unitControlOffCmd

1.3.6.1.4.1.534.6.6.7.1.3.1.2

Description

Unit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDU…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.534.6.6.7.1.3.1 (unitControlEntry)
Node code
2
Node name
unitControlOffCmd
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.534.6.6.7.1.3.1.2
URN notation
urn:oid:1.3.6.1.4.1.534.6.6.7.1.3.1.2
Type
OBJECT-TYPE
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 534 6 6 7 1 3 1 2}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) exide(534) products(6) pduAgent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) exide(534) products(6) pduagent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) exide(534) product(6) pduAgent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) exide(534) product(6) pduagent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) eaton(534) products(6) pduAgent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) eaton(534) products(6) pduagent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) eaton(534) product(6) pduAgent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) eaton(534) product(6) pduagent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) powerware(534) products(6) pduAgent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) powerware(534) products(6) pduagent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) powerware(534) product(6) pduAgent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) powerware(534) product(6) pduagent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) exide(534) products(6) pduAgent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) exide(534) products(6) pduagent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) exide(534) product(6) pduAgent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) exide(534) product(6) pduagent(6) eatonEpdu(7) units(1) unitControlTable(3) unitControlEntry(1) unitControlOffCmd(2)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/534/6/6/7/1/3/1/2
  • /ISO/Identified-Organization/6/1/4/1/534/6/6/7/1/3/1/2
  • /ISO/3/6/1/4/1/534/6/6/7/1/3/1/2
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/exide/products/pduAgent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/exide/products/pduagent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/exide/product/pduAgent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/exide/product/pduagent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/eaton/products/pduAgent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/eaton/products/pduagent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/eaton/product/pduAgent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/eaton/product/pduagent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/powerware/products/pduAgent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/powerware/products/pduagent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/powerware/product/pduAgent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprise/powerware/product/pduagent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprises/exide/products/pduAgent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprises/exide/products/pduagent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprises/exide/product/pduAgent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • /iso/identified-organization/dod/internet/private/enterprises/exide/product/pduagent/eatonEpdu/units/unitControlTable/unitControlEntry/unitControlOffCmd
  • Additional combinations skipped.

SNMP properties

Value type
Integer32
Maximum access defined by MIB
read-write
Status in MIB
current
Allowed ranges
-1–99999

Using this OID with SNMP

At least one MIB declaration places this object in a table row. A value belongs to a row instance; its suffix depends on the row's INDEX or AUGMENTS definition.

In EATON-EPDU-MIB, the row index strappingIndex is declared as Integer32. A non-negative index value is encoded as one numeric subidentifier. An instance has the form .1.3.6.1.4.1.534.6.6.7.1.3.1.2.<strappingIndex>. Use an index value actually present on the device and permitted by its MIB. Other definitions can differ.

snmpwalk [connection options] DEVICE .1.3.6.1.4.1.534.6.6.7.1.3.1.2

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

The displayed source records contain one distinct definition. Compare its source records.

unitControlOffCmd  OBJECT-TYPE
	SYNTAX     Integer32 (-1..99999)
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Unit-level outlet control command.
		
		Once the command is issued, outlets will turn Off.
		0-n : Time in seconds until the outlet Sequence Off command is issued
		-1 : Cancel a pending unit-level Off command 
		
		When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command."
	::= { unitControlEntry 2 }

Meaning

Descriptions

2 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Description 1

Unit-level outlet control command.

Once the command is issued, outlets will turn Off.
0-n : Time in seconds until the outlet Sequence Off command is issued
-1 : Cancel a pending unit-level Off command

When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.

Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object.
Sources for this description

MIBdepot

Parsed from EATON-EPDU-MIB_Advanced_Monitored_and_Managed_with_LCD.txt · eaton · EATON-EPDU-MIB

Source file: Download EATON-EPDU-MIB · Publisher's file

Vendor MIB copy from the Observium Community archive.

Related source files and packages:

Source file: Download EATON-EPDU-MIB · Publisher's file

Vendor MIB copy from the LibreNMS archive.

Source file: Download EATON-EPDU-MIB_.txt

Browse all files from MIBdepot

Description 2

Unit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.

Sources for this description

MIBdepot

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; open a group to compare definitions and supporting files.

Records for description 2MIBdepot1 record · 1 source

Description 2

unitControlOffCmd · currentMIBdepot1 source

Status in source: current.

Names: unitControlOffCmd

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "unitControlOffCmd",
    "OBJECT-TYPE",
    "SYNTAX",
    "Integer32",
    "(",
    "-",
    "1",
    ".",
    ".",
    "99999",
    ")",
    "MAX-ACCESS",
    "read-write",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Unit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.\"",
    "::=",
    "{",
    "unitControlEntry",
    "2",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "Integer32",
      [
        "integerSubType",
        [
          [
            -1,
            99999
          ]
        ]
      ]
    ],
    null,
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Unit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command."
    ],
    null,
    null,
    null,
    null
  ]
}
  • Preserved mibdepot archive

    Module: EATON-EPDU-MIB

    See published definition above

    Module imports
    {'SNMPv2-TC': ['DateAndTime', 'DisplayString'], 'EATON-OIDS': ['pduAgent'], 'SNMPv2-SMI': ['OBJECT-TYPE', 'NOTIFICATION-TYPE', 'MODULE-IDENTITY', 'Counter32', 'Unsigned32', 'Integer32'], 'SNMPv2-CONF': ['NOTIFICATION-GROUP', 'OBJECT-GROUP', 'MODULE-COMPLIANCE']}
    · Download EATON-EPDU-MIB.txt

Historical records

Additional source information

Information from MIBdepot
unitControlOffCmd  OBJECT-TYPE
	SYNTAX     Integer32 (-1..99999)
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Unit-level outlet control command.
		
		Once the command is issued, outlets will turn Off.
		0-n : Time in seconds until the outlet Sequence Off command is issued
		-1 : Cancel a pending unit-level Off command 
		
		When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
          
          Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
          commands.  These will respond with an error if a command value of > 0 is written to this object."
	::= { unitControlEntry 2 }

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.534)

Hammill Brian

Siblings (1)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.534.6.6.7.1.3.1.3 unitControlOnCmd00 Unit-level outlet control command.

Once the command is issued, outlets will turn On according to their outletControlSequenceDel…