Reference record for OID 1.3.6.1.4.1.53973.1.1.30.1.8.2

Parent
1.3.6.1.4.1.53973.1.1.30.1.8 (ups29Control)
Node code
2
Node name
ups29ShutdownAfterDelay
Numeric OID
1.3.6.1.4.1.53973.1.1.30.1.8.2
URN notation
urn:oid:1.3.6.1.4.1.53973.1.1.30.1.8.2
ASN.1 notation

{1 3 6 1 4 1 53973 1 1 30 1 8 2}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) abb(53973) ups(1) upsModular(1) upsModule29(30) ups29Objects(1) ups29Control(8) ups29ShutdownAfterDelay(2)}
OID-IRI notation
  • /1/3/6/1/4/1/53973/1/1/30/1/8/2
  • /ISO/Identified-Organization/6/1/4/1/53973/1/1/30/1/8/2
  • /ISO/3/6/1/4/1/53973/1/1/30/1/8/2
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/identified-organization/dod/internet/private/enterprises/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/identified-organization/dod/internet/private/vendor-objects/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/org/dod/internet/private/enterprise/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/org/dod/internet/private/enterprises/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/org/dod/internet/private/ldap-enterprise/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/org/dod/internet/private/vendor-objects/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/iso-identified-organization/dod/internet/private/enterprise/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/iso-identified-organization/dod/internet/private/enterprises/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/iso-identified-organization/dod/internet/private/ldap-enterprise/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/iso-identified-organization/dod/internet/private/vendor-objects/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/iso-organization/dod/internet/private/enterprise/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/iso-organization/dod/internet/private/enterprises/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/iso-organization/dod/internet/private/ldap-enterprise/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay
  • /iso/iso-organization/dod/internet/private/vendor-objects/abb/ups/upsModular/upsModule29/ups29Objects/ups29Control/ups29ShutdownAfterDelay

Descriptions

ups29ShutdownAfterDelay — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of ups29ShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if ups29ShutdownType = system and the system is already off. Similarly, there is no additional action at that time if ups29ShutdownType = output and the output is already off. When read, ups29ShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any ups29ShutdownAfterDelay already in effect.

Source records

ups29ShutdownAfterDelay

Status in source: current.

Names: ups29ShutdownAfterDelay

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "ups29ShutdownAfterDelay",
    "OBJECT-TYPE",
    "SYNTAX",
    "Integer32",
    "(",
    "-",
    "1",
    ".",
    ".",
    "2147483647",
    ")",
    "UNITS",
    [
      "literal",
      "227365636f6e647322"
    ],
    "MAX-ACCESS",
    "read-only",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of ups29ShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if ups29ShutdownType = system and the system is already off. Similarly, there is no additional action at that time if ups29ShutdownType = output and the output is already off. When read, ups29ShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any ups29ShutdownAfterDelay already in effect.\"",
    "::=",
    "{",
    "ups29Control",
    "2",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "Integer32",
      [
        "integerSubType",
        [
          [
            -1,
            2147483647
          ]
        ]
      ]
    ],
    [
      "UNITS",
      "seconds"
    ],
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of ups29ShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if ups29ShutdownType = system and the system is already off. Similarly, there is no additional action at that time if ups29ShutdownType = output and the output is already off. When read, ups29ShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any ups29ShutdownAfterDelay already in effect."
    ],
    null,
    null,
    null,
    null
  ]
}
  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: ABBMODULARUPS-MIB

    Vendor MIB copy from the LibreNMS archive.

    Module: ABBMODULARUPS-MIB

    Published definition
    ups29ShutdownAfterDelay OBJECT-TYPE
           SYNTAX     Integer32 (-1..2147483647)
           UNITS      "seconds"
           MAX-ACCESS read-only
           STATUS     current
           DESCRIPTION
                   "Setting this object will shutdown (i.e., turn off)
                   either the UPS output or the UPS system (as determined
                   by the value of ups29ShutdownType at the time of
                   shutdown) after the indicated number of seconds, or
                   less if the UPS batteries become depleted. Setting
                   this object to 0 will cause the shutdown to occur
                   immediately.  Setting this object to -1 will abort the
                   countdown.  If the system is already in the desired
                   state at the time the countdown reaches 0, then
                   nothing will happen.  That is, there is no additional
                   action at that time if ups29ShutdownType = system and
                   the system is already off.  Similarly, there is no
                   additional action at that time if ups29ShutdownType =
                   output and the output is already off.  When read,
                   ups29ShutdownAfterDelay will return the number of
                   seconds remaining until shutdown, or -1 if no shutdown
                   countdown is in effect.  On some systems, if the agent
                   is restarted while a shutdown countdown is in effect,
                   the countdown may be aborted.  Sets to this object
                   override any ups29ShutdownAfterDelay already in effect."
           ::= { ups29Control 2 }
    Module imports
    {'SNMPv2-TC': ['DisplayString', 'TimeStamp', 'TimeInterval', 'TestAndIncr', 'AutonomousType', 'TEXTUAL-CONVENTION'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'NOTIFICATION-TYPE', 'OBJECT-IDENTITY', 'Counter32', 'Gauge32', 'Integer32', 'Unsigned32', 'enterprises'], 'SNMPv2-CONF': ['MODULE-COMPLIANCE', 'OBJECT-GROUP']}

    Related source files and packages:


    Source location: ABBMODULARUPS-MIB::ups29ShutdownAfterDelay.
    Source version and references

    Downloaded: 2026-10-24T02:14:13.121331+00:00.

Current Registration Authority (inferred from ancestor 1.3.6.1.4.1.53973)

ABB Power Protection SA

Siblings (3)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.53973.1.1.30.1.8.1 ups29ShutdownType00
1.3.6.1.4.1.53973.1.1.30.1.8.3 ups29StartupAfterDelay00
1.3.6.1.4.1.53973.1.1.30.1.8.4 ups29RebootWithDuration00