A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).
Sources for this description
Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
OID reference
1.3.6.1.4.1.318.1.1.32.2.4.1.10
A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).
Identification
{1 3 6 1 4 1 318 1 1 32 2 4 1 10}
At least one MIB declaration places this object in a table row. A value belongs to a row instance; its suffix depends on the row's INDEX or AUGMENTS definition.
In CPDU-MIB, the row index pduUnitStatusIndex is declared as Integer32. A non-negative index value is encoded as one numeric subidentifier. An instance has the form .1.3.6.1.4.1.318.1.1.32.2.4.1.10.<pduUnitStatusIndex>. Use an index value actually present on the device and permitted by its MIB. Other definitions can differ.
snmpwalk [connection options] DEVICE .1.3.6.1.4.1.318.1.1.32.2.4.1.10
Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.
Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.
The displayed source records contain one distinct definition. Compare its source records.
pduUnitStatusResettableEnergy OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A user resettable energy meter measuring PDU energy consumption
in tenths of kilowatt-hours(kWh)."
::= { pduUnitStatusEntry 10 }
Meaning
Identical descriptions are grouped. Different wording and device-specific notes are retained.
A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).
Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
Evidence
Matching descriptions are grouped; open a group to compare definitions and supporting files.
Status in source: current.
Names: pduUnitStatusResettableEnergy
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"pduUnitStatusResettableEnergy",
"OBJECT-TYPE",
"SYNTAX",
"Integer32",
"MAX-ACCESS",
"read-only",
"STATUS",
"current",
"DESCRIPTION",
"\"A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).\"",
"::=",
"{",
"pduUnitStatusEntry",
"10",
"}"
],
"syntax_tree": [
[
"SimpleSyntax",
"Integer32"
],
null,
[
"MaxAccessPart",
"read-only"
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh)."
],
null,
null,
null,
null
]
}Vendor MIB copy from the Observium Community archive.
Module: CPDU-MIB
See published definition above
{'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'SNMPv2-TC': ['MacAddress'], 'RFC1155-SMI': ['enterprises', 'IpAddress', 'Gauge', 'TimeTicks'], 'RFC1213-MIB': ['DisplayString'], 'INET-ADDRESS-MIB': ['InetAddressType', 'InetAddress'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}Related source files and packages:
Vendor MIB copy from the LibreNMS archive.
Module: PowerNet-MIB
{'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'SNMPv2-TC': ['MacAddress'], 'RFC1155-SMI': ['enterprises', 'IpAddress', 'Gauge', 'TimeTicks'], 'RFC1213-MIB': ['DisplayString', 'sysDescr'], 'INET-ADDRESS-MIB': ['InetAddressType', 'InetAddress'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}Source data warning: Recovered from a file whose complete MIB does not parse. The original assignment and definition are preserved. Registration and implementation details may be inaccurate; consult the original file. Other damaged or unresolved declarations are not established registrations.
· Download PowerNet-MIBRelated source files and packages:
Registration
| OID | Name | Direct children | Descendants | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.318.1.1.32.2.4.1.1 | pduUnitStatusIndex | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.2 | pduUnitStatusName | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.3 | pduUnitStatusLoadState | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.4 | pduUnitStatusActivePower | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.5 | pduUnitStatusApparentPower | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.6 | pduUnitStatusPeakPower | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.7 | pduUnitStatusPeakPowerTimestamp | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.8 | pduUnitStatusPeakPowerStartTime | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.9 | pduUnitStatusEnergy | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.11 | pduUnitStatusEnergyStartTime | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.12 | pduUnitStatusOutletsEnergyStartTime | 0 | 0 | |
| 1.3.6.1.4.1.318.1.1.32.2.4.1.13 | pduUnitStatusPowerFactor | 0 | 0 |