Reference record for OID 1.3.6.1.4.1.53973.1.1.12.1.2.1

Parent
1.3.6.1.4.1.53973.1.1.12.1.2 (ups11Battery)
Node code
1
Node name
ups11BatteryStatus
Numeric OID
1.3.6.1.4.1.53973.1.1.12.1.2.1
URN notation
urn:oid:1.3.6.1.4.1.53973.1.1.12.1.2.1
ASN.1 notation

{1 3 6 1 4 1 53973 1 1 12 1 2 1}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) abb(53973) ups(1) upsModular(1) upsModule11(12) ups11Objects(1) ups11Battery(2) ups11BatteryStatus(1)}
OID-IRI notation
  • /1/3/6/1/4/1/53973/1/1/12/1/2/1
  • /ISO/Identified-Organization/6/1/4/1/53973/1/1/12/1/2/1
  • /ISO/3/6/1/4/1/53973/1/1/12/1/2/1
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/identified-organization/dod/internet/private/enterprises/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/identified-organization/dod/internet/private/vendor-objects/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/org/dod/internet/private/enterprise/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/org/dod/internet/private/enterprises/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/org/dod/internet/private/ldap-enterprise/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/org/dod/internet/private/vendor-objects/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/iso-identified-organization/dod/internet/private/enterprise/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/iso-identified-organization/dod/internet/private/enterprises/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/iso-identified-organization/dod/internet/private/ldap-enterprise/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/iso-identified-organization/dod/internet/private/vendor-objects/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/iso-organization/dod/internet/private/enterprise/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/iso-organization/dod/internet/private/enterprises/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/iso-organization/dod/internet/private/ldap-enterprise/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus
  • /iso/iso-organization/dod/internet/private/vendor-objects/abb/ups/upsModular/upsModule11/ups11Objects/ups11Battery/ups11BatteryStatus

Descriptions

ups11BatteryStatus — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than ups11ConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to ups11ConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).

Source records

ups11BatteryStatus

Status in source: current.

Names: ups11BatteryStatus

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "ups11BatteryStatus",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "{",
    "unknown",
    "(",
    "1",
    ")",
    ",",
    "batteryNormal",
    "(",
    "2",
    ")",
    ",",
    "batteryLow",
    "(",
    "3",
    ")",
    ",",
    "batteryDepleted",
    "(",
    "4",
    ")",
    "}",
    "MAX-ACCESS",
    "read-only",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than ups11ConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to ups11ConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).\"",
    "::=",
    "{",
    "ups11Battery",
    "1",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER",
      [
        "enumSpec",
        [
          [
            "unknown",
            1
          ],
          [
            "batteryNormal",
            2
          ],
          [
            "batteryLow",
            3
          ],
          [
            "batteryDepleted",
            4
          ]
        ]
      ]
    ],
    null,
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than ups11ConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to ups11ConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output)."
    ],
    null,
    null,
    null,
    null
  ]
}
  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: ABBMODULARUPS-MIB

    Vendor MIB copy from the LibreNMS archive.

    Module: ABBMODULARUPS-MIB

    Published definition
    ups11BatteryStatus OBJECT-TYPE
           SYNTAX     INTEGER {
               unknown(1),
               batteryNormal(2),
               batteryLow(3),
               batteryDepleted(4)
           }
           MAX-ACCESS read-only
           STATUS     current
           DESCRIPTION
                   "The indication of the capacity remaining in the UPS
                   system's batteries.   A value of batteryNormal
                   indicates that the remaining run-time is greater than
                   ups11ConfigLowBattTime.  A value of batteryLow indicates
                   that the remaining battery run-time is less than or
                   equal to ups11ConfigLowBattTime.  A value of
                   batteryDepleted indicates that the UPS will be unable
                   to sustain the present load when and if the utility
                   power is lost (including the possibility that the
                   utility power is currently absent and the UPS is
                   unable to sustain the output)."
           ::= { ups11Battery 1 }
    Module imports
    {'SNMPv2-TC': ['DisplayString', 'TimeStamp', 'TimeInterval', 'TestAndIncr', 'AutonomousType', 'TEXTUAL-CONVENTION'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'NOTIFICATION-TYPE', 'OBJECT-IDENTITY', 'Counter32', 'Gauge32', 'Integer32', 'Unsigned32', 'enterprises'], 'SNMPv2-CONF': ['MODULE-COMPLIANCE', 'OBJECT-GROUP']}

    Related source files and packages:


    Source location: ABBMODULARUPS-MIB::ups11BatteryStatus.
    Source version and references

    Downloaded: 2026-10-24T02:14:13.121331+00:00.

Current Registration Authority (inferred from ancestor 1.3.6.1.4.1.53973)

ABB Power Protection SA

Siblings (6)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.53973.1.1.12.1.2.2 ups11SecondsOnBattery00
1.3.6.1.4.1.53973.1.1.12.1.2.3 ups11EstimatedMinutesRemaining00
1.3.6.1.4.1.53973.1.1.12.1.2.4 ups11EstimatedChargeRemaining00
1.3.6.1.4.1.53973.1.1.12.1.2.5 ups11BatteryVoltage00
1.3.6.1.4.1.53973.1.1.12.1.2.6 ups11BatteryCurrent00
1.3.6.1.4.1.53973.1.1.12.1.2.7 ups11BatteryTemperature00