Monitor Differential Temperature Return to Normal
           139  Battery Monitor Differential Temperature Low
           140  Battery Monitor Voltage Very High
           141  Battery Monitor Voltage High
           142  Battery Monitor Voltage Return to Normal
           143  Battery Monitor Voltage Low
           144  Battery Monitor Voltage Very Low
           145  Battery Monitor Differential Voltage Very High
           146  Battery Monitor Differential Voltage High
           147  Battery Monitor Differential Voltage Return to Normal
           148  Battery Monitor Charge Level Return to Normal
           149  Battery Monitor Charge Level Low
           150  Battery Monitor Charge Level Very Low
           151  Battery Monitor Health Return to Normal
           152  Battery Monitor Health Low
           153  Battery Monitor Health Very Low
           154  Battery Monitor Charge Current Very High
           155  Battery Monitor Charge Current High
           156  Battery Monitor Charge Current Return to Normal
           157  Battery Monitor Discharge Current Very High
           158  Battery Monitor Discharge Current High
           159  Battery Monitor Discharge Return to Normal
           160  Generator Failed to Start
           162  Location Fix Failure
           163  Location Fix Success
           164  Reset
           165  Sleep
           166  Fuel Sensor Levels Auto Adjust
           "
    ::= { productIds 4 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

The user-defined trap variable for the type of event that happened. Definitions: 4 Scheduled 7 Serial Handshaking Low 8 Serial Handshaking High 10 Contact Closure Active 11 Contact Closure Inactive 12 Temperature High 13 Temperature Very High 14 Temperature Low 15 Temperature Very Low 16 Temperature Return to Normal 17 Humidity High 18 Humidity Very High 19 Humidity Low 20 Humidity Very Low 21 Humidity Return to Normal 26 Analog High 27 Analog Very High 28 Analog Low 29 Analog Very Low 30 Analog Normal 40 EventSensor Unresponsive 41 Custom 42 CPE Down 44 CPE Normal 49 Fuel Sensor Disconnect 50 Fuel Sensor Disconnect Return to Normal 56 Fuel Sensor 57 AC Power Monitor Average Voltage Very Low 58 AC Power Monitor Average Voltage Low 59 AC Power Monitor Average Voltage Return to Normal 60 AC Power Monitor Average Voltage High 61 AC Power Monitor Average Voltage Very High 62 AC Power Monitor Average Current Very Low 63 AC Power Monitor Average Current Low 64 AC Power Monitor Average Current Return to Normal 65 AC Power Monitor Average Current High 66 AC Power Monitor Average Current Very High 67 AC Power Monitor Frequency Very Low 68 AC Power Monitor Frequency Low 69 AC Power Monitor Frequency Return to Normal 70 AC Power Monitor Frequency High 71 AC Power Monitor Frequency Very High 72 AC Power Monitor Total Real Power Very Low 73 AC Power Monitor Total Real Power Low 74 AC Power Monitor Total Real Power Return to Normal 75 AC Power Monitor Total Real Power High 76 AC Power Monitor Total Real Power Very High 77 AC Power Monitor Disconnect 78 AC Power Monitor Disconnect Return to Normal 81 Fuel Sensor Volume Sudden Change 82 Fuel Sensor Volume Slow Change 83 CPE Down Reminder 84 AC Power Monitor Total Power Factor Very Low 85 AC Power Monitor Total Power Factor Low 86 AC Power Monitor Total Power Factor Return to Normal 100 Contact Closure Active Reminder 101 Temperature High Reminder 102 Temperature High Very Reminder 103 Temperature Low Reminder 104 Temperature Very Low Reminder 105 Humidity High Reminder 106 Humidity Very High Reminder 107 Humidity Low Reminder 108 Humidity Very Low Reminder 109 Analog High Reminder 110 Analog Very High Reminder 111 Analog Low Reminder 112 Analog Very Low Reminder 130 Relay Output Active 131 Relay Output Inactive 132 Power Output On 133 Power Output Off 134 Battery Monitor Temperature High 135 Battery Monitor Temperature Return to Normal 136 Battery Monitor Temperature Low 137 Battery Monitor Differential Temperature High 138 Battery Monitor Differential Temperature Return to Normal 139 Battery Monitor Differential Temperature Low 140 Battery Monitor Voltage Very High 141 Battery Monitor Voltage High 142 Battery Monitor Voltage Return to Normal 143 Battery Monitor Voltage Low 144 Battery Monitor Voltage Very Low 145 Battery Monitor Differential Voltage Very High 146 Battery Monitor Differential Voltage High 147 Battery Monitor Differential Voltage Return to Normal 148 Battery Monitor Charge Level Return to Normal 149 Battery Monitor Charge Level Low 150 Battery Monitor Charge Level Very Low 151 Battery Monitor Health Return to Normal 152 Battery Monitor Health Low 153 Battery Monitor Health Very Low 154 Battery Monitor Charge Current Very High 155 Battery Monitor Charge Current High 156 Battery Monitor Charge Current Return to Normal 157 Battery Monitor Discharge Current Very High 158 Battery Monitor Discharge Current High 159 Battery Monitor Discharge Return to Normal 160 Generator Failed to Start 162 Location Fix Failure 163 Location Fix Success 164 Reset 165 Sleep 166 Fuel Sensor Levels Auto Adjust

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; open a group to compare definitions and supporting files.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 1

trapEventTypeNumber · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: current.

