MODBUS HR 40256: BIC Alarm Status. 40256:00 Alarm 40256:01 DiagnosticMode 40256:02 Isolation position sensor error 40256:03 ATS position switch error 40256:04 BTS transfer timeout (100mS) 40256:05 BPS position switch error 40256:06 PS voltage error (5V or 24V) 40256:07 Rack between States 40256:08 Voltage sense error 40256:09 Coil Control voltage error 40256:10 Shorted source 40256:11 Button Stuck (> 1 minute) 40256:12 Ats Inibit Alarm
Sources for this description