thermalPowerOffDelay

1.3.6.1.4.1.4413.2.2.2.1.11.1.5

Description

This delay is used to ensure the remainder of the board is completely powered down prior to the Thermal Shutdown Circuit entering Over Temperature state. Because some power supplies may experience a current trip when input power is suddenly removed, this delay must be long enough to ensure the board will successfully …

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.4413.2.2.2.1.11.1 (thermalMgmtBase)
Node code
5
Node name
thermalPowerOffDelay
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.4413.2.2.2.1.11.1.5
URN notation
urn:oid:1.3.6.1.4.1.4413.2.2.2.1.11.1.5
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 4413 2 2 2 1 11 1 5}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) broadcom(4413) cableData(2) cableDataMgmt(2) cableDataMgmtMIB(2) cableDataMgmtMIBObjects(1) thermalMgmt(11) thermalMgmtBase(1) thermalPowerOffDelay(5)}
OID-IRI notation
  • /1/3/6/1/4/1/4413/2/2/2/1/11/1/5
  • /ISO/Identified-Organization/6/1/4/1/4413/2/2/2/1/11/1/5
  • /ISO/3/6/1/4/1/4413/2/2/2/1/11/1/5
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/identified-organization/dod/internet/private/enterprises/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/identified-organization/dod/internet/private/vendor-objects/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/org/dod/internet/private/enterprise/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/org/dod/internet/private/enterprises/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/org/dod/internet/private/ldap-enterprise/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/org/dod/internet/private/vendor-objects/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/iso-identified-organization/dod/internet/private/enterprise/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/iso-identified-organization/dod/internet/private/enterprises/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/iso-identified-organization/dod/internet/private/ldap-enterprise/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/iso-identified-organization/dod/internet/private/vendor-objects/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/iso-organization/dod/internet/private/enterprise/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/iso-organization/dod/internet/private/enterprises/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/iso-organization/dod/internet/private/ldap-enterprise/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay
  • /iso/iso-organization/dod/internet/private/vendor-objects/broadcom/cableData/cableDataMgmt/cableDataMgmtMIB/cableDataMgmtMIBObjects/thermalMgmt/thermalMgmtBase/thermalPowerOffDelay

SNMP properties

Value type
Unsigned32
Units
Seconds
Maximum access defined by MIB
read-write
Status in MIB
current
Allowed ranges
5–60

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.4413.2.2.2.1.11.1.5.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

The displayed source records contain one distinct definition. Compare its source records.

thermalPowerOffDelay OBJECT-TYPE
    SYNTAX      Unsigned32 (5..60)
    UNITS       "Seconds"
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "This delay is used to ensure the remainder of the board is completely powered 
         down prior to the Thermal Shutdown Circuit entering Over Temperature state. 
         Because some power supplies may experience a current trip when input power is 
         suddenly removed, this delay must be long enough to ensure the board will 
         successfully power back up following power removal. The delay is specified in 
         seconds; 5 to 60."
    ::= { thermalMgmtBase 5 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

This delay is used to ensure the remainder of the board is completely powered down prior to the Thermal Shutdown Circuit entering Over Temperature state. Because some power supplies may experience a current trip when input power is suddenly removed, this delay must be long enough to ensure the board will successfully power back up following power removal. The delay is specified in seconds; 5 to 60.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; open a group to compare definitions and supporting files.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 1

thermalPowerOffDelay · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: current.

Names: thermalPowerOffDelay

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "thermalPowerOffDelay",
    "OBJECT-TYPE",
    "SYNTAX",
    "Unsigned32",
    "(",
    "5",
    ".",
    ".",
    "60",
    ")",
    "UNITS",
    [
      "literal",
      "225365636f6e647322"
    ],
    "MAX-ACCESS",
    "read-write",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"This delay is used to ensure the remainder of the board is completely powered down prior to the Thermal Shutdown Circuit entering Over Temperature state. Because some power supplies may experience a current trip when input power is suddenly removed, this delay must be long enough to ensure the board will successfully power back up following power removal. The delay is specified in seconds; 5 to 60.\"",
    "::=",
    "{",
    "thermalMgmtBase",
    "5",
    "}"
  ],
  "syntax_tree": [
    [
      "ApplicationSyntax",
      "Unsigned32",
      [
        "integerSubType",
        [
          [
            5,
            60
          ]
        ]
      ]
    ],
    [
      "UNITS",
      "Seconds"
    ],
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "This delay is used to ensure the remainder of the board is completely powered down prior to the Thermal Shutdown Circuit entering Over Temperature state. Because some power supplies may experience a current trip when input power is suddenly removed, this delay must be long enough to ensure the board will successfully power back up following power removal. The delay is specified in seconds; 5 to 60."
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.4413)

Fan Frankie

Siblings (6)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.4413.2.2.2.1.11.1.1 thermalCurrentTemperature00
1.3.6.1.4.1.4413.2.2.2.1.11.1.2 thermalPowerOffThreshold00
1.3.6.1.4.1.4413.2.2.2.1.11.1.3 thermalPowerOnThreshold00
1.3.6.1.4.1.4413.2.2.2.1.11.1.4 thermalPowerOnDelay00
1.3.6.1.4.1.4413.2.2.2.1.11.1.6 thermalNotificationDelay00
1.3.6.1.4.1.4413.2.2.2.1.11.1.7 thermalMonitorInitialized00