1.3.6.1.4.1.534.6.6.7.6.4.1.4
Status of the measured outlet current relative to the configured thresholds.
Identification
{1 3 6 1 4 1 534 6 6 7 6 4 1 4}
| Value | Name |
|---|---|
| 0 | good |
| 1 | lowWarning |
| 2 | lowCritical |
| 3 | highWarning |
| 4 | highCritical |
At least one MIB declaration places this object in a table row. A value belongs to a row instance; its suffix depends on the row's INDEX or AUGMENTS definition.
In EATON-EPDU-MIB, the row index consists of these components in order:
strappingIndex (Integer32): one numeric subidentifier for the non-negative value.outletIndex (Integer32): one numeric subidentifier for the non-negative value.An instance has the form .1.3.6.1.4.1.534.6.6.7.6.4.1.4.<strappingIndex>.<outletIndex>. Use values present on the device and permitted by its MIB. Other definitions can differ.
snmpwalk [connection options] DEVICE .1.3.6.1.4.1.534.6.6.7.6.4.1.4
Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.
Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.
Available source records contain 2 distinct definitions; some records may not include a definition.
outletCurrentThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (0),
lowWarning (1),
lowCritical (2),
highWarning (3),
highCritical (4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the measured outlet current relative to the configured thresholds.
A negative value indicates that this object is not available."
::= { outletCurrentEntry 4 }outletCurrentThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (0),
lowWarning (1),
lowCritical (2),
highWarning (3),
highCritical (4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the measured outlet current relative to the configured thresholds.
A negative value indicates that this object is not available."
::= { outletCurrentEntry 4 }
Meaning
Identical descriptions are grouped. Different wording and device-specific notes are retained.
Description 1
Parsed from EATON-EPDU-MIB_Advanced_Monitored_and_Managed_with_LCD.txt · eaton · EATON-EPDU-MIB
Source file: Download EATON-EPDU-MIB_.txt
Source file: Download EATON-EPDU-MIB.txt
Description 2
Status of the measured outlet current relative to the configured thresholds. A negative value indicates that this object is not available.
Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
Evidence
Matching descriptions are grouped; open a group to compare definitions and supporting files.
Status in source: current.
Names: outletCurrentThStatus
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"outletCurrentThStatus",
"OBJECT-TYPE",
"SYNTAX",
"INTEGER",
"{",
"good",
"(",
"0",
")",
",",
"lowWarning",
"(",
"1",
")",
",",
"lowCritical",
"(",
"2",
")",
",",
"highWarning",
"(",
"3",
")",
",",
"highCritical",
"(",
"4",
")",
"}",
"MAX-ACCESS",
"read-only",
"STATUS",
"current",
"DESCRIPTION",
"\"Status of the measured outlet current relative to the configured thresholds. A negative value indicates that this object is not available.\"",
"::=",
"{",
"outletCurrentEntry",
"4",
"}"
],
"syntax_tree": [
[
"SimpleSyntax",
"INTEGER",
[
"enumSpec",
[
[
"good",
0
],
[
"lowWarning",
1
],
[
"lowCritical",
2
],
[
"highWarning",
3
],
[
"highCritical",
4
]
]
]
],
null,
[
"MaxAccessPart",
"read-only"
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"Status of the measured outlet current relative to the configured thresholds. A negative value indicates that this object is not available."
],
null,
null,
null,
null
]
}Vendor MIB copy from the LibreNMS archive.
Module: EATON-EPDU-MIB
See published definition above
{'SNMPv2-TC': ['TEXTUAL-CONVENTION', 'DateAndTime', 'DisplayString'], 'EATON-OIDS': ['pduAgent'], 'SNMPv2-SMI': ['OBJECT-TYPE', 'NOTIFICATION-TYPE', 'MODULE-IDENTITY', 'Counter32', 'Unsigned32', 'Integer32', 'enterprises'], 'SNMPv2-CONF': ['NOTIFICATION-GROUP', 'OBJECT-GROUP', 'MODULE-COMPLIANCE']}Related source files and packages:
Vendor MIB copy from the Observium Community archive.
Module: EATON-EPDU-MIB
See published definition above
{'SNMPv2-TC': ['TEXTUAL-CONVENTION', 'DateAndTime', 'DisplayString'], 'EATON-OIDS': ['pduAgent'], 'SNMPv2-SMI': ['OBJECT-TYPE', 'NOTIFICATION-TYPE', 'MODULE-IDENTITY', 'Counter32', 'Unsigned32', 'Integer32', 'enterprises'], 'SNMPv2-CONF': ['NOTIFICATION-GROUP', 'OBJECT-GROUP', 'MODULE-COMPLIANCE']}Related source files and packages:
Historical records
outletCurrentThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (0),
lowWarning (1),
lowCritical (2),
highWarning (3),
highCritical (4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the measured outlet current relative to the configured thresholds."
::= { outletCurrentEntry 4 }
Registration
| OID | Name | Direct children | Descendants | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.534.6.6.7.6.4.1.2 | outletCurrentCapacity | 0 | 0 | Rated current capacity of the outlet. A negative value indicates that the hardware current capacity is unknown. Units are mill… |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.3 | outletCurrent | 0 | 0 | An outlet current measurement value. Units are milliamps. |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.5 | outletCurrentThLowerWarning | 0 | 0 | Lower warning threshold. Units are milliamps. A value of -1 indicates that this object is not available for a particular ePDU … |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.6 | outletCurrentThLowerCritical | 0 | 0 | Lower critical threshold. Units are milliamps. A value of -1 indicates that this object is not available for a particular ePDU… |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.7 | outletCurrentThUpperWarning | 0 | 0 | Upper warning threshold. Units are milliamps. A value of -1 indicates that this object is not available for a particular ePDU … |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.8 | outletCurrentThUpperCritical | 0 | 0 | Upper critical threshold. Units are milliamps. A value of -1 indicates that this object is not available for a particular ePDU… |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.9 | outletCurrentCrestFactor | 0 | 0 | |
| 1.3.6.1.4.1.534.6.6.7.6.4.1.10 | outletCurrentPercentLoad | 0 | 0 |