Names: trapEventTypeNumber

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "trapEventTypeNumber",
    "OBJECT-TYPE",
    "SYNTAX",
    "Integer32",
    "MAX-ACCESS",
    "read-only",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"The user-defined trap variable for the type of event that happened. Definitions: 4 Scheduled 7 Serial Handshaking Low 8 Serial Handshaking High 10 Contact Closure Active 11 Contact Closure Inactive 12 Temperature High 13 Temperature Very High 14 Temperature Low 15 Temperature Very Low 16 Temperature Return to Normal 17 Humidity High 18 Humidity Very High 19 Humidity Low 20 Humidity Very Low 21 Humidity Return to Normal 26 Analog High 27 Analog Very High 28 Analog Low 29 Analog Very Low 30 Analog Normal 40 EventSensor Unresponsive 41 Custom 42 CPE Down 44 CPE Normal 49 Fuel Sensor Disconnect 50 Fuel Sensor Disconnect Return to Normal 56 Fuel Sensor 57 AC Power Monitor Average Voltage Very Low 58 AC Power Monitor Average Voltage Low 59 AC Power Monitor Average Voltage Return to Normal 60 AC Power Monitor Average Voltage High 61 AC Power Monitor Average Voltage Very High 62 AC Power Monitor Average Current Very Low 63 AC Power Monitor Average Current Low 64 AC Power Monitor Average Current Return to Normal 65 AC Power Monitor Average Current High 66 AC Power Monitor Average Current Very High 67 AC Power Monitor Frequency Very Low 68 AC Power Monitor Frequency Low 69 AC Power Monitor Frequency Return to Normal 70 AC Power Monitor Frequency High 71 AC Power Monitor Frequency Very High 72 AC Power Monitor Total Real Power Very Low 73 AC Power Monitor Total Real Power Low 74 AC Power Monitor Total Real Power Return to Normal 75 AC Power Monitor Total Real Power High 76 AC Power Monitor Total Real Power Very High 77 AC Power Monitor Disconnect 78 AC Power Monitor Disconnect Return to Normal 81 Fuel Sensor Volume Sudden Change 82 Fuel Sensor Volume Slow Change 83 CPE Down Reminder 84 AC Power Monitor Total Power Factor Very Low 85 AC Power Monitor Total Power Factor Low 86 AC Power Monitor Total Power Factor Return to Normal 100 Contact Closure Active Reminder 101 Temperature High Reminder 102 Temperature High Very Reminder 103 Temperature Low Reminder 104 Temperature Very Low Reminder 105 Humidity High Reminder 106 Humidity Very High Reminder 107 Humidity Low Reminder 108 Humidity Very Low Reminder 109 Analog High Reminder 110 Analog Very High Reminder 111 Analog Low Reminder 112 Analog Very Low Reminder 130 Relay Output Active 131 Relay Output Inactive 132 Power Output On 133 Power Output Off 134 Battery Monitor Temperature High 135 Battery Monitor Temperature Return to Normal 136 Battery Monitor Temperature Low 137 Battery Monitor Differential Temperature High 138 Battery Monitor Differential Temperature Return to Normal 139 Battery Monitor Differential Temperature Low 140 Battery Monitor Voltage Very High 141 Battery Monitor Voltage High 142 Battery Monitor Voltage Return to Normal 143 Battery Monitor Voltage Low 144 Battery Monitor Voltage Very Low 145 Battery Monitor Differential Voltage Very High 146 Battery Monitor Differential Voltage High 147 Battery Monitor Differential Voltage Return to Normal 148 Battery Monitor Charge Level Return to Normal 149 Battery Monitor Charge Level Low 150 Battery Monitor Charge Level Very Low 151 Battery Monitor Health Return to Normal 152 Battery Monitor Health Low 153 Battery Monitor Health Very Low 154 Battery Monitor Charge Current Very High 155 Battery Monitor Charge Current High 156 Battery Monitor Charge Current Return to Normal 157 Battery Monitor Discharge Current Very High 158 Battery Monitor Discharge Current High 159 Battery Monitor Discharge Return to Normal 160 Generator Failed to Start 162 Location Fix Failure 163 Location Fix Success 164 Reset 165 Sleep 166 Fuel Sensor Levels Auto Adjust \"",
    "::=",
    "{",
    "productIds",
    "4",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "Integer32"
    ],
    null,
