OID reference

upsSmartBatteryTemperature

1.3.6.1.4.1.935.1.1.1.2.2.3

Description

The current internal UPS temperature expressed in tenths of a Celsius degree.

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.935.1.1.1.2.2 (upsSmartBattery)
Node code
3
Node name
upsSmartBatteryTemperature
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.935.1.1.1.2.2.3
URN notation
urn:oid:1.3.6.1.4.1.935.1.1.1.2.2.3
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 935 1 1 1 2 2 3}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsBatteryp(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsBattery(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsBatteryp(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsBattery(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsBatteryp(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsBattery(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsBatteryp(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsBattery(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsBatteryp(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsBattery(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsBatteryp(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsBattery(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsBatteryp(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsBattery(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsBatteryp(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsBattery(2) upsSmartBattery(2) upsSmartBatteryTemperature(3)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/935/1/1/1/2/2/3
  • /ISO/Identified-Organization/6/1/4/1/935/1/1/1/2/2/3
  • /ISO/3/6/1/4/1/935/1/1/1/2/2/3
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/935/1/hardware/ups/upsBatteryp/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprise/935/1/hardware/ups/upsBattery/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprise/935/products/hardware/ups/upsBatteryp/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprise/935/products/hardware/ups/upsBattery/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/1/hardware/ups/upsBatteryp/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/1/hardware/ups/upsBattery/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/products/hardware/ups/upsBatteryp/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/products/hardware/ups/upsBattery/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprises/935/1/hardware/ups/upsBatteryp/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprises/935/1/hardware/ups/upsBattery/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprises/935/products/hardware/ups/upsBatteryp/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprises/935/products/hardware/ups/upsBattery/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/1/hardware/ups/upsBatteryp/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/1/hardware/ups/upsBattery/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/products/hardware/ups/upsBatteryp/upsSmartBattery/upsSmartBatteryTemperature
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/products/hardware/ups/upsBattery/upsSmartBattery/upsSmartBatteryTemperature
  • Additional combinations skipped.

SNMP properties

Value type
INTEGER
Maximum access defined by MIB
read-only
Status in MIB
mandatory

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.935.1.1.1.2.2.3.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

Available source records contain 2 distinct definitions; some records may not include a definition.

Show 2 published definitions

upsSmartBatteryTemperature · mandatory

upsSmartBatteryTemperature OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current internal UPS temperature expressed in tenths of
                a Celsius degree."
   ::= { upsSmartBattery 3 }

upsSmartBatteryTemperature · mandatory

upsSmartBatteryTemperature OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current internal UPS temperature expressed in tenths of
		 a Celsius degree."
	::= { upsSmartBattery 3 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

The current internal UPS temperature expressed in tenths of a Celsius degree.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)Reviewed vendor MIB copies in Fujitsu ServerViewCommon and standard MIB copies (LibreNMS/Observium Community)Netdisco MIB archive copies

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; representative source files are shown for each definition.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Reviewed vendor MIB copies in Fujitsu ServerView, and others1 record · 5 sources

Description 1

upsSmartBatteryTemperature · mandatoryMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Reviewed vendor MIB copies in Fujitsu ServerView, and others5 sources

Status in source: mandatory.

Names: upsSmartBatteryTemperature

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "upsSmartBatteryTemperature",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "ACCESS",
    "read-only",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"The current internal UPS temperature expressed in tenths of a Celsius degree.\"",
    "::=",
    "{",
    "upsSmartBattery",
    "3",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER"
    ],
    null,
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "The current internal UPS temperature expressed in tenths of a Celsius degree."
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.935)

An-Hsiang Tu

Siblings (6)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.935.1.1.1.2.2.1 upsSmartBatteryCapacity00
1.3.6.1.4.1.935.1.1.1.2.2.2 upsSmartBatteryVoltage00
1.3.6.1.4.1.935.1.1.1.2.2.4 upsSmartBatteryRunTimeRemaining00
1.3.6.1.4.1.935.1.1.1.2.2.5 upsSmartBatteryReplaceIndicator00
1.3.6.1.4.1.935.1.1.1.2.2.6 upsSmartBatteryFullChargeVoltage00
1.3.6.1.4.1.935.1.1.1.2.2.7 upsSmartBatteryCurrent00