Reference record for OID 1.3.6.1.4.1.63131.1.1.26.9.2.4.1.5

Parent
1.3.6.1.4.1.63131.1.1.26.9.2.4.1 (rPDU2OutletSwitchedControlEntry)
Node code
5
Node name
rPDU2OutletSwitchedControlCommand
Numeric OID
1.3.6.1.4.1.63131.1.1.26.9.2.4.1.5
URN notation
urn:oid:1.3.6.1.4.1.63131.1.1.26.9.2.4.1.5
ASN.1 notation

{1 3 6 1 4 1 63131 1 1 26 9 2 4 1 5}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) 63131 products(1) hardware(1) rPDU2(26) rPDU2Outlet(9) rPDU2OutletSwitched(2) rPDU2OutletSwitchedControlTable(4) rPDU2OutletSwitchedControlEntry(1) rPDU2OutletSwitchedControlCommand(5)}
OID-IRI notation
  • /1/3/6/1/4/1/63131/1/1/26/9/2/4/1/5
  • /ISO/Identified-Organization/6/1/4/1/63131/1/1/26/9/2/4/1/5
  • /ISO/3/6/1/4/1/63131/1/1/26/9/2/4/1/5
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/identified-organization/dod/internet/private/enterprises/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/identified-organization/dod/internet/private/vendor-objects/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/org/dod/internet/private/enterprise/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/org/dod/internet/private/enterprises/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/org/dod/internet/private/ldap-enterprise/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/org/dod/internet/private/vendor-objects/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/iso-identified-organization/dod/internet/private/enterprise/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/iso-identified-organization/dod/internet/private/enterprises/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/iso-identified-organization/dod/internet/private/ldap-enterprise/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/iso-identified-organization/dod/internet/private/vendor-objects/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/iso-organization/dod/internet/private/enterprise/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/iso-organization/dod/internet/private/enterprises/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/iso-organization/dod/internet/private/ldap-enterprise/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand
  • /iso/iso-organization/dod/internet/private/vendor-objects/PDU/products/hardware/rPDU2/rPDU2Outlet/rPDU2OutletSwitched/rPDU2OutletSwitchedControlTable/rPDU2OutletSwitchedControlEntry/rPDU2OutletSwitchedControlCommand

Descriptions

rPDU2OutletSwitchedControlCommand — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will cause the Switched Rack PDU to perform an immediateOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (5) will turn the outlet on after the rPDU2OutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (6) will turn the outlet off after the rPDU2OutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (7) will cause the Switched Rack PDU to perform a delayedOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (8) will cause any pending command to this outlet to be cancelled.

Source records

rPDU2OutletSwitchedControlCommand

Status in source: mandatory.

Names: rPDU2OutletSwitchedControlCommand

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "rPDU2OutletSwitchedControlCommand",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "{",
    "immediateOn",
    "(",
    "1",
    ")",
    ",",
    "immediateOff",
    "(",
    "2",
    ")",
    ",",
    "immediateReboot",
    "(",
    "3",
    ")",
    ",",
    "outletUnknown",
    "(",
    "4",
    ")",
    ",",
    "delayedOn",
    "(",
    "5",
    ")",
    ",",
    "delayedOff",
    "(",
    "6",
    ")",
    ",",
    "delayedReboot",
    "(",
    "7",
    ")",
    ",",
    "cancelPendingCommand",
    "(",
    "8",
    ")",
    "}",
    "ACCESS",
    "read-write",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will cause the Switched Rack PDU to perform an immediateOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (5) will turn the outlet on after the rPDU2OutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (6) will turn the outlet off after the rPDU2OutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (7) will cause the Switched Rack PDU to perform a delayedOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (8) will cause any pending command to this outlet to be cancelled.\"",
    "::=",
    "{",
    "rPDU2OutletSwitchedControlEntry",
    "5",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER",
      [
        "enumSpec",
        [
          [
            "immediateOn",
            1
          ],
          [
            "immediateOff",
            2
          ],
          [
            "immediateReboot",
            3
          ],
          [
            "outletUnknown",
            4
          ],
          [
            "delayedOn",
            5
          ],
          [
            "delayedOff",
            6
          ],
          [
            "delayedReboot",
            7
          ],
          [
            "cancelPendingCommand",
            8
          ]
        ]
      ]
    ],
    null,
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will cause the Switched Rack PDU to perform an immediateOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (5) will turn the outlet on after the rPDU2OutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (6) will turn the outlet off after the rPDU2OutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (7) will cause the Switched Rack PDU to perform a delayedOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (8) will cause any pending command to this outlet to be cancelled."
    ],
    null,
    null,
    null,
    null
  ]
}
  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: Source package: observium-community-latest.tar.gz

