Status in source: mandatory.
Names: pmmInputPhaseLoss
Technical details
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"pmmInputPhaseLoss",
"OBJECT-TYPE",
"SYNTAX",
"INTEGER",
"ACCESS",
"read-write",
"STATUS",
"mandatory",
"DESCRIPTION",
"\"Threshold below which an input phase loss condition will be generated. Specified as a percent deviation from phase to neutral nominal voltage. A value of zero indicates that the threshold is disabled. Returns -1 if unsupported or failed. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value\"",
"::=",
"{",
"pmmInputEntry",
"35",
"}"
],
"syntax_tree": [
[
"SimpleSyntax",
"INTEGER"
],
null,
[
"MaxAccessPart",
"read-write"
],
[
"Status",
"mandatory"
],
[
"DESCRIPTION",
"Threshold below which an input phase loss condition will be generated. Specified as a percent deviation from phase to neutral nominal voltage. A value of zero indicates that the threshold is disabled. Returns -1 if unsupported or failed. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value"
],
null,
null,
null,
null
]
}