Status in source: current.
Technical details
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"tnShelfHighVoltageThreshold",
"OBJECT-TYPE",
"SYNTAX",
"Unsigned32",
"(",
"0",
".",
".",
"8500",
")",
"UNITS",
[
"literal",
"22312f31303020766f6c747322"
],
"MAX-ACCESS",
"read-create",
"STATUS",
"current",
"DESCRIPTION",
"\"Shelf high voltage threshold. Default is depending on value of tnShelfExpectedVolts: v48 - 5700 v60 - 7200. Current configurable values: 0 to 8500, in increments of 50.\"",
"::=",
"{",
"tnShelfEntry",
"22",
"}"
],
"syntax_tree": [
[
"ApplicationSyntax",
"Unsigned32",
[
"integerSubType",
[
[
0,
8500
]
]
]
],
[
"UNITS",
"1/100 volts"
],
[
"MaxAccessPart",
"read-create"
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"Shelf high voltage threshold. Default is depending on value of tnShelfExpectedVolts: v48 - 5700 v60 - 7200. Current configurable values: 0 to 8500, in increments of 50."
],
null,
null,
null,
null
]
}