ups06FullCompliance — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
The compliance statement for UPSs that support advanced full-featured functions.
{1 3 6 1 4 1 53973 1 1 7 3 1 3}
The compliance statement for UPSs that support advanced full-featured functions.
Status in source: current.
Names: ups06FullCompliance
{
"smi_kind": "MODULE-COMPLIANCE",
"definition": [
"ups06FullCompliance",
"MODULE-COMPLIANCE",
"STATUS",
"current",
"DESCRIPTION",
"\"The compliance statement for UPSs that support advanced full-featured functions.\"",
"MODULE",
"MANDATORY-GROUPS",
"{",
"ups06FullIdentGroup",
",",
"ups06FullBatteryGroup",
",",
"ups06FullInputGroup",
",",
"ups06FullOutputGroup",
",",
"ups06FullAlarmGroup",
",",
"ups06FullTestGroup",
",",
"ups06FullControlGroup",
"}",
"OBJECT",
"ups06AlarmDescr",
"DESCRIPTION",
"\"Support of all `well known' alarm types is not required. The well known alarm types which must be supported are: ups06AlarmBatteryBad, ups06AlarmOnBattery, ups06AlarmLowBattery, ups06AlarmDepletedBattery, ups06AlarmTempBad, ups06AlarmInputBad, ups06AlarmOnBypass, ups06AlarmBypassBad, ups06AlarmOutputOffAsRequested, ups06AlarmUpsOffAsRequested, ups06AlarmUpsOutputOff, ups06AlarmUpsSystemOff, ups06AlarmGeneralFault, ups06AlarmDiagnosticTestFailed, ups06AlarmCommunicationsLost, ups06AlarmShutdownPending, and ups06AlarmTestInProgress.\"",
"OBJECT",
"ups06TestId",
"DESCRIPTION",
"\"Support of all `well known' test types is not required. The well known test types which must be supported are: ups06TestNoTestsInitiated, ups06TestGeneralSystemsTest, and ups06TestQuickBatteryTest.\"",
"OBJECT",
"ups06OutputSource",
"SYNTAX",
"INTEGER",
"{",
"normal",
"(",
"2",
")",
",",
"battery",
"(",
"4",
")",
"}",
"DESCRIPTION",
"\"Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required.\"",
"GROUP",
"ups06FullBypassGroup",
"DESCRIPTION",
"\"The ups06FullBypassGroup is only required for UPSs that have a Bypass present.\"",
"OBJECT",
"ups06ShutdownType",
"MIN-ACCESS",
"read-only",
"DESCRIPTION",
"\"Read-write access is not required, i.e., compliant systems need not support more than one shutdown type.\"",
"::=",
"{",
"ups06Compliances",
"3",
"}"
],
"syntax_tree": [
[
"Status",
"current"
],
[
"DESCRIPTION",
"The compliance statement for UPSs that support advanced full-featured functions."
],
null,
[
"ComplianceModules",
[
[
null,
[
"ups06FullIdentGroup",
"ups06FullBatteryGroup",
"ups06FullInputGroup",
"ups06FullOutputGroup",
"ups06FullAlarmGroup",
"ups06FullTestGroup",
"ups06FullControlGroup"
]
]
]
]
]
}Vendor MIB copy from the LibreNMS archive.
Module: ABBMODULARUPS-MIB
ups06FullCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The compliance statement for UPSs that support
advanced full-featured functions."
MODULE -- this module
MANDATORY-GROUPS { ups06FullIdentGroup, ups06FullBatteryGroup,
ups06FullInputGroup, ups06FullOutputGroup,
ups06FullAlarmGroup, ups06FullTestGroup,
ups06FullControlGroup }
OBJECT ups06AlarmDescr
DESCRIPTION
"Support of all `well known' alarm types is not
required. The well known alarm types which must be
supported are: ups06AlarmBatteryBad, ups06AlarmOnBattery,
ups06AlarmLowBattery, ups06AlarmDepletedBattery,
ups06AlarmTempBad, ups06AlarmInputBad, ups06AlarmOnBypass,
ups06AlarmBypassBad, ups06AlarmOutputOffAsRequested,
ups06AlarmUpsOffAsRequested, ups06AlarmUpsOutputOff,
ups06AlarmUpsSystemOff, ups06AlarmGeneralFault,
ups06AlarmDiagnosticTestFailed,
ups06AlarmCommunicationsLost, ups06AlarmShutdownPending,
and ups06AlarmTestInProgress."
OBJECT ups06TestId
DESCRIPTION
"Support of all `well known' test types is not
required. The well known test types which must be
supported are: ups06TestNoTestsInitiated,
ups06TestGeneralSystemsTest, and
ups06TestQuickBatteryTest."
OBJECT ups06OutputSource
SYNTAX INTEGER {
normal(2),
battery(4)
}
DESCRIPTION
"Support of the values other(1), none(2), bypass(4),
booster(6) and reducer(7) is not required."
GROUP ups06FullBypassGroup
DESCRIPTION
"The ups06FullBypassGroup is only required for UPSs that
have a Bypass present."
OBJECT ups06ShutdownType
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant
systems need not support more than one shutdown type."
::= { ups06Compliances 3 }{'SNMPv2-TC': ['DisplayString', 'TimeStamp', 'TimeInterval', 'TestAndIncr', 'AutonomousType', 'TEXTUAL-CONVENTION'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'NOTIFICATION-TYPE', 'OBJECT-IDENTITY', 'Counter32', 'Gauge32', 'Integer32', 'Unsigned32', 'enterprises'], 'SNMPv2-CONF': ['MODULE-COMPLIANCE', 'OBJECT-GROUP']}Related source files and packages: