ups09FullCompliance — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
The compliance statement for UPSs that support advanced full-featured functions.
{1 3 6 1 4 1 53973 1 1 10 3 1 3}
The compliance statement for UPSs that support advanced full-featured functions.
Status in source: current.
Names: ups09FullCompliance
{
"smi_kind": "MODULE-COMPLIANCE",
"definition": [
"ups09FullCompliance",
"MODULE-COMPLIANCE",
"STATUS",
"current",
"DESCRIPTION",
"\"The compliance statement for UPSs that support advanced full-featured functions.\"",
"MODULE",
"MANDATORY-GROUPS",
"{",
"ups09FullIdentGroup",
",",
"ups09FullBatteryGroup",
",",
"ups09FullInputGroup",
",",
"ups09FullOutputGroup",
",",
"ups09FullAlarmGroup",
",",
"ups09FullTestGroup",
",",
"ups09FullControlGroup",
"}",
"OBJECT",
"ups09AlarmDescr",
"DESCRIPTION",
"\"Support of all `well known' alarm types is not required. The well known alarm types which must be supported are: ups09AlarmBatteryBad, ups09AlarmOnBattery, ups09AlarmLowBattery, ups09AlarmDepletedBattery, ups09AlarmTempBad, ups09AlarmInputBad, ups09AlarmOnBypass, ups09AlarmBypassBad, ups09AlarmOutputOffAsRequested, ups09AlarmUpsOffAsRequested, ups09AlarmUpsOutputOff, ups09AlarmUpsSystemOff, ups09AlarmGeneralFault, ups09AlarmDiagnosticTestFailed, ups09AlarmCommunicationsLost, ups09AlarmShutdownPending, and ups09AlarmTestInProgress.\"",
"OBJECT",
"ups09TestId",
"DESCRIPTION",
"\"Support of all `well known' test types is not required. The well known test types which must be supported are: ups09TestNoTestsInitiated, ups09TestGeneralSystemsTest, and ups09TestQuickBatteryTest.\"",
"OBJECT",
"ups09OutputSource",
"SYNTAX",
"INTEGER",
"{",
"normal",
"(",
"2",
")",
",",
"battery",
"(",
"4",
")",
"}",
"DESCRIPTION",
"\"Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required.\"",
"GROUP",
"ups09FullBypassGroup",
"DESCRIPTION",
"\"The ups09FullBypassGroup is only required for UPSs that have a Bypass present.\"",
"OBJECT",
"ups09ShutdownType",
"MIN-ACCESS",
"read-only",
"DESCRIPTION",
"\"Read-write access is not required, i.e., compliant systems need not support more than one shutdown type.\"",
"::=",
"{",
"ups09Compliances",
"3",
"}"
],
"syntax_tree": [
[
"Status",
"current"
],
[
"DESCRIPTION",
"The compliance statement for UPSs that support advanced full-featured functions."
],
null,
[
"ComplianceModules",
[
[
null,
[
"ups09FullIdentGroup",
"ups09FullBatteryGroup",
"ups09FullInputGroup",
"ups09FullOutputGroup",
"ups09FullAlarmGroup",
"ups09FullTestGroup",
"ups09FullControlGroup"
]
]
]
]
]
}Vendor MIB copy from the LibreNMS archive.
Module: ABBMODULARUPS-MIB
ups09FullCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The compliance statement for UPSs that support
advanced full-featured functions."
MODULE -- this module
MANDATORY-GROUPS { ups09FullIdentGroup, ups09FullBatteryGroup,
ups09FullInputGroup, ups09FullOutputGroup,
ups09FullAlarmGroup, ups09FullTestGroup,
ups09FullControlGroup }
OBJECT ups09AlarmDescr
DESCRIPTION
"Support of all `well known' alarm types is not
required. The well known alarm types which must be
supported are: ups09AlarmBatteryBad, ups09AlarmOnBattery,
ups09AlarmLowBattery, ups09AlarmDepletedBattery,
ups09AlarmTempBad, ups09AlarmInputBad, ups09AlarmOnBypass,
ups09AlarmBypassBad, ups09AlarmOutputOffAsRequested,
ups09AlarmUpsOffAsRequested, ups09AlarmUpsOutputOff,
ups09AlarmUpsSystemOff, ups09AlarmGeneralFault,
ups09AlarmDiagnosticTestFailed,
ups09AlarmCommunicationsLost, ups09AlarmShutdownPending,
and ups09AlarmTestInProgress."
OBJECT ups09TestId
DESCRIPTION
"Support of all `well known' test types is not
required. The well known test types which must be
supported are: ups09TestNoTestsInitiated,
ups09TestGeneralSystemsTest, and
ups09TestQuickBatteryTest."
OBJECT ups09OutputSource
SYNTAX INTEGER {
normal(2),
battery(4)
}
DESCRIPTION
"Support of the values other(1), none(2), bypass(4),
booster(6) and reducer(7) is not required."
GROUP ups09FullBypassGroup
DESCRIPTION
"The ups09FullBypassGroup is only required for UPSs that
have a Bypass present."
OBJECT ups09ShutdownType
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant
systems need not support more than one shutdown type."
::= { ups09Compliances 3 }{'SNMPv2-TC': ['DisplayString', 'TimeStamp', 'TimeInterval', 'TestAndIncr', 'AutonomousType', 'TEXTUAL-CONVENTION'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'NOTIFICATION-TYPE', 'OBJECT-IDENTITY', 'Counter32', 'Gauge32', 'Integer32', 'Unsigned32', 'enterprises'], 'SNMPv2-CONF': ['MODULE-COMPLIANCE', 'OBJECT-GROUP']}Related source files and packages:
Downloaded: 2026-10-24T02:14:13.121331+00:00.
| OID | Name | Direct children | Descendants | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.53973.1.1.10.3.1.1 | ups09SubsetCompliance | 0 | 0 | |
| 1.3.6.1.4.1.53973.1.1.10.3.1.2 | ups09BasicCompliance | 0 | 0 |