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "The user-defined trap variable for the type of event that happened. Definitions: 4 Scheduled 7 Serial Handshaking Low 8 Serial Handshaking High 10 Contact Closure Active 11 Contact Closure Inactive 12 Temperature High 13 Temperature Very High 14 Temperature Low 15 Temperature Very Low 16 Temperature Return to Normal 17 Humidity High 18 Humidity Very High 19 Humidity Low 20 Humidity Very Low 21 Humidity Return to Normal 26 Analog High 27 Analog Very High 28 Analog Low 29 Analog Very Low 30 Analog Normal 40 EventSensor Unresponsive 41 Custom 42 CPE Down 44 CPE Normal 49 Fuel Sensor Disconnect 50 Fuel Sensor Disconnect Return to Normal 56 Fuel Sensor 57 AC Power Monitor Average Voltage Very Low 58 AC Power Monitor Average Voltage Low 59 AC Power Monitor Average Voltage Return to Normal 60 AC Power Monitor Average Voltage High 61 AC Power Monitor Average Voltage Very High 62 AC Power Monitor Average Current Very Low 63 AC Power Monitor Average Current Low 64 AC Power Monitor Average Current Return to Normal 65 AC Power Monitor Average Current High 66 AC Power Monitor Average Current Very High 67 AC Power Monitor Frequency Very Low 68 AC Power Monitor Frequency Low 69 AC Power Monitor Frequency Return to Normal 70 AC Power Monitor Frequency High 71 AC Power Monitor Frequency Very High 72 AC Power Monitor Total Real Power Very Low 73 AC Power Monitor Total Real Power Low 74 AC Power Monitor Total Real Power Return to Normal 75 AC Power Monitor Total Real Power High 76 AC Power Monitor Total Real Power Very High 77 AC Power Monitor Disconnect 78 AC Power Monitor Disconnect Return to Normal 81 Fuel Sensor Volume Sudden Change 82 Fuel Sensor Volume Slow Change 83 CPE Down Reminder 84 AC Power Monitor Total Power Factor Very Low 85 AC Power Monitor Total Power Factor Low 86 AC Power Monitor Total Power Factor Return to Normal 100 Contact Closure Active Reminder 101 Temperature High Reminder 102 Temperature High Very Reminder 103 Temperature Low Reminder 104 Temperature Very Low Reminder 105 Humidity High Reminder 106 Humidity Very High Reminder 107 Humidity Low Reminder 108 Humidity Very Low Reminder 109 Analog High Reminder 110 Analog Very High Reminder 111 Analog Low Reminder 112 Analog Very Low Reminder 130 Relay Output Active 131 Relay Output Inactive 132 Power Output On 133 Power Output Off 134 Battery Monitor Temperature High 135 Battery Monitor Temperature Return to Normal 136 Battery Monitor Temperature Low 137 Battery Monitor Differential Temperature High 138 Battery Monitor Differential Temperature Return to Normal 139 Battery Monitor Differential Temperature Low 140 Battery Monitor Voltage Very High 141 Battery Monitor Voltage High 142 Battery Monitor Voltage Return to Normal 143 Battery Monitor Voltage Low 144 Battery Monitor Voltage Very Low 145 Battery Monitor Differential Voltage Very High 146 Battery Monitor Differential Voltage High 147 Battery Monitor Differential Voltage Return to Normal 148 Battery Monitor Charge Level Return to Normal 149 Battery Monitor Charge Level Low 150 Battery Monitor Charge Level Very Low 151 Battery Monitor Health Return to Normal 152 Battery Monitor Health Low 153 Battery Monitor Health Very Low 154 Battery Monitor Charge Current Very High 155 Battery Monitor Charge Current High 156 Battery Monitor Charge Current Return to Normal 157 Battery Monitor Discharge Current Very High 158 Battery Monitor Discharge Current High 159 Battery Monitor Discharge Return to Normal 160 Generator Failed to Start 162 Location Fix Failure 163 Location Fix Success 164 Reset 165 Sleep 166 Fuel Sensor Levels Auto Adjust"
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.3052)

Renton Paul

Siblings (9)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.3052.18.3.1 siteName00
1.3.6.1.4.1.3052.18.3.2 thisProduct00
1.3.6.1.4.1.3052.18.3.3 stockTrapString00
1.3.6.1.4.1.3052.18.3.5 trapEventTypeName00
1.3.6.1.4.1.3052.18.3.6 trapIncludedValue00
1.3.6.1.4.1.3052.18.3.7 trapIncludedString00
1.3.6.1.4.1.3052.18.3.8 trapTypeString00
1.3.6.1.4.1.3052.18.3.9 trapEventClassNumber00
1.3.6.1.4.1.3052.18.3.10 trapEventClassName00