OID reference

upsSmartConfigLowTransferVolt

1.3.6.1.4.1.935.1.1.1.5.2.3

Description

The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units a…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.935.1.1.1.5.2 (upsSmartConfig)
Node code
3
Node name
upsSmartConfigLowTransferVolt
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.935.1.1.1.5.2.3
URN notation
urn:oid:1.3.6.1.4.1.935.1.1.1.5.2.3
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 935 1 1 1 5 2 3}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsConfig(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsConfig(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsConfig(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsConfig(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsConfig(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsConfig(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsConfig(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsConfig(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/935/1/1/1/5/2/3
  • /ISO/Identified-Organization/6/1/4/1/935/1/1/1/5/2/3
  • /ISO/3/6/1/4/1/935/1/1/1/5/2/3
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/935/1/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/935/1/hardware/ups/upsConfig/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/935/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/935/products/hardware/ups/upsConfig/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/1/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/1/hardware/ups/upsConfig/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/products/hardware/ups/upsConfig/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/935/1/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/935/1/hardware/ups/upsConfig/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/935/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/935/products/hardware/ups/upsConfig/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/1/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/1/hardware/ups/upsConfig/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/products/hardware/ups/upsConfig/upsSmartConfig/upsSmartConfigLowTransferVolt
  • Additional combinations skipped.

SNMP properties

Value type
INTEGER
Maximum access defined by MIB
read-write
Status in MIB
mandatory

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.935.1.1.1.5.2.3.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

Available source records contain 2 distinct definitions; some records may not include a definition.

Show 2 published definitions

upsSmartConfigLowTransferVolt · mandatory

upsSmartConfigLowTransferVolt OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The minimum line voltage in 1/10 VAC allowed before the
                UPS system transfers to battery backup.
                                
                Allowable values depend on the UPS used:
                120 Volt units allow settings of  970, 1000, 1030, 1060.
                100 Volt units allow settings of 810, 830, 850, 870.
                230 Volt units allow settings of 1880, 1960, 2040, 2080.
                208 Volt units allow settings of 1680, 1720, 1770, 1820.
                                
                If a value other than a supported value is provided in a
                set request, the UPS interprets it as a the next higher
                acceptable value.  If the provided value is higher than
                the highest acceptable value, the highest acceptable
                value is used."
   ::= { upsSmartConfig 3 }

upsSmartConfigLowTransferVolt · mandatory

upsSmartConfigLowTransferVolt OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The minimum line voltage in 1/10 VAC allowed before the
		 UPS system transfers to battery backup.

		 Allowable values depend on the UPS used:
		 120 Volt units allow settings of  970, 1000, 1030, 1060.
		 100 Volt units allow settings of 810, 830, 850, 870.
		 230 Volt units allow settings of 1880, 1960, 2040, 2080.
		 208 Volt units allow settings of 1680, 1720, 1770, 1820.

		 If a value other than a supported value is provided in a
		 set request, the UPS interprets it as a the next higher
		 acceptable value.  If the provided value is higher than
		 the highest acceptable value, the highest acceptable
		 value is used."
	::= { upsSmartConfig 3 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)Reviewed vendor MIB copies in Fujitsu ServerViewCommon and standard MIB copies (LibreNMS/Observium Community)Netdisco MIB archive copies

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; representative source files are shown for each definition.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Reviewed vendor MIB copies in Fujitsu ServerView, and others1 record · 5 sources

Description 1

upsSmartConfigLowTransferVolt · mandatoryMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Reviewed vendor MIB copies in Fujitsu ServerView, and others5 sources

Status in source: mandatory.

Names: upsSmartConfigLowTransferVolt

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "upsSmartConfigLowTransferVolt",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "ACCESS",
    "read-write",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.\"",
    "::=",
    "{",
    "upsSmartConfig",
    "3",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER"
    ],
    null,
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used."
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.935)

An-Hsiang Tu

Siblings (11)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.935.1.1.1.5.2.1 upsSmartConfigRatedOutputVoltage00
1.3.6.1.4.1.935.1.1.1.5.2.2 upsSmartConfigHighTransferVolt00
1.3.6.1.4.1.935.1.1.1.5.2.4 upsSmartConfigAlarm00
1.3.6.1.4.1.935.1.1.1.5.2.5 upsSmartConfigAlarmTimer00
1.3.6.1.4.1.935.1.1.1.5.2.6 upsSmartConfigMinReturnCapacity00
1.3.6.1.4.1.935.1.1.1.5.2.7 upsSmartConfigSensitivity00
1.3.6.1.4.1.935.1.1.1.5.2.8 upsSmartConfigLowBatteryRunTime00
1.3.6.1.4.1.935.1.1.1.5.2.9 upsSmartConfigReturnDelay00
1.3.6.1.4.1.935.1.1.1.5.2.10 upsSmartConfigShutoffDelay00
1.3.6.1.4.1.935.1.1.1.5.2.11 upsSmartConfigUpsSleepTime00
1.3.6.1.4.1.935.1.1.1.5.2.12 upsSmartConfigSetEEPROMDefaults00