    Vendor MIB copy from the Observium Community archive.

    Module: PowerNet-Inova

    Published definition
    rPDU2OutletSwitchedControlCommand OBJECT-TYPE
    			SYNTAX INTEGER
    				{
    				immediateOn(1),
    				immediateOff(2),
    				immediateReboot(3),
    				outletUnknown(4),
    				delayedOn(5),
    				delayedOff(6),
    				delayedReboot(7),
    				cancelPendingCommand(8)
    				}
    			ACCESS read-write
    			STATUS mandatory
    			DESCRIPTION
    				"Getting this variable will return the outlet state. If
    				the outlet is on, the immediateOn (1) value will be returned.
    				If the outlet is off, the immediateOff (2) value will be
    				returned. If the state of the outlet cannot be
    				determined, the outletUnknown (4) value will be returned.
    				If the outletUnknown condition should occur, all devices
    				powered by the PDU should be shut down. The PDU's power
    				should then be cycled to clear this condition.
    				
    				Setting this variable to immediateOn (1) will immediately turn
    				the outlet on.
    				
    				Setting this variable to immediateOff (2) will immediately turn
    				the outlet off.
    				
    				Setting this variable to immediateReboot (3) will cause the
    				Switched Rack PDU to perform an immediateOff command, wait the
    				rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an
    				immediateOn command.
    				
    				Setting this variable to delayedOn (5) will turn the outlet on
    				after the rPDU2OutletSwitchedConfigPowerOnTime OID time has elapsed.
    				
    				Setting this variable to delayedOff (6) will turn the outlet off
    				after the rPDU2OutletSwitchedConfigPowerOffTime OID time has elapsed.
    				
    				Setting this variable to delayedReboot  (7) will cause the
    				Switched Rack PDU to perform a delayedOff command, wait the
    				rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a
    				delayedOn command.
    				
    				Setting this variable to cancelPendingCommand (8) will cause any
    				pending command to this outlet to be cancelled."
    			::= { rPDU2OutletSwitchedControlEntry 5 }
    Module imports
    {'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'RFC1155-SMI': ['enterprises', 'TimeTicks', 'IpAddress', 'Gauge', 'Opaque'], 'RFC1213-MIB': ['DisplayString']}

    Source data warning: Recovered from a file whose complete MIB does not parse. The original assignment and definition are preserved. Registration and implementation details may be inaccurate; consult the original file. Other damaged or unresolved declarations are not established registrations.

    · Download PowerNet-Inova

    Related source files and packages:


    Source location: PowerNet-Inova::rPDU2OutletSwitchedControlCommand.
    Source version and references

    Downloaded: 2026-10-24T02:14:27.572142+00:00.

Current Registration Authority (inferred from ancestor 1.3.6.1.4.1.63131)

INOVA DC

Siblings (4)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.63131.1.1.26.9.2.4.1.1 rPDU2OutletSwitchedControlIndex00
1.3.6.1.4.1.63131.1.1.26.9.2.4.1.2 rPDU2OutletSwitchedControlModule00
1.3.6.1.4.1.63131.1.1.26.9.2.4.1.3 rPDU2OutletSwitchedControlName00
1.3.6.1.4.1.63131.1.1.26.9.2.4.1.4 rPDU2OutletSwitchedControlNumber00